Plan Review Details - Permit 04110381
Plan Review Stops For Permit 04110381
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-01-18 Cont ID  
Sent By lsmith Date 2005-01-18 Time 14:00 Rev Time 1.50
Received By lsmith Date 2005-01-18 Time 14:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-01-03 Cont ID  
Sent By lsmith Date 2005-01-03 Time 11:55 Rev Time 3.00
Received By lsmith Date 2005-01-03 Time 08:58 Sent To  
Notes
2005-01-03 00:00:00BUILDING PLAN REVIEW: FAILED
  
 1. PLANS MUST BE TAKEN TO PBC AND
 IMPACT
 FEES PAID.THE RECEIPT MUST BE
 SUBMITTED BEFORE A PERMIT CAN BE
 PRINTED. THE PLANS WILL BE STAMPED BY
 PBC.
  
 2. "H" WINDOWS LIVING ROOM:
 THESE STOREFRONT WINDOWS ARE NOT
 IMPACT WINDOWS. STORM PANELS MUST BE
 INSTALLED.SUBMIT THE DRAWING FOR THE
 STORM PANELS.
  
 3. THE SITE SPECIFIC PRODUCT APPROVAL
 FORM LISTS NATIONAL ACCREDITATION &
 MGM.
 AS THE THIRD PARTY QUALITY ASSURANCE
 BUT
 MIAMI-DADE COUNTY PRODUCT APPROVAL WAS
 SUBMITTED FOR ARCH ALUMINUM & GLASS CO.
 FOR THE 5 STOREFRONT WINDOWS IN THE
 LIVING ROOM.THE ENGINEER DRAWING SHOWS
 DESIGN PRESSURE +30.7, -33.4.THESE DO
 NOT AGREE WITH THE WINDOW SCHEDULE ON
 SHEET A2.
  
 4. THE SITE SPECIFIC FORM FOR THE BUTT
 GLASS ASSEMBLY IN THE CAFE IS STILL NOT
 COMPLETED. IT APPEARS YOU PHOTOCOPIED
 THE FORM FROM THE STOREFRONT WINDOWS IN
 THE LIVING ROOM. SINCE THESE ARE SITE
 SPECIFIC YOU MUST SUBMIT COPIES OF THE
 REPORTS FROM THE TESTING AGENCY
 (MIAMI-DADE). THE NAME OF THE PRODUCT
 MUST BE ENTERED ON THE FORM (LINE 8)
  
 5. THE FORM "LETTER OF INTENT" THOMAS
 M.
 KELAHER, P.E. SHOULD BE HAND DATED WHEN
 HE SIGNS & SEALS IT.ALSO THE LOT
 NUMBER MUST BE FILLED IN.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-12-02 Cont ID  
Sent By lsmith Date 2004-12-02 Time 15:02 Rev Time 3.50
Received By lsmith Date 2004-12-02 Time 11:27 Sent To  
Notes
2004-12-02 00:00:00BUILDING PLAN REVIEW: FAILED
  
 1. SQ. FT. OF HOUSE HAS BEEN CORRECTED
 TO INCLUDE THE UNCONDITIONED AREAS.
 TOTAL SQ. FT. IS 6027 PER SHEET A-2 OF
 THE ARCH. PLANS.
  
 2. PLANS MUST BE TAKEN TO PBC AND IMPACT
 FEES PAID.THE RECEIPT MUST BE
 SUBMITTED BEFORE A PERMIT CAN BE
 ISSUED.
  
 3.SUBMIT THE FL PRODUCT APPROVAL FOR THE
 STOREFRONT PANELS SHOWN AS "H" ON WINDOW
 SCHEDULE.
  
 4. SUBMIT THE MANUFACTURERS
 SPECIFICATIONS FOR THE GAS FIREPLACE IN
 THE LIVING ROOM.
  
 5. THE SITE SPECIFIC DOCUMENTS FOR THE
 BUTT GLASS ASSEMBLY IS MISSING THE ARCH
 ALUMINUM PRODUCT APPROVAL. LINE 1 FOR
 THE APPROVAL BY METHOD 1 OR 2 HAS NOT
 BEEN FILLED IN.THE LETTER OF INTENT BY
 THE ENGINEER DATED 6/29/2004 IS MISSING
 THE LEGAL INFORMATION FOR LOT 37.
  
 6. THE ENGINEER HAS SUBMITTED 8 1/2 X 11
 DETAILS FOR A SERIES OF WINDOWS 30" WIDE
 X 107" HIGH. NO PRODUCT APPROVAL WAS
 ATTACHED. HE REFERENCES ARCH ALUMINUM
 SERIES 3000 WITH A NOA 01-0329.02
 EXPIRES 5/28/06. IF THIS IS THE SERIES
 OF WINDOWS MARKED AS "H" ON THE PLANS
 SUBMIT THE SUPPORTING DOCUMENTS. PLANS
 SHOW THEY ARE MULLED TOGETHER. IF THERE
 IS NO FLORIDA PRODUCT APPROVAL AVAILABLE
 THEN A SITE SPECIFIC/LOCAL APPLICATION
 WILL HAVE TO BE SUBMITTED WITH THE NOA.
  
 SITE SPECIFIC APPLICATION FOR ANOTHER
 LOT WAS INCLUDED IN PERMIT PACKAGE
 (L21)
  
 7. DUPLICATE COPIES OF PRODUCT APPROVALS
 WERE SUBMITTED.ONLY SUBMIT 2 COPIES
 EVEN IF THE PRODUCT IS USED IN SEVERAL
 AREAS OF THE HOUSE.
  
 8. SUBMIT FLORIDA PRODUCT APPROVALS FOR
 THE STRUCTURAL COMPONENTS. SEE SHEET A7
 USP & SIMPSON TRUSS STRAPS, ETC.
  
 9. SEE OTHER PLAN REVIEWERS' NOTES
 REGARDING THE ARCHITECT SEAL.
  
 10. THE LETTER FROM MAURICE MENASCHE FOR
 STRUCTURAL REVIEW REFERENCES L 30 AT
 HAWKS LANDING INSTEAD OF L. 37.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-10-03 Cont ID  
Sent By dpalmer Date 2005-10-03 Time 10:12 Rev Time 0.33
Received By dpalmer Date 2005-10-03 Time 10:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-06-21 Cont ID  
Sent By dpalmer Date 2005-06-21 Time 10:10 Rev Time 0.00
Received By dpalmer Date 2005-06-21 Time 10:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-06-07 Cont ID  
Sent By dpalmer Date 2005-06-07 Time 09:42 Rev Time 0.30
Received By dpalmer Date 2005-06-07 Time 09:15 Sent To  
Notes
2005-06-07 00:00:00****** UNSAT *******
  
 1)NOTE: PLEASE SEE 424.3B FOR MIN OCP OF
 AHU HEAT.
 PLEASE ALSO SEE 60A OCP FOR 7.5KW.
 MIN 125%
  
 2)NOTE: PLEASE SEE RISER, PLEASE SEE
 MISSING EQUIPMENT GROUNDING CONDUCTOR
 FROM PANEL"A" TO POOL SUB PANEL.
 PLEASE ALSO SEE RISER IS MISSING
 REQUIRED NEUTRAL FOR SAME PANEL.
 250.24,250.110,250.122 ETC.
  
 3)NOTE: PLEASE SEE MANY ITEMS ARE SHOWN
 AS OPTIONAL ON PLANS. PLANS NEED TO
 REFLECT ACTUAL INSTALLATION OF PROJECT.
 ROUGH INSPECTIONS HAVE ALREADY BEEN
 PASSED.
 PLEASE SEE ORIGINAL PLANS WERE STAMPED
 "ALL REVSIONS AND OPTIONS ARE TO BE
 SUBMITTED AND REVIEWED BEFORE ROUGH
 INSPECTION"
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-12-29 Cont ID  
Sent By dpalmer Date 2004-12-29 Time 14:30 Rev Time 0.33
Received By dpalmer Date 2004-12-29 Time 14:05 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-11-12 Cont ID  
Sent By dpalmer Date 2004-11-12 Time 21:49 Rev Time 0.33
Received By dpalmer Date 2004-11-12 Time 21:49 Sent To M
Notes
2004-11-12 00:00:00********* UNSAT *************
  
 1)NOTE: PLEASE SEE PLANS FOR SOME
 MISSING RECEPTS PER 210.52, 2' OF WALL
 SPACE/
 PLEASE ALSO SEE KITCHEN COUNTERSPACE
 WHICH MAY REQUIRE GFI 12" OR MORE
 210.52C1
  
 2)NOTE: PLEASE SEE HI-HAT LOADS ARE
 BASED ON MAX WATTAGE FOR A FIXTURE.
 MOST RECESSED AIR LOCK CANS ARE 75W
 RATED. 220.3B4
 TYPE OF FIXTURE NOT SUPPLIED, THIS IS
 ONLY A NOTE>
  
 3)NOTE: PLEASE SEE RASIED SEAL IS NOT
 CLEAR AND VISABLE AS REQUIRED UNDER FS
 481.221, FAC 61G1-16
 TRIED TO SHADOW SEAL WITH PENCIL,
 HOWEVER THIS WOULD NOT PROVIDE A CLEAR
 SEAL WITH INFORMATION ON SEAL.
 PLEASE SEE THIS IS REQUIRED ON ALL
 SHEETS WHEATHER OR NOT COMMENT IS MADE
 BY OTHER REVIEWERS.
  
 PLEASE SEE ONE SET OF PLANS HAS SOME OF
 THE ABOVE ITEMS REDLINED FOR LOCATIONS/
 CLARITY.
  
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-09-27 Cont ID  
Sent By adarroug Date 2005-09-27 Time 09:58 Rev Time 0.00
Received By adarroug Date 2005-09-27 Time 09:58 Sent To E
Notes
2005-09-27 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-06-15 Cont ID  
Sent By shill Date 2005-06-15 Time 15:08 Rev Time 0.00
Received By shill Date 2005-06-15 Time 15:06 Sent To E
Notes
2005-06-15 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-05-31 Cont ID  
Sent By adarroug Date 2005-05-31 Time 11:22 Rev Time 0.00
Received By adarroug Date 2005-05-31 Time 11:22 Sent To E
Notes
2005-05-31 00:00:00TO "DPALMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-01-12 Cont ID  
Sent By mjacobs Date 2005-01-12 Time 11:16 Rev Time 0.00
Received By mjacobs Date 2005-01-12 Time 11:16 Sent To B
Notes
2005-01-12 00:00:00TO "LS" DESK./RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-12-29 Cont ID  
Sent By mjacobs Date 2004-12-29 Time 07:21 Rev Time 0.00
Received By mjacobs Date 2004-12-29 Time 07:21 Sent To E
Notes
2004-12-29 00:00:00TO "DP" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-12-21 Cont ID  
Sent By mjacobs Date 2004-12-21 Time 13:29 Rev Time 0.00
Received By mjacobs Date 2004-12-21 Time 13:29 Sent To Z
Notes
2004-12-21 00:00:00SENT TO "Z"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-29 Cont ID  
Sent By lsmith Date 2004-12-02 Time 14:30 Rev Time 0.00
Received By lsmith Date 2004-11-12 Time 16:07 Sent To  
Notes
2004-11-12 00:00:00TO SFD RACK/E
2004-11-08 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-11-18 Cont ID  
Sent By drunnels Date 2004-11-18 Time 14:03 Rev Time 1.00
Received By drunnels Date 2004-11-18 Time 14:02 Sent To P
Notes
2004-11-18 00:00:00PAT RAFTER

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-01-01 Cont ID  
Sent By jleech Date 2005-01-01 Time 10:15 Rev Time 0.33
Received By jleech Date 2005-01-01 Time 10:14 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-11-22 Cont ID  
Sent By kstevens Date 2004-11-22 Time 05:07 Rev Time 0.25
Received By kstevens Date 2004-11-22 Time 05:07 Sent To B1
Notes
2004-11-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT A-1 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS.
 A) THE BIDET REQUIRES A TRAP PER
 SECTION 1002.1
 B) BIDET IS NOT VENTED PER SECTION
 901.2.1. EITHER TIE IN ON THE VENTED
 BLDG BRANCH LINE, TO CONNECT TO A STACK
 VENT.
 2) FAC 61G1-16.003(1) THE SEAL SHALL
 CONTAIN THE NAME OF THE ARCHITECT, AND
 THE REGISTRATION NUMBER, ALONG WITH THE
 WORDS "STATE OF FLORIDA" AND ARCHITECT.
 NONE OF THIS CAN BE SEEN ON THE SEAL.
 FS 481.221
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2004-12-28 Cont ID  
Sent By mmclean Date 2004-12-28 Time 16:53 Rev Time 0.00
Received By mmclean Date 2004-12-28 Time 16:53 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2004-11-10 Cont ID  
Sent By mmclean Date 2004-11-10 Time 16:09 Rev Time 0.00
Received By mmclean Date 2004-11-10 Time 16:09 Sent To I
Notes
2004-11-10 00:00:00NOTE: DENIED, NEED TO HAVE THE REF
 CHANGED TO AN UNDER COUNTER REF.CALLED
 CONTRACTOR MM