Plan Review Details - Permit 04110302
Plan Review Stops For Permit 04110302
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-01-26 Cont ID  
Sent By alange Date 2005-01-26 Time 11:36 Rev Time 0.66
Received By alange Date 2005-01-26 Time 11:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-01-24 Cont ID  
Sent By alange Date 2005-01-24 Time 10:43 Rev Time 1.00
Received By alange Date 2005-01-24 Time 10:43 Sent To  
Notes
2005-01-24 00:00:00DENIED
  
 PRODUCT APPROVALS:
  
 I COMPLETED THE PRODUCT APPROVAL AND
 MADE 2 COMPLETE THE BEST I COULD.
 I AM STILL MISSING 2 COPIES OF
 MIAMI-DADE FOR PGT CASEMENT WINDOW.
 THE STATE APPROVALS FOR THESE WINOW IS
 ALSO MISSING PAGES 2 AND 3.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-11-29 Cont ID  
Sent By alange Date 2004-11-29 Time 16:29 Rev Time 2.50
Received By alange Date 2004-11-29 Time 14:47 Sent To Z
Notes
2004-11-29 00:00:00DENIED
  
  
 1.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2.SUBMIT TWO COMPLETE SETS OF PRODUCT
 APPROVALS FOR EXTERIOR DOORS, WINDOWS,
 MULLIONS,IMPACT PROTECTION, STRAPS AND
 TIE-DOWNS AND ROOFING.
 SUBMIT QUALITY ASSURANCE TESTING WITH
 THE FOLLOWING.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 3.SEE NOTES FROM OTHER REVIEWERS THAT
 MAY EFFECT ISSUING OF A PERMIT.
  
 4.SHOW TIE-IN FROM EXISITNG SLAB TO
 NEW SLAB.
  
  
 5.1015.2 HEIGHT. GUARDRAILS SHALL
 FORM A VERTICAL PROTECTIVE BARRIER NOT
 LESS THAN 42" HIGH.
 1015.3 OPENINGS. OPEN GUARDRAILS
 SHALL HAVE INTERMEDIATE RAILS OR ORNA-
 MENTAL PATTERNS SUCH AS A 4" DIAMETER
 SPHERE CAN NOT PASS THROUGH. A BOTTOM
 RAIL OR CURB SHALL BE PROVIDED THAT WILL
 REJECT THE PASSAGE OF 2" DIAMETER
 SPHERE.SHOW ON PLAN HOW THIS WILL
 COMPLY.
  
 6.SHOW ATTIC ACCESS COMPLYING WITH FBC
 2309.6.
  
 7.SHOW HOW BUILDING WILL COMPLY WITH
 FBC 3401.7.1.2.1
  
 8.FBC 1005.4.4 WINDOWS IN BEDROOM 4
 AND 5 DO NOT MEET EMERGENCY ESCAPE AND
 RESCUE OPENING REQUIREMENTS.
  
 9. SUBMIT 2 COPIES OF ENERGY CALCS
 COPLYING WWITH CH.13 FBC.
  
 10.SHOW ROOF AND WALL SHEATHING
 NAILING SCHEDULE.
  
 11.SHOW SMOKE DETECTORS COMPLYING WITH
 905.2 FOR BEDROOMS.
  
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-08-09 Cont ID  
Sent By dpalmer Date 2005-08-09 Time 06:42 Rev Time 0.50
Received By dpalmer Date 2005-08-04 Time 20:06 Sent To  
Notes
2005-08-09 00:00:00PANEL "B" SHOWN AS 200A MLO ON PANEL
 SCHEDULE AND 100A MLO ON RISER ?
2005-08-04 00:00:00IN ELEC FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-01-18 Cont ID  
Sent By dpalmer Date 2005-01-18 Time 14:12 Rev Time 0.50
Received By dpalmer Date 2005-01-18 Time 14:12 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-11-15 Cont ID  
Sent By dpalmer Date 2004-11-15 Time 07:00 Rev Time 0.25
Received By dpalmer Date 2004-11-15 Time 06:42 Sent To B
Notes
2004-11-15 00:00:00************ UNSAT *************
  
 1)NOTE: PLEASE SEE FAC 61G1-16.004 AND
 FAC 61G15-23.002 FIR MISSING INFORMATION
 REQUIRED ON TITLE BLOCKS FOR ARCH/
 ENGINEERING FIRMS.
 PLEASE ALSO SEE FS 481.219, 471.023.
 THIS IS REQUIRED ON ALL SHEETS AND FOR
 ALL TRADES WHEATHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWERS.
  
 2)NOTE: PLEASE SUBMIT ELECTRICAL PLANS
 FOR REMODEL AND ADDITION AS REQUIRED.
 MIN TO BE SHOWN FOR ELECTRICAL PER 2002
 NEC, FBC.
 PLEASE SEE COVER LIST ELECTRICAL PLANS
 YET NONE WERE IN SETS.
 PLEASE SEE CHAPTER 34 OF THE FBC FOR
 ADDITIONS AND RE-MODEL OD EXISTING
 DWELLINGS.
 SD'S AND GFI'S REQUIRED FOR ADDTIONS, IF
 RE-MODEL IS OVER 50%, BRINGING
 ELECTRICAL UP TO CODE WILL BE REQUIRED.
 3401.7.1.2.1,3401.7.2.6
 PLEASE SUBMIT ELECTRICAL PLANS.
 NEC 215.5,104.2.1,104.3.1,101.4.1
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected].
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2004-11-04 Time   Rev Time 0.00
Received By   Date 2004-11-04 Time   Sent To  
Notes
2004-11-04 00:00:00APPROVED PER SHERRY PILAND

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-08-03 Cont ID  
Sent By adarroug Date 2005-08-03 Time 10:28 Rev Time 0.00
Received By adarroug Date 2005-08-03 Time 10:27 Sent To E
Notes
2005-08-03 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-01-25 Cont ID  
Sent By mjacobs Date 2005-01-25 Time 10:21 Rev Time 0.00
Received By mjacobs Date 2005-01-25 Time 10:21 Sent To B
Notes
2005-01-25 00:00:00TO "AL" DESK/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-01-13 Cont ID  
Sent By mjacobs Date 2005-01-13 Time 15:55 Rev Time 0.00
Received By mjacobs Date 2005-01-13 Time 15:55 Sent To E
Notes
2005-01-13 00:00:00TO "DP" DESK./RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-06 Cont ID  
Sent By mjacobs Date 2005-01-06 Time 16:39 Rev Time 0.00
Received By mjacobs Date 2005-01-06 Time 16:39 Sent To Z
Notes
2005-01-06 00:00:00TO "Z" BOX./RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-11-05 Cont ID  
Sent By csiegber Date 2004-11-05 Time 13:24 Rev Time 0.00
Received By csiegber Date 2004-11-05 Time 13:24 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-01-29 Cont ID  
Sent By pschmitz Date 2005-01-29 Time 10:29 Rev Time 0.00
Received By pschmitz Date 2005-01-29 Time 10:29 Sent To PC
Notes
2005-01-29 00:00:00REVISION SUBMITTED,PLUMBING PERMIT
 # 05011335

Review Stop Z ZONING
Rev No 2 Status P Date 2005-01-13 Cont ID  
Sent By mmclean Date 2005-01-13 Time 15:13 Rev Time 0.00
Received By mmclean Date 2005-01-13 Time 15:13 Sent To I
Notes
2005-01-13 00:00:00PLANS GIVEN OUT TO CONTRACTOR TO HAVE
 HISTORIC RESTAMPS PLANS 1/12/05. PLANS
 RETURNED 1/13/05 WITH HISTORIC STAMPS &
 TWO COPY OF SURVEY.

Review Stop Z ZONING
Rev No 1 Status F Date 2004-12-02 Cont ID  
Sent By mmclean Date 2004-12-02 Time 17:00 Rev Time 0.00
Received By mmclean Date 2004-12-02 Time 16:59 Sent To  
Notes
2004-12-02 00:00:00DENIED, NEED TO SHOW THE WORK (ADDITION)
 ON THE SITEPLAN WITH SETBACKS.CALLED
 OWNER, FILE W FOR P/U MM