| 2004-12-03 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT:04110281 |
| | ADD: 2600 BROADWAY |
| | CONT: K&M COMMERCIAL CONTRACTOR |
| | LLC |
| | TEL: (561)248-9648 BLD CODE= 2001 |
| | FLORIDA BUILDING CODE * WEST PALM BEACH |
| | AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT |
| | NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE |
| | FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | |
| | 1)PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2)FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, THERE |
| | SEEMS TO BE A DISCREPANCY IN WHAT WORK |
| | IS TO BE ACCOMPLISHED UNDER THIS |
| | PERMIT. |
| | THE APPLICATION INDICATES REPLACEMENT |
| | OF |
| | WINDOWS VS PLANS WITH A TENENT FIT UP |
| | FOR (4) BAYS. |
| | |
| | |
| | 3)FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | AGAIN THERE SEEMS TO BE CONFUSION AS TO |
| | |
| | WHAT THE CONTRACTOR IS SUBMITTING. THE |
| | CONTRACTOR HAS SUBMITTED IMPACT RATED |
| | GLAXING PRODUCT APPROVAL AND WINDOW |
| | APPROVAL FOR "NON IMPACT" RATED SYSTEM. |
| | 3401.7.2.4 REPLACEMENT OF EXTERIOR |
| | DOORS |
| | WINDOWS AND SKYLIGHTS SHALL BE DESIGNED |
| | AND CONSTRUCTED TO COMPLY WITH CHAPTER |
| | 16 OF THIS CODE. WIND AND LARGE MISSLE |
| | IMPACT TESTING, EITHER THROUGH GLAZING |
| | SYSTEM OR STORM SHUTTERS. |
| | |
| | 4) IN EITHER CASE, REPLACEMENT OF |
| | GLAZING OR TENANT FIT UP THE PERMIT |
| | IS VERY, VERY LOW. IF THE TRUE VALUE IS |
| | NOT SUBMITTED, WE WILL USE MARSHALL & |
| | SWIFT TO CALCULATE THE PERMIT VALUE. |
| | |
| | 5) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) STORM SHUTTRERS IF NON-IMPACT |
| | GLAZING IS INSTALLED. |
| | |
| | 6) FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 7A) PLANS INDICATE THE REMOVAL OF BLOCK |
| | BENEATH THE EXISTING WINDOWS WITHOUT |
| | ANY |
| | |
| | VERTICAL NOR HORIZONTAL REINFORCING |
| | STEEL? EXPLAIN RATIONAL?1707.4.5.2 |
| | MULLIONS SHALL BE DESIGNED TO TRANSFER |
| | THE DESIGN PRESSURE LOADS APPLIED BY |
| | THE |
| | WINDOW OR DOOR ASSEMBLIES TO THE ROUGH |
| | OPENING SUBTRATE. |
| | IF THERE IS NO WINDOW SILL HOW WILL |
| | THIS TRANSFER OF LOADS OCCUR? |
| | 7B) PLANS ALSO INDICATE INFILL AT THE |
| | WINDOWS AT VARIOUS OPENINGS, NO |
| | COLUMNS? |
| | EXPLAIN RATIONAL? |
| | |
| | 8) PLANS INDICATE THEY COMPLY WITH THE |
| | CURRENT REQUIREMENTS OF AMERICANS WITH |
| | DISABILITIES ACT. PLANS SHOULD READ |
| | FLORIDA AMERICANS WITH DISABILITES & |
| | ACCESSIBILITY IMPLENTATION ACT |
| | 553.501-553.513. |
| | |
| | 9) PLANS DO NOT INDICATE THE LENGHT OF |
| | THE GRAB BARS NOR POSITIONING OF THE |
| | GRAB BARS BEHIND THE WATER CLOSET. |
| | |
| | 10) PROVIDE WHAT TYPE OF OCCUPANCY WILL |
| | OCCUR IN THESE UNITS ? |
| | |
| | |
| | 11)704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| | STOP PARTITIONS, HORIZONTAL EXIT PART- |
| | ITIONS, EXIT ENCLOSURES, AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND |
| | PERMANETLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE |
| | AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| | TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| | CEILING CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| | PROTECT ALL OPENINGS". |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |