Plan Review Details - Permit 04110346
Plan Review Stops For Permit 04110346
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-03-22 Cont ID  
Sent By rbrown Date 2005-03-22 Time 08:42 Rev Time 0.00
Received By rbrown Date 2005-03-22 Time 08:42 Sent To  
Notes
2005-03-22 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 --PROVISO--
 489.103 F.S. SHEET S-1, STRUCTURAL PLAN.
 CUTTING/REINSTATEMENT OF THE ROOF AND
 FLOOR SLABS IS OUTSIDE THE SCOPE OF
 LICENSURE FOR THE MECHANICAL AND
 ELECTRICAL CONTRACTORS.THIS WORK SHALL
 BE SUB-CONTRACTED TO A LICENSED GENERAL
 CONTRACTOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-03-17 Cont ID  
Sent By rbrown Date 2005-03-17 Time 15:29 Rev Time 0.00
Received By rbrown Date 2005-03-17 Time 15:29 Sent To  
Notes
2005-03-17 00:00:00BUILDING PLAN REVIEW
 ******DENIED********
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 SHEET S-1, FOUNDATION PLAN WAS PASSED
 WITH PROVISO AND STAMPED AFTER THE LAST
 REVIEW.WHEN THE PLANS WERE
 RESUBMITTED, TO ADDRESS THE ELECTRICAL
 PLAN REVIEW COMMENTS, ONLY ONE COPY OF
 SHEET S-1 WAS INCLUDED.SUBMIT THE
 OTHER COPY OR TWO NEW COPIES (OMITTING
 THE ROOF FRAMING DETAILS) OF SHEET S-1.
  
 --PROVISO FROM LAST REVIEW--
 489.103 F.S. SHEET S-1, STRUCTURAL PLAN.
 CUTTING/REINSTATEMENT OF THE ROOF AND
 FLOOR SLABS IS OUTSIDE THE SCOPE OF
 LICENSURE FOR THE MECHANICAL AND
 ELECTRICAL CONTRACTORS.THIS WORK SHALL
 BE SUB-CONTRACTED TO A LICENSED GENERAL
 CONTRACTOR.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-12-08 Cont ID  
Sent By rbrown Date 2004-12-08 Time 16:17 Rev Time 0.00
Received By rbrown Date 2004-12-08 Time 16:17 Sent To  
Notes
2004-12-08 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 --PROVISO--
 489.103 F.S. SHEET S-1, STRUCTURAL PLAN.
 CUTTING/REINSTATEMENT OF THE ROOF AND
 FLOOR SLABS IS OUTSIDE THE SCOPE OF
 LICENSURE FOR THE MECHANICAL AND
 ELECTRICAL CONTRACTORS.THIS WORK SHALL
 BE SUB-CONTRACTED TO A LICENSED GENERAL
 CONTRACTOR.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-02-15 Cont ID  
Sent By dpalmer Date 2005-02-15 Time 04:04 Rev Time 0.30
Received By dpalmer Date 2005-02-15 Time 04:04 Sent To  
Notes
2005-02-15 00:00:00***
 VALUE FOR SCOPE OF WORK TO BE INCREASED
 FOR COMPLETE SCOPE OF WORK.
 NO CONTRACT INFORMATION PROVIDED.
 VALUE TO INCLUDE:
 ALL ELECTRICAL ASSOCIATED WITH
 INSTALLATION OF NEW GEN/ ATS/DISC'S ETC.
 GENERATOR,AND ALL ELECTRICAL EQUIPMENT.
 NEW DIEISEL FIRE PUMP.
 PLUMB/MECH WORK.
  
  
 VALUE SHOWN AT $155K AT THIS TIME.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-11-29 Cont ID  
Sent By dpalmer Date 2004-11-29 Time 08:03 Rev Time 1.00
Received By dpalmer Date 2004-11-29 Time 07:40 Sent To  
Notes
2004-11-29 00:00:00******* UNSAT ********
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002 FOR
 MISSING LICENSE INFORMATION REQUIRED ON
 TITLE BLOCKS. PLEASE SEE FS 471.023 FOR
 REQUIRED CA #.
 THIS IS REQUIRED ON ALL SHEETS AND FOR
 ALL TRADES WHEATHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWERS. MECH/FIRE
 STAMPS HAVE BEEN VOIDED.
 PLEASE PROVIDE NEW SHEETS FOR TRADES.
  
 2)NOTE: PLEASE PROVIDE COPY OF
 COMPPLETE
 CONTRACT FOR SCOPE OF WORK. VALUE IS TO
 BE BASED ON LABOR AND MATERIALS. THIS
 WOULD INCLUDE GEN ETC. EVEN IF OWNER
 SUPPLIED. FBC 104.6.5.
 VALUE SHOWN AT $155K.
 IF VALUE SHOWN ON ELECTRICAL PERMIT
 APPLICATION IS TO BE ADDED TO MECH
 PERMIT APPLICATION , PLEASE ADJUST MECH
 PERMIT APPLICATION.
  
 3)NOTE: PLEASE ALSO SUBMIT MANUFACT.
 SPECS ON NEW TRANSFER SWITCH.
  
 4)NOTE: PLEASE SEE # OF CONDUCTORS FROM
 ATS -2 TO NEW DISC(CODED NOTES #10).
 SHOWN AS 3-POLE DISC'S AND EQUIPMENT,
 HOWEVER ONLY 3- CONDUCTORS ARE SHOWN.
 PLEASE SEE 240.4C, 240.21 FOR SIZING OF
 CONDUCTORS AND TERMINATION INTO 400A
 DISC FROM 1000A OCP.
 PLEASE VERIFY THE ABOVE.
  
 5)NOTE: PLEASE VERIFY GFI PROTECTION ON
 GENERATOR PER 240.13,230.95.
 EXISTING EM MAIN, DOES INDICATE GFI
 PROTECTION.
  
 6)NOTE: PLEASE VERIFY , RISER INDICATES
 NEW TRANSFER SWITCH (FORMERLY FIRE
 PUMP)? IS FIRE PUMP FEED BEING REMOVED?
 IS THERE ALREADY A NEW FEED FOR FIRE
 PUMP?
 PLEASE VERIFY.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-03-10 Cont ID  
Sent By mcarsill Date 2005-03-10 Time 15:49 Rev Time 0.00
Received By mcarsill Date 2005-03-10 Time 15:49 Sent To  
Notes
2005-03-10 00:00:001. WHEN THE REQUIRED EXISTING FIRE
 PUMP IS REMOVED, AN APPROVED FIRE
 WATCH WILL BE REQUIRED FOR THE
 BUILDING. PROPER NOTIFICATION IS TO
 OCCUR WHEN THE FIRE PUMP IS TAKEN
 OFF-LINE OR REMOVED FROM THE
 BUILDING.
  
 2. EMERGENCY GENERATOR INSTALLATION
 TO COMPLY WITH NFPA 110.
  
 3. THE EXHAUST FROM THE GENERATOR
 SHALL NOT RE-ENTER THE BUILDING. NO
 BACK FEEDING OF VAPORS ARE TO OCCUR.
  
 4. NEW DAY TANK IS TO BE PROPERLY
 LABELED WITH STICKERS INDICATING
 THE PRODUCT NAME, NO SMOKING, ETC.
  
 5. THE NEW FIRE PUMP WHEN INSTALLED
 SHALL BE INSPECTED, TESTED, AND
 APPROVED BY THE FIRE PREVENTION
 BUREAU TO ENSURE PROPER OPERATION.
  
 6. FIRE PUMP INSTALLATION TO COMPLY
 WITH NFPA 20.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-11-23 Cont ID  
Sent By nmccray Date 2004-11-23 Time 16:14 Rev Time 0.00
Received By nmccray Date 2004-11-23 Time 16:14 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-03-11 Cont ID  
Sent By adarroug Date 2005-03-11 Time 15:06 Rev Time 0.00
Received By adarroug Date 2005-03-11 Time 15:05 Sent To B
Notes
2005-03-11 00:00:00TO RBROWN DESK/TAKEN OFF BD#41

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-03-22 Cont ID  
Sent By pkrauss Date 2005-03-22 Time 08:56 Rev Time 0.00
Received By pkrauss Date 2005-02-09 Time 12:14 Sent To  
Notes
2005-02-09 00:00:00ORIGINAL OR DUPLICATE PERMIT REQUIRED
 PRIOR TO PERMIT BEING ISSUED

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-02-11 Cont ID  
Sent By pkrauss Date 2004-12-08 Time 08:20 Rev Time 0.00
Received By pkrauss Date 2004-11-05 Time 14:36 Sent To  
Notes
2004-11-24 00:00:00SENT TO "COMM" BD#14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-11-05 Cont ID  
Sent By csiegber Date 2004-11-05 Time 14:27 Rev Time 0.00
Received By csiegber Date 2004-11-05 Time 14:27 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-05-18 Cont ID  
Sent By hmoser Date 2005-05-18 Time 15:20 Rev Time 0.00
Received By hmoser Date 2005-05-18 Time 15:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-02-11 Cont ID  
Sent By pkrauss Date 2005-02-11 Time 07:51 Rev Time 0.40
Received By pkrauss Date 2005-02-11 Time 07:15 Sent To  
Notes
2005-02-11 00:00:00PROVISO:
 THE GENERATOR EXHAUST SHALL TERMINATE IN
 SUCH A MANNER THAT TOXIC FUMES CANNOT
 REENTER A BUILDING OR STRUCTURE THROUGH
 DOORS, WINDOWS, AIR INTAKES OR THE
 ENGINE AIR INTAKE SYSTEM.NFPA 110
 SECTION 7.10.2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-11-22 Cont ID  
Sent By pkrauss Date 2004-11-22 Time 11:38 Rev Time 0.55
Received By pkrauss Date 2004-11-22 Time 11:05 Sent To FIRE
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-03-09 Cont ID  
Sent By kstevens Date 2005-03-09 Time 17:37 Rev Time 0.50
Received By kstevens Date 2005-03-09 Time 17:37 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy