Plan Review Details - Permit 04110353
| Plan Review Stops For Permit 04110353 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2004-12-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-12-07 |
Time |
08:46 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2004-12-07 |
Time |
08:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-11-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-11-12 |
Time |
17:04 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2004-11-12 |
Time |
17:04 |
Sent To |
|
|
| Notes |
| 2004-11-12 00:00:00 | *********** UNSAT ************ | | | | | | 1)NOTE: PLEASE INCLUDE SEC'S ON RISER | | | DIAGRAM. | | | 215.5,310.16 | | | | | | 2)NOTE: PLEASE INCLUDE GRND RDS AND CWP | | | MIN FOR GROUNDING ELECTRODE SYSTEM. | | | 250.50 | | | | | | | | | 3) NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | | | | 4)NOTE: PLEASE INCLUDE PRINTED NAME AND | | | SIGNATURE OF PERSON RESPONSIBLE FOR | | | PLANS/DRAWINGS. | | | FBC 104.2.1 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | | | | ****** NOTE*** | | | TRIED TO CALL CONTRACTOR ON # LISTED ON | | | APPLICATION. (848-7881) 8-TIMES. THEN | | | TRIED TO CALL ON OLD # 640-0400. BOTH | | | #'S RANG BUSY FOR 1 1/2 HRS??? |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-12-01 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2004-12-01 |
Time |
18:29 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2004-12-01 |
Time |
18:29 |
Sent To |
E |
|
| Notes |
| 2004-12-01 00:00:00 | SENT TO "DP" DESK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-11-05 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-11-05 |
Time |
16:29 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-11-05 |
Time |
16:29 |
Sent To |
E |
|
| Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy