Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-12-07 Cont ID  
Sent By dpalmer Date 2004-12-07 Time 08:46 Rev Time 0.25
Received By dpalmer Date 2004-12-07 Time 08:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-11-12 Cont ID  
Sent By dpalmer Date 2004-11-12 Time 17:04 Rev Time 0.25
Received By dpalmer Date 2004-11-12 Time 17:04 Sent To  
Notes
2004-11-12 00:00:00*********** UNSAT ************
  
 1)NOTE: PLEASE INCLUDE SEC'S ON RISER
 DIAGRAM.
 215.5,310.16
  
 2)NOTE: PLEASE INCLUDE GRND RDS AND CWP
 MIN FOR GROUNDING ELECTRODE SYSTEM.
 250.50
  
  
 3) NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 4)NOTE: PLEASE INCLUDE PRINTED NAME AND
 SIGNATURE OF PERSON RESPONSIBLE FOR
 PLANS/DRAWINGS.
 FBC 104.2.1
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
 ****** NOTE***
 TRIED TO CALL CONTRACTOR ON # LISTED ON
 APPLICATION. (848-7881) 8-TIMES. THEN
 TRIED TO CALL ON OLD # 640-0400. BOTH
 #'S RANG BUSY FOR 1 1/2 HRS???

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-12-01 Cont ID  
Sent By mjacobs Date 2004-12-01 Time 18:29 Rev Time 0.00
Received By mjacobs Date 2004-12-01 Time 18:29 Sent To E
Notes
2004-12-01 00:00:00SENT TO "DP" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-11-05 Cont ID  
Sent By csiegber Date 2004-11-05 Time 16:29 Rev Time 0.00
Received By csiegber Date 2004-11-05 Time 16:29 Sent To E
Notes
***NONE***