Plan Review Details - Permit 04110306
Plan Review Stops For Permit 04110306
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-11-18 Cont ID  
Sent By dpalmer Date 2004-11-18 Time 08:12 Rev Time 0.50
Received By dpalmer Date 2004-11-18 Time 08:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-11-12 Cont ID  
Sent By dpalmer Date 2004-11-12 Time 16:55 Rev Time 0.25
Received By dpalmer Date 2004-11-12 Time 16:55 Sent To  
Notes
2004-11-12 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE SUBMIT A WIRING
 DIAGRAM/RISER FOR HOOK-UP OF NEW HEAT
 PUMP.
 PLEASE INCLUDE CONDUIT/WIRE SIZES. ETC.
 FROM EXISITNG PANEL? SIZE OF OCP.
 240.4, 310.16,215.5
  
 2)NOTE: PLEASE SUBMIT A LOAD CALCUALTION
 FOR SERVICE WITH NEW LOAD ADDED.220.31B
 PLEASE SHOW ALL CONTINUOUS LOADS AT
 125%
 230.42,215.3
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-11-05 Cont ID  
Sent By csiegber Date 2004-11-05 Time 14:30 Rev Time 0.00
Received By csiegber Date 2004-11-05 Time 14:30 Sent To E
Notes
***NONE***