Plan Review Details - Permit 04110228
Plan Review Stops For Permit 04110228
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-08-14 Cont ID  
Sent By jwitmer Date 2005-08-14 Time 06:41 Rev Time 3.33
Received By jwitmer Date 2005-08-14 Time 06:33 Sent To PC
Notes
2005-08-14 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04110228
 ADD: 516 BANYAN BLVD
 "THE PLACE VIA CLEMATIS"
 CONT:THE OPERIS GROUP, CORP.
 TEL: (305)624-0245
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)YOUR RESPONCE TO THIS COMMENT IS
 BMD/LLC, PLEASE PROVIDE THE RECORDED
 DOCUMENT OR IF IT IS A NEW PLAT PROVIDE
 THE PLAT.
 THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'.A 'UNITY OF TITLE' SHALL
 BE RECORDED AT THE COUNTY COURTHOUSE.
 SUBMIT A COPY OF THE RECORDED 'UNITY OF
 OF TITLE' DOCUMENT SO THAT FBC TABLE
 600 BOUNDARY LINE REQUIREMENTS MAY BE
 DEEMED NOT APPLICABLE.
  
 3)THIS DOCUMENT MUST BE PROVIDED AS PART
 OF THE PERMIT PACKAGE BEFORE THE PERMIT
 WILL BE ISSUED. FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING
 WHICH IS GREATER THAN (3) STORIES OR 50
 FT IN HEIGHT, OR WHICH HAS AN ASSEMBLY
 OCCUPANCY CLASSIFICATION AS DEINED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 SRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER
 OF RECORD. THE "STRUCTURAL INSPECTION
 PLAN" MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A
 BUILDING PERMIT FOR THE CONSTRUCTION OF
 A THRESHOLD BUILDING. THE PURPOSE OF THE
 SRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND
 SCHEDULES SO THAT THE BUILDING CAN BE
 ADEQUATELY INSPECTED FOR COMPLIANCE WITH
 THE PERMITTED DOCUMENTS.
  
 4)RESPONCE TO THIS COMMENT IS SEE SHEET
 1 OF 8? AGAIN THIS DOCUMENT MUST BE PART
 OF THE PERMIT PACKAGE BEFORE ISSUANCE OF
 THIS PERMIT PRIOR TO THE ISSUANCE OF
 THIS PERMIT.
 WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 5) W.P.B. AMENDMENT 105.13.4.4 ALL
 PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CON-
 TAIN A STATEMENT THAT, TO THE BEST OF
 THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE,
 THE PLANS AND SPECIFICATIONS COMPLY WITH
 THE APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
 THIS IS A THRESHOLD BUILDING THIS
 STATEMENT IS TO BE ON ALL SHEETS
 INCLUDING STRUCTURAL SHEETS. SEE
 REQUIREMENTS FOR THE MEP DRAWINGS TO SEE
 IF EACH OF THESE TRADES QUALIFY AS
 THRESHOLD BUILDING, IF SO THEY ALSO MUST
 HAVE THE SAME STATEMENT ON ALL PAGES.
  
  
 6) FBC* F102.2.7ARCHITECTURAL TRIM,
 TRELLISES, ON BUILDINGS LOCATED IN THE
 FIRE DISTRICT,SHALL BE CONSTRUCTED OF
 APPROVED NON-COMBUSTIBLE MATERIALS OR
 FIRE RETARDANT TREATED WOOD.ANNOTATE
 THE PLANS TO DEMONSTRATE COMPLIANCE.
 A PAINT ON THE SURFACE PRODUCT WILL NOT
 BE ACCEEPTED BY THE BUILDING OFFICIAL.
  
 A NOTE WAS ADDED INDICATING TRELLISES
 SHALL BE OF ALUMINUM BUT THE ORIGINAL
 NOTE WOOD TRELLISES IS STILL THERE,
 "DELETE THE WOOD TRELLIS NOTE!!"ALSO
 DELETE THE NOTES FOR FIRE RETARDANT
 PAINT ON WOOD TRELLISES.
  
  
  
 7) FBC* F102.2.8PERMANENT CANOPIES/
 AWNINGS AND THEIR SUPPORTS, ON BUILDINGS
 LOCATED IN THE FIRE DISTRICT, SHALL BE
 OF NON-COMBUSTIBLE MATERIAL, FIRE
 RETARDANT TREATED WOOD, WOOD OF TYPE
 III SIZES OR OF 1-HOUR RESISTANT
 CONSTRUCTION.ANNOTATE THE PLANS TO
 DEMONSTRATE COMPLIANCE. THE BUILDING
 OFFICIAL HAS RULED THAT A PAINT ON
 RETARDANT WILL NOT BE ACCEPTABLE FOR
 WOOD PRODUCTS. AGAIN DELETE ALL NOTES
 ABOUT WOOD TRIM ON THE EXTERIOR OF THE
 BUILDING.1404.1.1 ARCHITECTURAL TRIM ON
 BUILDINGS OF TYPE I, II AND IV
 CONSTRUCTION NOT MORE THAN THREE STORIES
 OR 40 FT (12.2 M) HIGH MAY BE OFTYPE
 VI CONSTRUCTION, THIS BUILDING IS OVER
 40' TALL.
  
  
 8) FBC* F102.2.4ROOF COVERINGS, ON
 BUILDINGS LOCATED IN THE FIRE DISTRICT,
 SHALL CONFORM TO THE REQUIREMENTS OF
 CLASS A OR B ROOF COVERINGS, AS DEFINED
 IN FBC 1505.ANNOTATE THE PLANS TO
 DEMONSTRATE COMPLIANCE. THE MIAMI-DADE
 REPORT NEOGARD WAS NOT TEST FOR FIRE
 CLASSIFICATION. NO REPORTS WERE
 SUBMITTED FOR ASPHALT UNDERLAYMENT OR
 ROLL ROOFING.NO SUBMITTALS FOR THE
 FINISH ROOF TILE.
  
 *** ALSO NOTE THIS IS A TYPE II
 BUILDINGWHERE THE PLYWOOD ROOF
 SHEATHING IS SPECIFIED ( S2.1 DETAIL
 4)SEE FOOTNOTE (E) TABLE 600, BUILDINGS
 NOT OVER TWO STORIES APPROVED FIRE
 RETARDANT TREATED WOOD MAY BE USED.
  
  
 9) THE PLANS DO NOT PROVIDE
 INFORMATION FOR WORK TO BE COMPLETED IN
 THE PUBLIC PROPERTY. SEE CHAPTER 33,
 WHERE COVERED WALKWAYS WILL BE REQUIRED
 3304, CONSTRUCTION OF WALKWAYS, FENCES
 AND PROTECTIVE COVERINGS. AGAIN THE NOTE
 ONLY COVERS THE UNDERMINING OF THE RIGHT
 OF WAY. NO PRECAUTIONS WERE TAKEN THE
 SHEET PILE ARE NOT IN AND THE ALEY WAY
 IS BEING ERODED AWAY, NO PRECAUTONS TO
 DATE HAVE BEEN TAKEN.
  
  
  
 10) CONCERNS THAT TABLE 600 ISSUES EXIST
 SINCE THE BUILDING IS ON THE PROPERTY
 LINE AND THE ALLEY IS ONLY 14' WIDE.
 SINCE THE STRUCTURE IS DIRECTLY ON THE
 PROPERTY LINE TABLE 600 ISSUES OCCUR.
 PROVIDE DOCUMENTATION AS TO WHAT THE
 VARIANCE WAS GRANTED FOR.
  
 UNTIL COPIES OF THE GRANTED VARIANCE ARE
 RECEIVED NO COMMENT ON 10AOR B.
  
  
 10C) PROVIDE THE EQUIVALENT THICKNESS
 REQUIRED FOR BEARING AND NONBEARING
 CONCRETE BLOCK. SEE 709.3.1. DO NOT
 PROVIDE A UL RATING BUT THE ACTUAL
 EQUIVALENT THICKNESS FROM THE BLOCK
 MANUFACTURE FOR2HR, 3 HR & 4HR WALLS.
  
  
  
 11 SEE DOOR SCHEDULE A.35 IS MISSING
 PROTECTION OF OPENINGS IN INTERIOR
 WALLS,( 705.1.2) SEE TABLE 705.1.2 FOR
 THE REQUIRED RATINGS.PLANS INDICATE THIS
 TO BE A LOUVERED DOOR, PLANS ONLY
 INDICATE FIRE RATED NO RATING, INDICATE
 HOW RATING WILL BE ACHIEVED ON A
 LOUVERED DOOR.
  
  
 12) ADDITIONAL INFORMATION REQUIRED,
 PLANS HAVE A COMMENT STATING "A SEPERATE
 PERMIT REQUIRED", SHEET A35 FOR WINDOWS
 AND DOORS. PRODUCT APPROVALS HAVE BEEN
 SUBMITTED, WHAT ISN'T CLEAR IS IF THESE
 SUBMITTALS ARE TO BE PART OF THIS
 PERMIT.
 ****SINCE THE LAST REVIEW THE BUILDING
 OFFICIAL HAS MADE ME AWARE THAT FOR AN
 ENCLOSED BUILDING WE SHALL HAVE ALL THE
 INFORMATION REQUIRED ( WINDOWS, DOORS
 AND ASSOCIATED ROOFING COMPONENTS)
 BEFORE A PERMIT TO START CONSTRUCTION
 SHALL BE ISSUED.****
  
 12A) THE DOORS OR WINDOWS THAT FACE THE
 SOUTH THAT ARE WITHIN 15' OF THE
 PROPERTY LINE WILL REQUIRE OPENING
 PROTECTIVES. ONCE IN RECEIPT OF THE
 VARIANCE THIS MAY BE RESOLVED.
  
 12B) 1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR
 PROTECTED WITH AN IMPACT RESISTANT
 COVERING MEETING THE REQUIREMENTS OF
 SSTD 12, ASTM E 1886 AND ASTM E 1996 OR
 MIAMI-DADE.
 1) GLAZED OPENINGS LOCATED WITHIN 30
 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.SEE COPY OF CITY OF
 W.P.B. INTERPRETATION OF HURRICANE
 STANDARDS FOR LARGE PROJECTS.
  
 12C) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 13)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS- FIXED OR OPERATABLE
 B) PANELWALL-STOREFRONT
 C) GLAZED EXTERIOR DOORS
 D) SOLID EXTERIOR DOORS
 E) MULLIONS
 F) VENTS/ LOUVERS
 G) STRUCTURAL COMPONENTS- TRUSS
 ANCHORS
 CONCRETE ADMIXTURES, RAILINGS
 H) ROOFING PRODUCTS- AND INSULATION.
 THE ABOVE IS MENTIONED AS TO
 REQUIREMENTS TO OBTAIN A BUILDING
 PERMIT. THE NOTES FOUND ON A.35 NOTE
 FOR WINDOWS AND STOREFRONT ARE TO BE
 UNDER A SEPERATE PERMIT.
 ****SINCE THE LAST REVIEW THE
 BUILDING OFFICIAL HAS MADE ME AWARE THAT
 FOR AN ENCLOSED BUILDING WE SHALL HAVE
 ALL THE
 INFORMATION REQUIRED ( WINDOWS, DOORS
 AND ASSOCIATED ROOFING COMPONENTS)
 BEFORE A PERMIT TO START CONSTRUCTION
 SHALL BE ISSUED.****
  
 14) THE 4 GARAGE OPENINGS ON THE SOUTH
 SIDE OF THE BUILDING DO NOT PROVIDE THE
 PRESSURES (POS/NEG) ASSSOCIATED WITH THE
 BUILDING? 1606.6/ ASCE 7-98. THE GARAGE
 DOOR REPORTS MAY OR MAY NOT WORK BECAUSE
 OF LOW PRESSURES?NO FL COVERSHEET MAY
 ALSO REQUIRE A LOCAL PRODUCT APPROVAL.
 THIS MAY ALSO CHANGE ON THE RESULTS
 OF THE VARIANCE, ORIGINALLY A CHAINED
 TYPE GATE OF GARAGE DOOR WAS CONSIDERED.
 IF NOT USING THE GARAGE DOOR REMOVE FROM
 PACKAGE, THE SAME WITH THE FIRELITE
 GLASS.
  
 15) THE WINDOW REPORTS SUBMITTED HAVE
 MULTIPLE TYPES OF GLAZING THAT MAY BE
 USED, HIGHLIGHT OR INDICATE THE SYSTEM
 USED, ALSO LOOK AT THE HEIGHT/WIDTH AND
 PRESSURES, END ZONES -123, WILL THERE BE
 ONE TYPE OF GLAZING FOR END ZONES AND
 ANOTHER FOR INTERIOR ZONES IF SO
 INDICATE?
  
 16) THE R C ALUMINIUM REPORT SUBMITTED
 IS FOR LARGE MISSLE TESTING ONLY NOT
 TESTED FOR PRESSURES.
 A) 2400 ST SLIDING GLASS DOOR
 B) "FX-345" IF IN END ZONE WILL NOT MEET
 THE REQUIRED -123.8
 C) RD 45 ONLY GOOD FOR +- 80 WILL NOT
 MEET END ZONES
 D) STEELCRAFT OUTSWING +- 65 LOW
 PRESSURE FOR INTERIOR ZONES + END ZONES.
  
  
 17) THE R C ALUMINIUM ENTRY DOOR LMI
 INDICATES MAXIMUM DESIGN PRESSURES GOOD
 FOR +/- 80, BUT END ZONES INDICATE -123.
  
 18) STEELCRAFT DOORS INDICATES MAXIMUM
 DESIGN PRESSURE OF +- 65 THESE DOORS
 WILL BE USED ON THE ROOF TOP WHERE THE
 PRESSURES WILL BE -123.
  
 19) ON THE ROOF TOP DECK THE RESTROOMS
 ARE USING INTERIOR DOORS, DOOR# 15 IS A
 INTERIOR DOOR.
 NOTE NO OTHER PRODUCT APPROVALS WERE
 SUBMITTED.
  
 20) A-37 DETAILS 6 & 7, SOFFITS, DROP
 CEILINGS, OR TRAY CEILINGS ALL INDICATE
 THE SAME PHRASE," TO BE PROPERLY
 ANCHORED TO THEUNDERSIDE OF STRUCTURE"
 BUT THE DESIGN TEAM LACKS INDICATING HOW
 TO ACHIEVE THIS TASK?
 104.2.1 W.P.B. ADMINISTRATIVE CODE
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES.
 SUCH INFORMATION SHALL BE SPECIFIC AND
 THE TECHNICAL CODES "SHALL NOT BE CITED
 AS A WHOLE OR IN PART, NOR THE TERM
 "LEGAL" OR ITS RQUIVALENT BE USED AS A
 SUBSTITUTE FOR SPECIFIC INFORMATION".
  
 21) TYPE II CONSTRUCTION 604 REQUIRES
 STRUCTURAL MEMBERS TO BE NON
 COMBUSTIBLE.
 A.15 WOOD TRELLIS EIGHTHFLOOR TO BE
 NONCOMBUSTIBLE,1404.1.1 ARCHITECTURAL
 TRIM ON BUILDINGS OF TYPE I, II AND IV
 CONSTRUCTION NOT MORE THAN THREE
 STORIES OR 40 FT (12.2 M) HIGH MAY BE OF
 TYPE VI CONSTRUCTION.THIS BUILDINGS MEAN
 ROOF THEIGHT IS 90FT.
 A.20 THE POOL HOUSE, STAIR AND
 ELEVATION SHEETS INDICATE WOOD RAFTERS.
 A.24 WALL SECTIONS A&D INDICATE THE USE
 OF 5/8" CDX PLYWOOD FOR ROOF SHEATHING.
 ALSO 2X6 WOOD FACIA OVER 1X8?????
 TYPE II CONSTRUCTION, TABLE 600 ROOFS TO
 BE 1HR PROTECTED, NONCOMBUSTIBLE.
  
 22) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 FOR THE POOL HOUSE AND ASSOCIATED
 STRUCTURES ATOP THE BUILDING, NO
 INFORMATION WAS SUBMITTED TO BE ABLE TO
 DO A THROUGH PLAN REVIEW!!!!!!!! ROOF
 FRAMING PACKAGE FOR POOL DECK
 STRUCTURES. THE ONLY ITEM THE POOL
 CONTRACTOR WILL BE PERMITING IS THE
 PLUMBING AND ELECTRICAL.STRUCTURAL
 DETAILS FOR THIS DECK TO BE PART OF THE
 STRUCTURAL PLANS.
  
 S-1.7A/S-1.7B POOL DECK PLANS DO NOT
 INDICATE STRUCTURAL DETAILS FOR THE
 STRUCTURESLOCATED ON THIS FLOOR, PLANS
 INDICATE LIGHT GAUGE STEEL TRUSSES. THE
 ENGINEER OF RECORD TO DESIGN THE
 MAGNITUDE OF LOADS ARE TO BE RESISTED,
 UPLIFT, GRAVITY AND LATERAL LOADS.ALSO R
 THE COLUMN FRAMING FOR THE BREEZEWAYS.
 1606.1.3 ANCHORAGE AGAINST
 OVERTURNING, UPLIFT AND SLIDING.
 STRUCTURALMEMBERS AND SYSTEMS, AND
 COMPONENTS AND CLADDING IN A BUILDING OR
 STRUCTURE SHALL BE ANCHORED TO RESIST
 WIND-INDUCED OVERTURNING, UPLIFTAND
 SLIDING AND TO PROVIDE CONTINUOUS LOAD
 PATHS FOR THESE FORCES TO THE
 FOUNDATION.WHERE A PORTION OF THE
 RESISTANCE TO THESE FORCES IS PROVIDED
 BY DEAD LOAD, THE MINIMUM DEAD LOAD
 LIKELY TO BE IN PLACE DURING A DESIGN
 WIND EVENT SHALL BE USED.
  
 23) STAIRWELLS INDICATE HOW PLANS ARE TO
 COMPLY WITH 11-4..4.2 HEADROOM.THIS
 SECTION OF THE CODE DEALS WITH THE BLIND
 ON THE BOTTOM OF THE STAIRWELL WALKING
 IN UNDERNEATH THE STAIRS AND CAUSING
 INJURY TO THEIR HEAD BECAUSE THIS AREA
 BENEATH THE STAIRWAY WAS NOT ENCLOSED OR
 BLOCKED OFF.
 SEE THIS SECTION OF THE CODE WHAT IS
 REQUIRED!!!!!!!!
  
 24) SHOW COMPLIANCE WITH 412.5 SMOKE
 CONTROL, M-16 SMOKE ZONE CONTROLS/ ZONE
 II, PLANS INDICATE THE USE OF
 PRESSURIZATION, THIS STILL DOESN'T
 REMOVE SMOKE, SEE 412.5.
  
 25) COMMEENT # 28 FROM THE PEVIOUS
 REVIEW:
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 25) COMMEENT# 29 FROM THE PREVIOUS
 REVIEW, PLEASE PULL THE ARCHITECTURAL
 AND STRUCTURAL SHEETS OUT TO FORM THERE
 OWN ROLL
 ** TO DATE THIS HAS NOT BEEN COMPLETED**
  
 26) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS, TO FORM A SET OF
 'OLD/VOID SHEETS', FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
 ***************TO DATE THIS HAS NOT BEEN
 COMPLETED, NONE OF THE OLD REVISED PLANS
 HAVE BEEN SUBMITTED********************
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-04-07 Cont ID  
Sent By jwitmer Date 2005-04-07 Time 08:26 Rev Time 3.33
Received By jwitmer Date 2005-04-07 Time 08:26 Sent To  
Notes
2005-04-07 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04110228
 ADD: TO BE DECIDED
 "THE PLACE VIA CLEMATIS"
 CONT:PLAN REVIEW
 CONTACT: BLUE MOON DEV
 TEL: (786)554-0900
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'.A 'UNITY OF TITLE' SHALL
 BE RECORDED AT THE COUNTY COURTHOUSE.
 SUBMIT A COPY OF THE RECORDED 'UNITY OF
 OF TITLE' DOCUMENT SO THAT FBC TABLE
 600 BOUNDARY LINE REQUIREMENTS MAY BE
 DEEMED NOT APPLICABLE.
  
 3) FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY
 OCCUPANCY CLASSIFICATION AS DEINED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 SRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER
 OF RECORD. THE STRUCTURAL INSPECTION
 PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A
 BUILDING PERMIT FOR THE CONSTRUCTION OF
 A THRESHOLD BUILDING. THE PURPOSE OF THE
 SRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND
 SCHEDULES SO THAT THE BUILDING CAN BE
 ADEQUATELY INSPECTED FOR COMPLIANCE WITH
 THE PERMITTED DOCUMENTS.
  
 4) WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 5) W.P.B. AMENDMENT 105.13.4.4 ALL
 PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CON-
 TAIN A STATEMENT THAT, TO THE BEST OF
 THE ARCHITECT'S PRENGINEER'S KNOWLEDGE,
 THE PLANS AND SPECIFICATIONS COMPLY WITH
 THE APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 6) FBC* F102.2.7ARCHITECTURAL TRIM,
 TRELLISES, ON BUILDINGS LOCATED IN THE
 FIRE DISTRICT,SHALL BE CONSTRUCTED OF
 APPROVED NON-COMBUSTIBLE MATERIALS OR
 FIRE RETARDANT TREATED WOOD.ANNOTATE
 THE PLANS TO DEMONSTRATE COMPLIANCE.
 A PAINT ON THE SURFACE PRODUCT WILL NOT
 BE ACCEEPTED BY THE BUILDING OFFICIAL.
  
 7) FBC* F102.2.8PERMANENT CANOPIES/
 AWNINGS AND THEIR SUPPORTS, ON BUILDINGS
 LOCATED IN THE FIRE DISTRICT, SHALL BE
 OF NON-COMBUSTIBLE MATERIAL, FIRE
 RETARDANT TREATED WOOD, WOOD OF TYPE
 III SIZES OR OF 1-HOUR RESISTANT
 CONSTRUCTION.ANNOTATE THE PLANS TO
 DEMONSTRATE COMPLIANCE. THE BUILDING
 OFFICIAL HAS RULED THAT A PAINT ON
 RETARDANT WILL NOT BE ACCEPTABLE FOR
 WOOD PRODUCTS.
  
 8) FBC* F102.2.4ROOF COVERINGS, ON
 BUILDINGS LOCATED IN THE FIRE DISTRICT,
 SHALL CONFORM TO THE REQUIREMENTS OF
 CLASS A OR B ROOF COVERINGS, AS DEFINED
 IN FBC 1505.ANNOTATE THE PLANS TO
 DEMONSTRATE COMPLIANCE. THE MIAMI-DADE
 REPORT NEOGARD WAS NOT TEST FOR FIRE
 CLASSIFICATION. NO REPORTS WERE
 SUBMITTED FOR ASPHALT UNDERLAYMENT OR
 ROLL ROOFING.
 *** ALSO NOTE THIS IS A TYPE II
 BUILDINGWHERE THE PLYWOOD ROOF
 SHEATHING IS SPECIFIED ( S2.1 DETAIL
 4)SEE FOOTNOTE (E) TABLE 600, BUILDINGS
 NOT OVER TWO STORIES APPROVED FIRE
 RETARDANT TREATED WOOD MAY BE USED.
  
  
 9) THE PLANS DO NOT PROVIDE
 INFORMATION FOR WORK TO BE COMPLETED IN
 THE PUBLIC PROPERTY. SEE CHAPTER 33,
 WHERE COVERED WALKWAYS WILL BE REQUIRED
 3304, CONSTRUCTION OF WALKWAYS, FENCES
 AND PROTECTIVE COVERINGS.
  
 10) CONCERNS THAT TABLE 600 ISSUES EXIST
 SINCE THE
 BUILDING IS ON THE PROPERTY LINE AND
 THE ALLEY IS ONLY 14' WIDE. SINCE THE
 STRUCTURE IS DIRECTLY ON THE PROPERTY
 LINE TABLE 600 ISSUES OCCUR.
  
 10A) THE WALL SECTION THAT IS 6'-0"
 AWAY FROM THE PROPERTY LINE, THAT
 CONTAINS THE OPENING FOR THE RAMPED
 DRIVE CAN ONLY HAVE 20% OPENINGS &
 REQUIRES A 3 HR WALL. 1/2 OF THE ALLEY
 OR 7'+6'= 13' OR 20% ALLOWABLE OPENINGS,
 PER FLOOR!SEE 705.1.1.2 FOR OPENINGS
 LESS THAN 15' FROM THE PROPERTY LINE.
  
 10B) THE WALL SECTIONS THAT ARE JUST TO
 THE EASTARE RIGHT ON THE PROPERTY LINE
 (0'-3') CAN'T HAVE ALLOWABLE OPENINGS
 AND REQUIRE A 4 HR WALL. PLANS INDICATE
 OPENINGS ALLOWING ENTRY TO THE ENCLOSED
 GARAGE WITH A ROLL-UP ELECTTRIC GATE.
 IN BOTH CASES 14(A( & (B) THE APPLICANT
 IS GOING BEFORE THE CBAA FOR A VARIANCE
 THE HEARING TO BE APRIL 21/2005.WILL
 AWAIT OUTCOME OF HEARING!
  
 10C) PROVIDE THE EQUIVALENT THICKNESS
 REQUIRED FOR BEARING AND NONBEARING
 CONCRETE BLOCK. SEE 709.3.1. DO NOT
 PROVIDE A UL RATING BUT THE ACTUAL
 EQUIVALENT THICKNESS FROM THE BLOCK
 MANUFACTURE FOR2HR, 3 HR & 4HR WALLS.
  
  
  
 11 SEE DOOR SCHEDULE A.35 IS MISSING
 PROTECTION OF OPENINGS IN INTERIOR
 WALLS,( 705.1.2) SEE TABLE 705.1.2 FOR
 THE REQUIRED RATINGS.
 A)MISSING THE RATING FOR STAIRTOWER
 DOORS, NOT LISTED IN COMMENTS.
  
 12) ADDITIONAL INFORMATION REQUIRED,
 PLANS HAVE A COMMENT STATING "A SEPERATE
 PERMIT REQUIRED", SHEET A35 FOR WINDOWS
 AND DOORS. PRODUCT APPROVALS HAVE BEEN
 SUBMITTED, WHAT ISN'T CLEAR IS IF THESE
 SUBMITTALS ARE TO BE PART OF THIS
 PERMIT.
  
 12A) THE SECOND ISSUE SUBMITTALS FOR
 FIRELITE GLAZING BUT IT DOES NOT SHOW UP
 IN THE DOOR OR WINDOW SCHEDULE.
  
 12B) THE DOORS OR WINDOWS THAT FACE THE
 SOUTH THAT ARE WITHIN 15' OF THE
 PROPERTY LINE WILL REQUIRE OPENING
 PROTECTIVES. INDICATE IN THE DOOR AND
 WINDOW SCHEDULES WHICH OPENINGS ARE
 EFFECTED. ALSO IF FIRE LITE IS TO BE
 USED HOW ARE THE REQUIREMENTS FOR LARGE
 AND SMALL MISSLE TESSTING BEING MET?
  
 12C) 1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR
 PROTECTED WITH AN IMPACT RESISTANT
 COVERING MEETING THE REQUIREMENTS OF
 SSTD 12, ASTM E 1886 AND ASTM E 1996 OR
 MIAMI-DADE.
 1) GLAZED OPENINGS LOCATED WITHIN 30
 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.SEE COPY OF CITY OF
 W.P.B. INTERPRETATION OF HURRICANE
 STANDARDS FOR LARGE PROJECTS.
  
 12D) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 13)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS- FIXED OR OPERATABLE
 B) PANELWALL-STOREFRONT
 C) GLAZED EXTERIOR DOORS
 D) SOLID EXTERIOR DOORS
 E) MULLIONS
 F) VENTS
 G) STRUCTURAL COMPONENTS- TRUSS
 ANCHORS
 CONCRETE ADMIXTURES, RAILINGS
 H) ROOFING PRODUCTS- AND INSULATION.
 THE ABOVE IS MENTIONED AS TO
 REQUIREMENTS TO OBTAIN A BUILDING
 PERMIT. THE NOTES FOUND ON A.35 NOTE
 FOR WINDOWS AND STOREFRONT ARE TO BE
 UNDER A SEPERATE PERMIT. AT WHAT TIME
 WILL THESE ITEMS BE ADDRESSED? SHOULD
 THE BUILDING BE CLASSIFIED AS OPEN OR
 PARTIALLY OPEN SINCE NO TIME FACTOR IS
 MENTIONED TO WHEN THEY WILL BE
 INSTALLED?
  
 14) THE 4 GARAGE OPENINGS ON THE SOUTH
 SIDE OF THE BUILDING DO NOT PROVIDE THE
 PRESSURES (POS/NEG) ASSSOCIATED WITH THE
 BUILDING? 1606.6/ ASCE 7-98. THE GARAGE
 DOOR REPORTS MAY OR MAY NOT WORK BECAUSE
 OF LOW PRESSURES?NO FL COVERSHEET MAY
 ALSO REQUIRE A LOCAL PRODUCT APPROVAL.
  
 15) THE WINDOW REPORTS SUBMITTED HAVE
 MULTIPLE TYPES OF GLAZING THAT MAY BE
 USED, HIGHLIGHT OR INDICATE THE SYSTEM
 USED, ALSO LOOK AT THE HEIGHT/WIDTH AND
 PRESSURES, END ZONES -123, WILL THERE BE
 ONE TYPE OF GLAZING FOR END ZONES AND
 ANOTHER FOR INTERIOR ZONES IF SO
 INDICATE?
  
 16) THE R C ALUMINIUM REPORT SUBMITTED
 IS FOR LARGE MISSLE TESTING ONLY NOT
 TESTED FOR PRESSURES.
  
 17) THE R C ALUMINIUM ENTRY DOOR LMI
 INDICATES MAXIMUM DESIGN PRESSURES GOOD
 FOR +/- 80, BUT END ZONES INDICATE -123.
  
 18) STEELCRAFT DOORS INDICATES MAXIMUM
 DESIGN PRESSURE OF +- 65 THESE DOORS
 WILL BE USED ON THE ROOF TOP WHERE THE
 PRESSURES WILL BE -123.
  
 19) ON THE ROOF TOP DECK THE RESTROOMS
 ARE USING INTERIOR DOORS, DOOR# 15 IS A
 INTERIOR DOOR.
 NOTE NO OTHER PRODUCT APPROVALS WERE
 SUBMITTED.
  
 20) A-37 DETAILS 6 & 7, SOFFITS, DROP
 CEILINGS, OR TRAY CEILINGS ALL INDICATE
 THE SAME PHRASE," TO BE PROPERLY
 ANCHORED TO THEUNDERSIDE OF STRUCTURE"
 BUT THE DESIGN TEAM LACKS INDICATING HOW
 TO ACHIEVE THIS TASK?
 104.2.1 W.P.B. ADMINISTRATIVE CODE
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES.
 SUCH INFORMATION SHALL BE SPECIFIC AND
 THE TECHNICAL CODES "SHALL NOT BE CITED
 AS A WHOLE OR IN PART, NOR THE TERM
 "LEGAL" OR ITS RQUIVALENT BE USED AS A
 SUBSTITUTE FOR SPECIFIC INFORMATION".
  
 21) TYPE II CONSTRUCTION 604 REQUIRES
 STRUCTURAL MEMBERS TO BE NON
 COMBUSTIBLE.
 A.15 WOOD TRELLIS EIGHTHFLOOR TO BE
 NONCOMBUSTIBLE, F102.2.7 FIRE DISTRICT
 A.20 THE POOL HOUSE, STAIR AND
 ELEVATION
 SHEETS INDICATE WOOD RAFTERS.
 A.24 WALL SECTIONS A&D INDICATE THE USE
 OF 5/8" CDX PLYWOOD FOR ROOF SHEATHING.
 ALSO 2X6 WOOD FACIA OVER 1X8?????
  
 22) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 FOR THE POOL HOUSE AND ASSOCIATED
 STRUCTURES ATOP THE BUILDING, NO
 INFORMATION WAS SUBMITTED TO BE ABLE TO
 DO A THROUGH PLAN REVIEW!!!!!!!!
 S-1.6A/S-1.6B POOL DECK PLANS DO NOT
 INDICATE STRUCTURAL DETAILS FOR THE POOL
 STRUCTURE, SPA NOR THE COLUMN FRAMING
 FOR THE BREEZEWAYS.
  
 23) STAIRWELLS INDICATE HOW PLANS ARE TO
 COMPLY WITH 11-4..4.2 HEADROOM.THIS
 SECTION OF THE CODE DEALS WITH THE BLIND
  
 ON THE BOTTOM OF THE STAIRWELL WALKING
 IN UNDERNEATH THE STAIRS AND CAUSING
 INJURY TO THEIR HEAD BECAUSE THIS AREA
 BENEATH THE STAIRWAY WAS NOT ENCLOSED OR
 BLOCKED OFF.
  
 24) SHOW COMPLIANCE WITH 412.5 SMOKE
 CONTROL, M-16 SMOKE ZONE CONTROLS/ ZONE
 II, PLANS INDICATE THE USE OF
 PRESSURIZATION, THIS STILL DOESN'T
 REMOVE SMOKE, SEE 412.5.
  
 25) A-7 AUTO RAMP TO THE MEZZANINE FLOOR
 PLAN INDICATES OPENSIDED RAMP, PROVIDE
 INFORMATION FOR COMPLIANCE WITH
 1608.2.3. PARKING GAURDRAILS, IMPACT
 GAURDRAILS, AND BOLLARDS.
  
 26) A-8 PROVIDE FLOOR SLOPES AT THE
 HANDICAPED PARKING AT THE EAST END OF
 THE BLDG. DRAINAGE GRATE IN THE MIDDLE
 OF THE HANDICAPPED SPACE?
  
 27) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 A-9/A-10 NO INFORMATION IS PROVIDED FOR
 WALLS AND GATES OF PRIVATE LANAI?
  
 28)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 29) PLEASE PULL THE ARCHITECTURAL AND
 STRUCTURAL SHEETS OUT TO FORM THERE OWN
 ROLL.
  
 30) SHEET S4.2THE FOUNDATION SCHEDULE
 IS BLANK.
  
 31) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS, TO FORM A SET OF
 'OLD/VOID SHEETS', FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-12-02 Cont ID  
Sent By jwitmer Date 2004-12-02 Time 16:15 Rev Time 24.00
Received By jwitmer Date 2004-12-02 Time 16:14 Sent To  
Notes
2004-12-02 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04110228
 ADD: TO BE DECIDED
 "THE PLACE VIA CLEMATIS"
 CONT:PLAN REVIEW
 CONTACT: BLUE MOON DEV
 TEL: (786)554-0900
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL
 LETTER
 LISTING THE ORIGINAL REVIEW COMMENT
 NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR
 SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'.A 'UNITY OF TITLE' SHALL
 BE
 RECORDED AT THE COUNTY COURTHOUSE.
 SUBMIT A COPY OF THE RECORDED 'UNITY OF
 OF TITLE' DOCUMENT SO THAT FBC TABLE
 600
 BOUNDARY LINE REQUIREMENTS MAY BE
 DEEMED
 NOT APPLICABLE.
  
 3)FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN
 QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE
 EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.SUPPLY (3) REPORTS.
  
 4) FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY
 OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 SRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL
 INSPEC
 TION PLAN PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING
 AGEN-
 CY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A
 THRESH-
 OLD BUILDING. THE PURPOSE OF THE
 SRUCTUR
 AL INSPECTION PLAN IS TO PROVIDE
 SPECIF-
 IC INSPECTION PROCEDURES AND SCHEDULES
 SO THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 5) WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 6) W.P.B. AMENDMENT 105.13.4.4 ALL
 PLANS
 FOR THE BUILDING WHICH ARE REQUIRED TO
 BE SIGNED AND SEALED BY THE ARCHITECT
 OR
 ENGINEER OF RECORD CON- TAIN A
 STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR
 ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 7) FBC* F102.2.7ARCHITECTURAL TRIM,
 ON
 BUILDINGS LOCATED IN THE FIRE DISTRICT,
 SHALL BE CONSTRUCTED OF APPROVED
 NON-COMBUSTIBLE MATERIALS OR FIRE
 RETARDANT TREATED WOOD.ANNOTATE THE
 PLANS TO DEMONSTRATE COMPLIANCE.
  
 8) FBC* F102.2.8PERMANENT CANOPIES/
 AWNINGS AND THEIR SUPPORTS, ON
 BUILDINGS
 LOCATED IN THE FIRE DISTRICT, SHALL BE
 OF NON-COMBUSTIBLE MATERIAL, FIRE
 RETARDANT TREATED WOOD, WOOD OF TYPE
 III
 SIZES OR OF 1-HOUR RESISTANT
 CONSTRUCTION.ANNOTATE THE PLANS TO
 DEMONSTRATE COMPLIANCE.
  
 9) FBC* F102.2.4ROOF COVERINGS, ON
 BUILDINGS LOCATED IN THE FIRE DISTRICT,
 SHALL CONFORM TO THE REQUIREMENTS OF
 CLASS A OR B ROOF COVERINGS, AS DEFINED
 IN FBC 1505.ANNOTATE THE PLANS TO
 DEMONSTRATE COMPLIANCE.
  
 10) THE PLANS DO NOT PROVIDE
 INFORMATION FOR WORK TO BE COMPLETED IN
 THE PUBLIC PROPERTY. SEE CHAPTER 33,
 WHERE COVERED WALKWAYS WILL BE REQUIRED
 3304, CONSTRUCTION OF WALKWAYS, FENCES
 AND PROTECTIVE COVERINGS.
  
 11) PROVIDE INFORMATION ON THE SHEET
 PILING, EXCAVATION ,DENSAFICATION OF
 SOILS AND IF SOIL NAILS ARE GOING TO
 BEREQUIRED AND DEWATERING. DEPENDING ON
 THE SEQUENCE OF EVENTS THERE IS
 POSSIBILITIES OF THE SHEET PILE GIVING
 WAY BECAUSE OF SOILS VIBRAFLOTATION.
  
 12) PROPERTY LINES- ON THE NORTH SIDE
 OF THE BUILDING SHEET A.5/A.6 INDICATE
 FRONT ENTRY DOORS SWINGING PAST THE
 PROPERTY LINE. 3203.1 DOORS SHALL NOT
 OPEN OR PROJECT UPON PUBLIC PROPERTY.
  
 13) SOUTH SIDE OF THE BUILDING SHEET
 A.5/A.6 CURB IS PAST THE PROPERTY LINE.
  
 14) BOTH SETS OF PLANS ARE MISSING THE
 A-19 SHEET WHICH DEPICTS THE SOUTH
 ELEVATION OF THE BUILDING. CONCERNS
 THAT TABLE 600 ISSUES EXIST SINCE THE
 BUILDING IS ON THE PROPERTY LINE AND
 THE ALLEY IS ONLY 14' WIDE. SINCE THE
 STRUCTURE IS DIRECTLY ON THE PROPERTY
 LINE TABLE 600 ISSUES OCCUR.
 14A) THE WALL SECTION THAT IS 6'-0"
 AWAY
 FROM THE PROPERTY LINECAN HAVE 20%
 OPENINGS & REQUIRES A 3 HR WALL.!/2 OF
 ALLEY OR 7'+6'= 13' OR 20% ALLOWABLE
 OPENINGS, PER FLOOR!SEE 705.1.1.2 FOR
 OPENINGS LESS THAN 15' FROM THE
 PROPERTY LINE.
 14B) THE WALL SECTIONS THAT ARE RIGHT
 ON THE PROPERTY LINE(0'-3') HAVE NO
 ALLOWABLE OPENINGS AND REQUIRE A 4 HR
 WALL.
 14C) PROVIDE THE EQUIVALENT THICKNESS
 REQUIRED FOR BEARING AND NONBEARING
 CONCRETE BLOCK. SEE 709.3.1. DO NOT
 PROVIDE A UL RATING BUT THE ACTUAL
 EQUIVALENT THICKNESS FROM THE BLOCK
 MANUFACTURE FOR2HR, 3 HR & 4HR WALLS.
  
 15) SHEET A-27 MEZANINES, THE AREA OF
 THE MEZZANINES IS OVER THE 1/3 OF THE
 ROOM IN WHICH IT IS LOCATED. SEE
 503.2.3.2. ENCLOSED SPACE UNDER A
 MEZZANINE SHALL NOT BE INCLUDED IN A
 DETERMINATION OF THE SIZE OF THE ROOM
 OR SPACE IN WHICH THE MEZANINE IS
 LOCATED. RECALCULATE AREAS.
  
 16)A.5 WALL LEGEND INDICATES VARIOUS
 BLOCK OR SOLID CONCRETE WALL AND THEIR
 RESPECTIVE HR. RATING. PROVIDE THE
 EQUIVALENT THICKNESS AS DESCRIBED IN
 TABLE 709.3.1. NOTE ALSO NO 3HR WALLS
 PROVIDED 0'-3' REQUIRES A 3HR RATED
 WALL. THE BLOCK INFORMATION SHOULD COME
 FROM THE BLOCK MANUFACTURER NOT A
 UL LISTING.
  
 17) A.5/A.6 SEE STAIRWAYS, 1007.1.5
 ENCLOSED EXIT STAIRWAYS THAT CONTINUE
 BEYOND THE FLOOR OF DISCHARGE SHALL BE
 INTERRUPTED AT THE FLOOR OF DISCHARGE
 BY PARTITIONS, DOORS OR OTHER EFFECTIVE
 MEANS.
  
 18) SEE DOOR SCHEDULE A.35 IS MISSING
 PROTECTION OF OPENINGS IN INTERIOR
 WALLS,( 705.1.2) SEE TABLE 705.1.2 FOR
 THE REQUIRED RATINGS.
  
 19) TRASH ROOM SEE A.6/A.35 MISSING THE
  
 DOOR RATING FOR THE TRASH TERMINATION
 ROOM. SEE 705.2.4.4.
  
 20) THE VARIOUS FLOORS (2-8) INCLUDE
 THE
  
 PHRASE TRASH ROOM (EXAMPLEROOM 103 ON
 A.10). THISDETAIL DOESN'T PROVIDE AN
 ACCURATE DETAIL WITH THE WORD ROOM, AT
 BEST IT IS A VESTIBULE, THE CODE DOES
 REQUIRE A ACCESS ROOM. THE SWING DOOR
 THAT IS NOT NUMBERED OR LABELED WILL
 MEET THE INTENT OF THE CODE IF THE
 3/4 HR RATING IS MET SEE 705.2.4.2.
  
 21)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 THERE IS A SPACE BETWEEN THE TRASH
 ROOM,
 STAIRWELL# 3, THAT IS NOT LABELED, WHAT
 WILL THIS AREA BE USED FOR? IF IT IS A
 CHASE PROVIDE A 2 HR RATED ASSEMBLY.SEE
 A.10, A.12, A.14 & A.16.
  
 22) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 THERE IS ALSO 2 AREAS ON EACH SIDE OF
 STAIRWELL# 2 THAT IS NOT CLEAR WHAT
 THIS
 AREA MAY BE USED FOR, IT IS DIRECTLY
 FOUND ON A.9, A.11 & A.13.
  
 23) INDICATE COMPLIANCE WITH 3003.4.1
 LEVATOR STRETCHER REQUIREMENTS.
  
 24) 1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR
 PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
 1) GLAZED OPENINGS LOCATED WITHIN 30
 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.SEE COPY OF CITY OF
 W.P.B. INTERPRETATION OF HURRICANE
 STANDARDS FOR LARGE PROJECTS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS- FIXED OR OPERATABLE
 B) PANELWALL-STOREFRONT
 C) GLAZED EXTERIOR DOORS
 D) SOLID EXTERIOR DOORS
 E) MULLIONS
 F) VENTS
 G) STRUCTURAL COMPONENTS- TRUSS
 ANCHORS
 CONCRETE ADMIXTURES, RAILINGS
 H) ROOFING PRODUCTS- AND INSULATION.
 THE ABOVE IS MENTIONED AS TO
 REQUIREMENTS TO OBTAIN A BUILDING
 PERMIT. THE NOTES FOUND ON A.35 NOTE
 FOR
 WINDOWS AND STOREFRONT ARE TO BE UNDER
 A
 SEPERATE PERMIT. AT WHAT TIME WILL
 THESE ITEMS BE ADDRESSED? SHOULD THE
 BUILDING BE CLASSIFIED AS OPEN OR
 PARTIALLY OPEN SINCE NO TIME FACTOR IS
 MENTIONED TO WHEN THEY WILL BE
 INSTALLED?
  
 25) THE OTHER ISSUE THAT NEEDS TO BE
 CLARIFIED, THERE CAN ONLY BE ONE
 CLASSIFICATION FOR A BUILDING OR
 STRUCTURE EITHER OPEN, PARTIALLY
 ENCLOSED OR ENCLOSED. . SEE ASCE 7-98
 6.5.9.4. SHEET S-4.1 WIND DESIGN
 INDICATES THAT YOU ARE DESIGNING TO A
 HIGH VELOCITY ZONE "C", AND EXPOSURE
 OF 146 MPH. S5.2 INDICATESE PARTIALLY
 ENCLOSED BUT COEFICIENTS FOUND ON S4.1
 INDICATEA CLOSED BUILDING 0.18+-,
 PLEASE INDICATE FINAL ANALYSIS?
  
 26) A-37 DETAILS 6 & 7, SOFFITS, DROP
 CEILINGS, OR TRAY CEILINGS ALL INDICATE
 THE SAME PHRASE," TO BE PROPERLY
 ANCHORED TOTHEUNDERSIDE OF STRUCTURE"
 BUT THE DESIGN TEAM LACKS INDICATING HOW
 TO ACHIEVE THIS TASK?
 104.2.1 W.P.B. ADMINISTRATIVE CODE
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES.
 SUCH INFORMATION SHALL BE SPECIFIC AND
 THE TECHNICAL CODES "SHALL NOT BE CITED
 AS A WHOLE OR IN PART, NOR THE TERM
 "LEGAL" OR ITS RQUIVALENT BE USED AS A
 SUBSTITUTE FOR SPECIFIC INFORMATION".
  
 27) TYPE II CONSTRUCTION 604 REQUIRES
 STRUCTURAL MEMBERS TO BE NON
 COMBUSTIBLE.
 A.15 WOOD TRELLIS EIGHTHFLOOR TO BE
 NONCOMBUSTIBLE, F102.2.7 FIRE DISTRICT
 A.20 THE POOL HOUSE, STAIR AND
 ELEVATION
 SHEETS INDICATE WOOD RAFTERS.
 A.24 WALL SECTIONS A&D INDICATE THE USE
 OF 5/8" CDX PLYWOOD FOR ROOF SHEATHING.
 ALSO 2X6 WOOD FACIA OVER 1X8?????
  
 28) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 FOR THE POOL HOUSE AND ASSOCIATED
 STRUCTURES ATOP THE BUILDING, NO
 INFORMATION WAS SUBMITTED TO BE ABLE TO
 DO A THROUGH PLAN REVIEW!!!!!!!!
 S-1.6A/S-1.6B POOL DECK PLANS DO NOT
 INDICATE STRUCTURAL DETAILS FOR THE POOL
 STRUCTURE, SPA NOR THE COLUMN FRAMING
 FOR THE BREEZEWAYS.
  
 29) A.15 THERE HAS BEEN NO INFORMATION
 SUBMITTED FOR AN ELEVATOR LOBBY FOR
 NONE
 OF THE ELEVATORS ON THE ROOF TERRACE
 LEVEL.SEE 412.6.
  
 30) THE FIRE SPRINKLER PLANS DO NOT
 INDICATE THE USE OF FIRE SPRINKLERS FOR
 THE STRUCTURES ON THE ROOF TERRACE
 LEVEL. SEE ATTACHMENT NFPA 13 8.14.7
 EXTERIOR ROOFS OR CANOPIES, INDICATE
 HOW
 TO ACHIEVE CODE COMPLIANCE.
  
 31) ASSUMPTION: FIRE SPRINKLERS FOR THE
  
 POOL ROOF TERRACE LEVEL NOR THE POOL
 DECK LEVEL, ISIT ASSUMED THAT AREA OF
 RESCUE WILL BE PROVIDED UNDER SECTION
 11-4.3.11?
  
 32) A-24 INDICATES THE USE OF CAST
 STONE
 WITH A THICKNESS OF 1"-6". SHOW
 COMPLIANCE WITH 1403.2.7.
  
 33) STAIRWELLS INDICATE HOW PLANS ARE TO
 COMPLY WITH 11-4..4.2 HEADROOM.
  
 34) A-23 DROP OFF ZONE 11-4.6.5
 PASSENGER LOADING ZONE PROVIDE THE
 VEHICLE ACCESS ROUTE WITHREQUIRED HEAD
 ROOM FROM THE ENTRY TO LOADING ZONE BACK
 TO THE EXIT.
  
 35) A-5 ACCESSIBLE PATH, ACCESS AISLE IS
 THERE A CURB @ COLUMN LINE 7/F1AND
 DROP OFF POINT?
  
 36) POOL STRUCTURE: POOL TO BE UNDER A
 SEPERATE PERMIT, THE STURTURAL WALLS
 WILL BE BUILT WITH THE BUILDING, THIS
 AGAIN IS AN ASSUMPTION. TO COMPLY WITH
 424. PUBLIC POOLS :
 A) DOES THE POOL OFFER SUNKEN SEATING
 OR IS THIS STAIRS? SEE 424.1.2.5.3 FOR
 STAIRS, 424.1.2.5.4.
  
 37) A-34 THE DOORS LEADING INTO THE POOL
 AREA DOOR 12 & 16 SHALL COMPLY WITH SELF
 CLOSING AND SELF LATCHING REQUIREMENTS,
 SEE 424.1 DOH 64E-9.002(6) EFFECTIVE
 BARRIER.
  
 38) A-36 DETAIL # 23 EXTERIOR
 GUARDRAIL;
 1015.2 HEIGHT. GUARDRAILS SHALL FORM
 A VERTICAL PROTECTIVE BARRIER NOT LESS
 THAN 42" HIGH.
 1015.3 OPENINGS. OPEN GUARDRAILS
 SHALL HAVE INTERMEDIATE RAILS OR ORNA-
 MENTAL PATTERNS SUCH AS A 4" DIAMETER
 SPHERE CAN NOT PASS THROUGH. A BOTTOM
 RAIL OR CURB SHALL BE PROVIDED THAT WILL
 REJECT THE PASSAGE OF 2" DIAMETER
 SPHERE.
  
 39) A-36 EXTERIOR GUARDRAILS TO COMPLY:
 1608.2.3 THE GUARDRAIL SYSTEM SHALL BE
 DESIGNED AND CONSTRUCTED TO RESIST A 200
 LB CONCENTRATED HORIZONTAL LOAD APPLIED
 ON A 1 SQ FT AREA AT ANY POINT IN THE
 SYSTEM INCLUDING INTERMEDIATE RAILS OR
 OTHER ELEMENTS SERVING THIS PURPOSE.
  
 40) A-5 RAMP DOWN TO 9'-4" NOTE
 INDICATESA 12" WIDE CONCRETE CURB SEE
  
 DETAILS 6/A-46? NO SUCH PLAN?STOPS AT
 40
  
 41) 411.4.2 6 AIR CHANGES PER HR/
 LEVEL.
 M-3 INDICATES A 15,000 CFM FAN
 EXHAUSTING , CENTERED IN A 50"-0"
 OPENING. PLANS DO NOT INDICATE ANY MAKE
 UP AIR, THIS EXHAUST WILL BE PULLED
 RIGHT BACK INTO THE GARAGE, EXPLAIN
 RATIONAL?
  
 42) SHOW COMPLIANCE WITH 412.5 SMOKE
 CONTROL, M-16 SMOKE ZONE CONTROLS/ ZONE
 II, PLANS INDICATE THE USE OF
 PRESSURIZATION, THIS STILL DOESN'T
 REMOVE SMOKE, SEE 412.5.
  
 43) M-6 EMERGENCY GENERATOR INDICATES A
 6" EXHAUST PIPE W/ 1 1/2" CALCIUM
 SILICATE WRAP THROUGH THE 2HR RATED
 FLOOR SLAB. 705.6.1 PROVIDE THE
 ASSEMBLY
 APPROVED FOR THIS APPLICATION.
 PENETRATIONS OF HORIZONTAL ASSEMBLIES.
  
 44) A-7 AUTO RAMP TO THE MEZZANINE FLOOR
 PLAN INDICATES OPENSIDED RAMP, PROVIDE
 INFORMATION FOR COMPLIANCE WITH
 1608.2.3. PARKING GAURDRAILS, IMPACT
 GAURDRAILS, AND BOLLARDS. BOLLARDS
 INDICATE A SECTION )/A-000.?????
  
 45) A-8 PROVIDE FLOOR SLOPES AT THE
 HANDICAPED PARKING AT THE EAST END OF
 THE BLDG. DRAINAGE GRATE IN THE MIDDLE
 OF THE HANDICAPPED SPACE?
  
 46) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 A-9/A-10 NO INFORMATION IS PROVIDED FOR
 WALLS AND GATES OF PRIVATE LANAI?
  
 47)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 PLANS ARE NOT COMPLETE AND THE ANSWERS
 TO THE QUESTIONS MAY RESULT IN
 ADDITIONAL COMMENTS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-07-14 Cont ID  
Sent By dpalmer Date 2005-07-14 Time 15:28 Rev Time 15.00
Received By dpalmer Date 2005-07-12 Time 16:24 Sent To  
Notes
2005-07-14 00:00:00********* UNSAT 3RD REVIEW ************
  
 "THE PLACE VIA CLEMATIS"
  
 PLEASE SEE COMMENTS FROM PREVIOUS TWO
 REVIEWS WHICH STILL NEED TO BE
 ADDRESSED.
  
 PLEASE ALSO SEE NEW COMMENTS DUE TO
 CHANGES IN PLANS/DESIGN AND SOME SHEETS
 MISSING FROM PREVIOUS SUBMITTED PLANS.
  
 THESE ARE TAKEN DIRECTLY FROM PREVIOUS
 TWO REVIEWS IN NUMMERICAL ORDER.
  
 1)NOTE: NOTE #1 NO, PLEASE SEE LETTER
 COULD NOT BE LOCATED IN PACKAGE.
  
 2)NOTE: NOTE #2 NO, PLEASE SEE OUTWARD
 SWINGS ON DOORS. PLEASE CORRELATE ALL
 SHEETS SHOWING ELECTRICAL ROOMS ETC.
 PLEASE HAVE PLANS INDICATE GUARD RAILS
 FOR EGRESS PROTECTION FROM SECOND FLR
 GEN RM. PLEASE UNDERSTAND ANY EGRESS IN
 CASE OF AN EMERGENCY OR OTHER MAY RESULT
 IN A LIFE SAFETY SITUATION AS SHOWN ON
 PLANS.
 PLEASE SEE DOORS WERE MOVED IN MAIN
 ELECTRICAL ROOM, HOWEVER, PLEASE SEE
 WALLS AND DOORS ARE SHOWN BUILT DIRECTLY
  
 IN FRONT OF ELECTRICAL EQUIPMENT.
 110.26
 PLEASE SEE MINIMUM STANDING/WALKING AREA
 ON THE OUTSIDE OF ELECTRICAL ROOM AFTER
 LEAVING DOOR SWING AREA. PLEASE SEE
 PLANS STILL MENTIONS: A SIGN TO BE
 PLACED AT DOORS LEAVING ELECTRICAL TO
 READ; "OPEN DOOR CAREFULLY, WATCH FOR
 CARS ON OTHERSIDE OF DOORS" PLEASE KNOW
 IN AN EMERGENCY SITUATION WHEN THE
 POSSIBILTY OF SOMEONE BEING BLINDED OR
 ON FIRE;A SIGN WILL NOT HELP IN EXITING
 ROOM AND ONCE AGAIN CREATING AN ADDITION
 LIFE SAFTEY HAZARD FOR THE PERSON(S)
 EXITING ROOM.
  
 NOTE FOR PANIC HARDWARE WAS PLACED ON
 A-SHEETS, HOWEVER PLEASE PLACE NOTE ON
 ELECTRICAL PLANS FOR ELECTRICAL RMS.
  
 3)NOTE: NOTE #3 OK.
  
 4)NOTE: NOTE #4 OK.
  
 5)NOTE: NOTE #5 OK, CIRCUITS ADDED,
 HOWEVER PLEASE SEE CIRCUITING PER ROOM
 PER 620.23,.24. ONLY ONE ELEVATOR
 MACHINE RM PER CIRCUIT.
 PLEASE SEE NEW NOTES FOR ELEV RM #4.
  
 6)NOTE: NOTE #6 NO, PLEASE SEE MANY
 RECEPTS FOR WALL SPACE ARE STILL
 MISSING. PLEASE SEE MOST LOCATIONS ARE
 REDLINED. 210.52
  
 7)NOTE: NOTE #7 OK.
  
 8)NOTE: NOTE #8 OK, HOWEVER PLEASE SEE
 NEW NOTE FOR NOTE ON E-19.
  
 9)NOTE: NOTE #9 OK.
  
 10)NOTE: NOTE #10 OK.
  
 11)NOTE: NOTE #11 OK, SEE NEW NOTES.
  
 12)NOTE: NO, SEE NOTE #3 FROM PREVIOUS
 REVIEW. PLEASE SEE SOME AREAS ARE SHOWN
 WITH LIVING RM. PLEASE ALSO SEE COMMENTS
 ABOUT CIRCUITING FOR DINING RM AREAS.
  
 13)NOTE: NOTE #13, OK, SHEETS SUBMITTED,
 HOWEVER SEE NEW NOTES DUE TO REVIEW
 BEING POSSIBLE AT THIS TIME.
  
 14)NOTE: NOTE #14 NO, PLEASE SEE MISSING
 KITCHEN GFI RECEPTS PER 210.52C1,
 210.8A6. PLEASE SEE SOME AREAS REDLINED
 ON PLANS.
  
 15)NOTE: NOTE #15 NO, PLEASE SEE
 PREVIOUS NOTES: PLEASE SEE SEE MANY
 RECEPTSWHICH ARE ON SM APPL CIRCUITS
 WHICH ARE IN AREAS NOT PERMITTED UNDER
 NEC 210.52B1
  
 16)NOTE: NOTE #16 OK.
  
 17)NOTE: NOTE #17 OK.
  
 18)NOTE: NOTE #18 OK,
  
 19)NOTE: NOTE #19 NO, SEE PREVIOUS NOTES
 #4 OF SECOND SECTION.
 MANY METER CENTERS STILL SHOWN AS
 "MAINS".
  
 20)NOTE: NOTE #20 OK.
  
 21)NOTE: NOTE #21 OK. SEE NEW NOTES.
  
 22)NOTE: NOTE #22 OK.
  
 23)NOTE: NOTE #23 OK.
  
 24)NOTE: NOTE #OK.
  
 25)NOTE: NOTE #25 OK.
  
 26)NOTE: NOTE #26 OK.
  
 27)NOTE: NOTE #27 OK.
  
 28)NOTE: NOTE #28 OK, HOWEVER SEE NEW
 NOTES.
  
 29)NOTE: NOTE #29 NO, SPECS SUBMITTED
 LIKE PREVIOUS REVIEW, HOWEVER SPECS
 SUBMITTED STILL DO NOT CORRELATE WITH
 PLANS FOR SIZING.
 PLEASE SEE NO SPECS SUBMITTED FOR SUB
 BASE FUEL TANK FOR FIRE REVIEW.
  
 30)NOTE: NOTE #30, NO, PLEASE SEE RISER
 NOTES FOR GENERATOR.
 PLEASE ALSO SEE NOTES PERATAINING TO
 RISER ETC.
  
 31)NOTE: NOTE #31 NO.
 PLEASE SEE BRKRS FROM GEN TO ATS AND OCP
 LISTED ON NOTES.
 PLEASE SEE NEW NOTES ALSO.
  
 32)NOTE: NOTE #32 NO, PLEASE SEE THERE
 ARE NUMEROUS ITEMS ON ELECTRICAL RISER
 DIAGRAM AND NOTES FOR FEEDERS ETC WHICH
 DO NOT CORRELATE.
 PLEASE SEE NEW NOTES PERTAINING TO
 "FEEDER SCHEDULE NOTES" AND "ELECTRICAL
 RISER DIAGRAM".
  
 33)NOTE: NOTE #33 OK.
  
 34)NOTE: NOTE #34, NO, SEE NEW NOTES FOR
 EQUIPMENT GROUNDING MISSING ETC.
  
 35)NOTE: NOTE #35 NO, SEE PREVIOUS TWO
 REVIEWS.
 250.6,250.24,250.110,.250.122 SEE NEW
 NOTES.
  
 36)NOTE: NOTE #36 OK, HOWEVER PLEASE SEE
 250.104 TO BE LISTED ON GROUNDING
 ELECTRODE DETAIL.
 PLEASE SEE SHEETS E-19 MAKES REFERENCES
 TO CODES THAT GROUNDING SHALL BE
 INSATLLED BY, HOWEVER PLEASE SEE FBC
 104.2.1, TECHNICAL CODES SHALL NOT BE
 USED IN LEIU OF PROVIDING THE DETAIL ON
 PLANS.
  
 37)NOTE: NOTE #37 NO, PLEASE SEE THERE
 ARE STILL LOCATIONS ON PLANS WHICH STILL
 REFERENCE CODES FROM 1996/1999 CODES.
  
 38)NOTE: NOTE #38 OK.
  
 39)NOTE: NOTE #39 OK, NO 277V SYSTEMS
 PRESENT.
  
 40)OK
  
 41)OK.
  
 42)OK.
  
 43)OK.
  
 ****************************************
 PLEASE SEE NOTES DIRECTLY TAKEN FROM
 "NEW NOTE" ON 2ND REVIEW".
  
 1)NOTE: NOTE #1 OK.
  
 2)NOTE: NOTE #2 OK.
  
 3)NOTE: NOTE #3 NO, PLEASE SEE MANY
 AREAS SHOWN AS DINING AND LIVING RM
 TOGETHER WHEN "DINING RM/AREA"
 DESIGNATION SHOULD BE MOVED TO CORRELATE
 WITH CIRCUTING SHOWN ON PLANS.
 PLEASE SEE AREAS WHERE A "HALLWAY/FOYER"
 AREA RECEPT IS ON SMALL APPLIANCE
 CIRCUIT.
 PLEASE SEE MANY AREAS REDLINED ON PLANS.
  
 4)NOTE: NOTE #4 NO, PLEASE SEE PREVIOUS
 NOTES , MANY AREAS ON PLANS WHERE METER
 CENTERS ARE STILL SHOWN AS BEING
 "MAINS", PLEASE CORRECT. SEE NEW NOTES
 ALSO.
  
 5)NOTE: NOTE #5, OK, LOAD CALCULATIONS
 AND PANEL SCHEDULES NOW SHOW AHU/HEAT
 LOADS @125%. PLEASE KNOW: ONLY THE OCP
 IS REQUIRED TO BE 125%. HOWEVER, IT IS
 PERMISSIBLE TO TO HAVE LOADS FIGURED AT
 A HIGHER AMOUNT THAN IS REQUIRED.
 NO CORRECTION IS NEEDED.
  
 6)NOTE: NOTE #6 OK.
  
 7)NOTE: NOTE #7 OK.
  
 8)NOTE: NOTE #8 NO, PLEASE SEE MANY
 RECEPTS STILL MISSING . PLEASE SEE
 PREVIOUS NOTES FROM BOTH REVIEWS.
  
 9)NOTE: NOTE #9 OK, SEE ALL SHEETS WERE
 SUBMITTED, HOWEVER PLEASE SEE SOME NOTES
 PERTAINING TO THESE SHEETS WHICH COULD
 NOT REVIEWED ON PREVIOUS SUBMITTAL.
  
 10)NOTE: NOTE #10 OK, HOWEVER PLANS SEE
 ELECTRICAL RM #1 EAST ELEVATION, ONE
 SHOWS 110,000 AND THE OTHER 100,000?
  
 11)NOTE: NOTE: OK, ALL ELECTRICAL
 REMOVED FROM VAULT.
  
 12)NOTE: NOTE #12 NO, SAME COMMENT.
  
 13)NOTE: NOTE #13 OK.
  
 14)NOTE: NOTE #14 OK.
  
 15)NOTE: NOTE #15 OK, HOWEVER SEE NEW
 NOTES;
  
 16)NOTE: NOTE #16 NO, PREVIOUSLY NOTED
 ON THIS REVIEW.
  
 17)NOTE: NOTE #17 OK, HOWEVER SEE NEW
 NOTES FOR FEED FROM FPL.
  
 18)NOTE: NOTE #18 NO, PLEASE SEE ALL
 UNPROTECTED CONDUCTORS/BUS-DUCT IS STILL
 SHOWN "INSIDE" BLDG. INSTALLATION AS
 SHOWN SHALL NOT BE PERMITTED AS SHOWN.
 THIS WAS GONE OVER IN MEETING ,YET PLANS
 STILL CAME BACK WITH NO CORRECTIONS?
 PLEASE SEE 230.70,230.6 ETC.
  
 19)NOTE: NOTE #19 NO, PLEASE SEE HDP-2
 STILL SHOWN AS A "SHUNT TRIP".??
  
 20)NOTE: NOTE #20 NO,? PLEASE SEE HDP-2
 IS STILL SHOWN AS GF PROTECTED. PLEASE
 ALSO SEE NEW NOTE ABOUT ATS.
 PLEASE SEE 230.95,240.13 GF PROTECTION
 IS NOT REQUIRED, HOWEVER MAY BE
 INSTALLED. PLEASE ATS NOTE:
  
 21)NOTE: NOTE #21 OK? NOT NEEDED ,
 HOWEVER MAY BE DONE.
  
  
 ****************************************
 NEW NOTES FOR 3RD REVIEW.
  
 1)NOTE: PLEASE SEE ELEVATOR RM #4.
 PLEASE SEE STATE ELEVATOR CODE. ELEVATOR
 MACHINE ROOM SHALL CONTAIN NO OTHER
 EQUIPMENT, USEAGE , ELECTRICAL EQUIPMENT
 ETC UNLESS DIRECTLY USED FOR ELEVATOR
 EQUIPMENT.
 PLEASE SEE ROOM #4, SHOWS "TRASH RM, AND
 "MECH RM" THIS IS NOT PERMITTED.
 THESE RMS WILL BE REQUIRED TO BE
 SEPARATED.
 PLEASE ALSO SEE REQUIREMENTS FOR TRASH
 RMS UNDER LS 101.
  
 2)NOTE: PLEASE CORRELATESIZES OF
 SWITCH GEAR MAINS. PLEASE SEE ONE SHEET
 SHOWS 3000A'S, RISER SHOWS 4,000A'S?
 PLEASE SEE REDLINED PLANS. SG #5?
  
 3)NOTE: PLEASE SEE LS 7-9. PLEASE SEE
 ALTERNATING CIRCUITS FOR EM LTS IN
 STAIRS WILL BE REQUIRED. THIS IS TO
 ALLEAVIATE EGRESS AREAS TO BE IN TOTAL
 DARKNESS BYT THE TRIPPING OF A SINLGE
 BRKR. PLEASE SEE A BATTERY BACK UP
 FIXTURE MAY BE INSTALLED AT EVERY OTHER
 LEVEL AS AN OPTION. PLEASE SEE EGRESS
 HALLWAYS AS SHOWN ON PLANS ALREADY HAVE
 BATTERY BACK LTS SHOWN. EVEN IF A BRKR
 FROM EDP TRIPS, EGRESS LIGHTNING WILL
 STILL BE PROVIDED.
  
 4)NOTE: PLEASE SEE SHEET #19 IS NOW
 SUBMITTED. PLEASE SEE SD NOTES:
 ONE NOTE MENTIONS FOR SD'S TO BE WIRED
 TO KITCHEN/BATH LIGHTING CIRCUIT,
 HOWEVER CIRCUITING ON PLANS DO NOT
 CORRELATE WITH THIS STATEMENT.
 PLEASE SEE KITCHEN/BATH LIGHTING
 CIRCUITS DO NOT INDICATE REQUIRED ARC
 FAULT PROTECTION AS REQUIRED UNDER 2002
 NEC 210.12. PLEASE ADJUST NOTE OR
 PLANS/CIRCUITS ETC.
  
 PLEASE SEE SECOND SD NOTE MENTIONS SD'S
 MAY BE WITHIN 20' OF KITCHEN COOKING
 APPLIANCE. THIS IS PERMITTED HOWEVER
 PLEASE SEE NFPA-72 8-1.4.2, A SPECFIC
 TYPE OF SD'S SHALL BE REQUIRED FOR ANY
 SMOKE DETECTORS CLOSER THAN 20' TO A
 COOKING APPLIANCE.
  
 5)NOTE: PLEASE CORRELATE RISER , RISER
 NOTESETC, PLEASE SEE RISER, PANEL
 SCHEDULES ETC INDICATE BUS-DUCT AND ALOS
 INDICATES FEEDERS ETC.
 PLEASE SEE NUMEROUS ITMES WHICH DO NOT
 CORRELATE.
  
 A) PLEASE SEE MAINS LISTED ON RISER
 DIAGRAM EQUIPMENT SCHEDULE ITME #4? THIS
 COULD NOT BE LOCATED ON RISER.
  
 B) PLEASE SEE MAIN DISC SHOWN AS 150A
 FOR ELEVATORS , YET NOTE MENTIONS
 200A'S.
  
 C)PLEASE SEE FEEDER SCHEDULES AND
 EQUIPMENT NOTES DO NOT CORRELATE FOR
 MAINS SEC'S OR BUS-DUCT.
  
 D)PLEASE SEE FEEDER SCHEDULE 5,7,8,9 AND
 10. PLEASE SEE THESE DO NOT CORRELATE
 WITH PANEL SCHEDULES FOR FEEDERS, ETC.
 PLEASE SEE THESE DO NOT INCLUDE ANY
 EQUIPMENT GRNDS?
  
 E)NOTE:PLEASE SEE SW GR #2 ONLY SHOWS
 ONE FEEDER TO MC'S. ETC ETC.
 MOST OF THESE ITEMS WERE REDLINED.
  
 6)NOTE: PLEASE SEE SEE FEEDER SCHEDULE
 MENTIONS ALL FEEDS TO APT UNITS TO BE IN
 EMT? PLEASE VERIFY THIS.PLEASE SEE EMT
 MAY NOT BE INSTALLED IN CONCRETE.
 ONLY IF OVERHEAD.
  
 7)NOTE:PLEASE SEE EQUIPMENT GROUNDING
 CONDUCTOR SHOWN FROM FPL TO FIRST MEANS
 OF DISCONNECT FOR FIRE PUMP. PLEASE SEE
 250.6, 250.24, EQP GRNDS SHALL ONLY BE
 INSTALLED "AFTER" THE FIRST MENS OF
 DISCONNECT.
  
 8)NOTE: PLEASE SEE OTHER CONDUITS ETC ON
 RISER MISSING ANY MENTION OF EQUIPMENT
 GROUNDING CONDUCTORS. PLEASE SEE FEEDERS
 FROM GEN TO FIRE PUMP AND EM ATS, EDP(SW
 GR #4).
 250.110, 250.122
  
 9)NOTE: PLEASE SEE ATS FOR EM STAND-BY
 IS NOTED AS GFCI PROTECTED?
 PLEASE SEE EQUIPMENT PROTECTION WOULD BE
 GF PROTECTED, NOT GFCI FOR PERSONNEL
 PROTECTION. PLEASE SEE GF PROTECTION OS
 NOT REQUIRED ON EM STAND-BY SYSTEMS OF
 THIS VOLTAGE AND SIZE. 240.13,230.95
 ETC. THIS IS ONLY NOTED AS TO WHY ?
 PLEASE SEE 701.17 FOR "LEGALLY REQUIRED
 STAND-BY SYSTEMS".
  
 10)NOTE: PLEASE SEE PREVIOUS NOTE FROM
 THIRD REVIEW5)D: WHICH MENTIONS
 CORRELATION OF FEEDER SCHEDULES.
 PLEASE SEE FEEDERS FOR ALL RTU'S, POOL
 PANEL. PLEASE SEE EDP'S AND HDP'S PANEL
 SCHEDULES AND FEEDERS INDICATED AT THOSE
 LOCATIONS. PLEASE CORRELATE.
 SEE NEW NOTE IN REF TO POOL PANEL.
  
 11)NOTE: PLEASE SEE NOTE #6 ON NOTES
 LISTED ON THE UPPER RIGHT HAND CORNER OF
 RISER DIAGRAM SHEET. THIS MENTIONS:
 "ONLY FOUR ELEVATOR THRU EMERGENCY
 GENERATOR"??
 PLEASE CLARIFY AS ONLY ONE ELEVATOR IS
 LISTED ON SWITCH GEAR MAIN #4?
 PLEASE SEE FIRE DEPARMENT REQUIREMENTS
 FOR ELEVATOR ON EM GEN SHALL ALSO BE
 STRETCHER ACCESSSIBLE. SEE ANY FIRE
 REVIEW NOTES FOR THIS.
  
 12)NOTE: PLEASE SEE SWITCH GEARR #4
 INDICATES CONNECTED LOAD OVER 1600 A'S
 ON A 2000A MAIN WITH A 2000A FEED FROM
 FPL. THIS IS OK, HOWEVER , PLEASE SEE
 ATS IS ALSO SHOWN AS HAVING 2000A
 CAPACITY, AND SERVICE ENTRANCE
 CONDUCTORS FROM FPL SHOWN FOR 2000A'S
 YET GENERATOR ONLY SHOWS A 1600A MCB?
 PLEASE EITHER INCREASE FEED FROM
 GENERATOR TO CORRLELATE WITHALL OTHER
 EQUIPMENT TO 2000A'S OR PLEASE PROVIDE
 LOAD CALCUALTIONS FOR ANY DERATING.
 PLEASE BEAR IN MIND FUTURE POSSIBLE
 LOADS OF ANY ADDITIONS.
 PLEASE SEE 90.8WHICH REQUIRES PLANS
 AND SPECIFICATIONS THAT PROVIDE AMPLE
 SPACE IN RACEWAYS, SPARE RACEWAYS, AND
 ADDITIONAL SPACES ALLOW FOR FUTURE
 INCREASES IN THE USE OF ELECTRICITY.
 DISTRIBUTION CENTERS LOCATED IN READILY
 ACCESSIBLE LOCATIONS PROVIDE CONVENIENCE
 AND SAFETY OF OPERATION.
 THE REQUIREMENT FOR PROVIDING THE
 EXCLUSIVELY DEDICATED EQUIPMENT SPACE
 MANDATED BY 110.26(F) SUPPORTS THE
 INTENT OF 90.8(A) REGARDING FUTURE
 INCREASES IN THE USE OF ELECTRICITY.
 DISTRIBUTION CENTERS SHOULD CONTAIN
 ADDITIONAL SPACE AND CAPACITY FOR FUTURE
 ADDITIONS AND SHOULD BE CONVENIENTLY
 LOCATED FOR EASY ACCESSIBILITY.
 THIS SHOULD ALSO BE TAKEN IN NOTE FOR
 ALL SERVICE EQUIPMENT AND THE
 POSSIBILITY OF ANY FUTURE EXPANTION.
 PLEASE SEE NO LOAD CALCULATIONS WERE
 SUBMITTED FOR MAINS 4 AND 5. IF LOAD
 CALCULATIONS ARE SUBMITTED, PLEASE SHOW
 ALL CONTINUOUS LOADS (3OR MORE HOURS) AT
 125%. 215.3,100,230.42 ETC.
  
 13)NOTE: PLEASE SEE POOL PANEL IS NOW
 SHOWN ON RISER AS NOTED IN NEW NOTE #10,
 HOWEVER PLEASE SEE NO POOL PANEL
 SCHEDULE WAS SUBMITTED? PLEASE ALSO
 INCLUDE LOADS ON PANEL. PLEASE SEE
 PREVIOUS NOTE ABOUT FEEDERS LISTED ON
 RISER SCHEDULES, RISER AND HDP-3.
  
 14)NOTE: PLEASE SEE MANY OF THE ABOVE
 ITEMS AS NOTED HAVE BEEN REDLINED ON
 PLANS AT AREAS OF NOTES. THIS IS IN NO
 WAY EVERY LOCATION OF SAID COMMENTS.
  
 15)NOTE: PLEASE BE SURE TO SEE ANY
 POSSIBLE COMMENTS FROM OTHER REVIEWERS
 WHICH MAY AFFECT ELECTRICAL PLANS.
 IE: DOOR SWINGS, EGRESS ETC.
  
 16)NOTE: PLEASE KNOW, A RESPONSE LETTER
 LISTING REVIEWERS COMMENTS AND ACTION
 TAKEN BY DESIGN TEAMWOULD HELP IN THE
 REVIEW PROCESS.
  
 17)NOTE: PLEASE REMOVE ANY OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.
 IT IS SUGGEESTED AN ADDITIONAL MEETING
 BE SET UP TO GO OVER ALL COMMENTS ONCE
 ALL REVIEWS ARE DONE FOR TRADES.
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-07-12 00:00:00ONE ROLL AND SPECS BOOKS IN ELECTRICAL
 FOR REVIEW.
 WAITING FOR REVIEW,

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-04-15 Cont ID  
Sent By dpalmer Date 2005-04-15 Time 15:43 Rev Time 15.00
Received By dpalmer Date 2005-04-14 Time 18:31 Sent To  
Notes
2005-04-15 00:00:00********** UNSAT 2ND REVIEW ***********
  
 REVIEW FOR "THE PLACE VIA CLEMATIS";
 PLEASE SEE PLANS ARE SUBMITTED FOR "PLAN
 REVIEW ONLY" AND NOT SUBMITTED FOR
 PERMIT.
  
 PLEASE SEE MANY COMMENTS FROM PREVIOUS
 REVIEW STTILL NEED TO BE ADDRESSED.
  
 PLEASE SEE NEW COMMENTS DUE TO MORE
 INFORMATIONPROVIDED FROM PREVIOUS SET
 OF PLANS.
 HOWEVER PLEASE SEE NEW COMMENT FOR PAGES
 MISSING. STILL UNABLE TO DO A FULL AND
 COMPLETE REVIEW DUE TO PLANS AND SPECS
 NOT BEING COMPLETE AT THIS TIME.
  
 1)NOTE: NOTE #1, NO, PLEASE SEE LETTER
 FOR ENGINEER TO BE SIGNED, DATED AND
 NOTORIZED FOR LEGAL SIGNATURE.
 TITLE BLOCKS "WHITED OUT" FOR FIRM NAME.
  
 2)NOTE: NOTE #2 NO, PLEASE SEE OUTWARD
 SWING IS NOW SHOWN, HOWEVER NOTE(S)
 REQUESTED ON PLANS FOR PANIC HARDWARE
 ETC WAS NOT ADDED.
  
 3)NOTE: NOTE #3 OK
  
 4)NOTE: NOTE #4 OK
  
 5)NOTE: NOTE #5 NO, PLEASE SEE 620.22-25
 PLEASE ALSO SEE LAYOUT FOR ELEV MACHINE
 ROOMS ARE MISSING ELECTRICAL EQUIPMENT.
 ETC.
  
 6)NOTE: NOTE #6 NO,PLEASE SEE PREVIOUS
 NOTES: MANY WERE ADDED HOWEVER THERE ARE
 STILL SOME MISSING, PLEASE SEE REDLLINED
 PLANS.210.52
  
 7)NOTE:NOTE #7 OK.
  
 8)NOTE: NOTE #8 OK.
  
 9)NOTE: NOTE #9 OK.
  
 10)NOTE: NOTE #10 OK.
  
 11)NOTE: NOTE #11 OK.
  
 12)NOTE: NOTE#12 NO, PLEASE SEE SOME
 ROOM DESIGNATIONS WERE ADDED HOWEVER
 SOME AREAS ARE STYILL MISSING.
 PELASE ALSO SEE NEW COMMENTS PERTAINING
 TO "DINING AREA".
  
 13)NOTE: NOTE #13 NO, PLEASE SEE E-19
 WAS NOT SUBMITTED. PLEASE SEE NEW
 COMMENTS PERTAINING TO "NEW " SHEETS
 MISSING.
  
 14)NOTE: NOTE #14 NO, PLEASE SEE SOME
 STILL MISSING. REDLINED.
  
 15)NOTE: NOTE #15 NO.PLEASE SEE MANY
 AREAS RECEPTS ARE SHOWN IN AREAS OTHER
 THAN "DINING AREA". PLEASE SEE SOME ARE
 HALLWAYS, FOYERS, LIVING RMS? ETC.
 PLEASE SEE PREVIOUS COMMENT ABBOUT
 DEIGNATED AREAS.
  
 16)NOTE: NOTE #16, OK.
  
 17)NOTE: NOTE #17 OK.
  
 18)NOTE: NOTE #18 OK.
  
 19)NOTE: NOTE #19 OK, HOWEVER, PLEASE
 SEE NEW NOTES BELOW PERTAINING TO
 LABELING OF METER CENTERS. ETC.
  
 20)NOTE: NOTE #20 OK.
  
 21)NOTE: NOTE #21OK.
  
 22)NOTE: NOTE #22 OK, HOWEVER PLEASE SEE
 NEW NOTES PERTAINING TO LABELING AND
 ELECTRICAL ROOMS. SAME AS #19.
  
 23)NOTE: NOTE #23 NO.
  
 24)NOTE: NOTE #24 OK, PLEASE SEE NEW
 NOTES PERTAINING TO FIRE PUMP FEED FROM
 EM DP.
  
 25)NOTE: NOTE #25 OK.
  
 26)NOTE: NOTE #26 OK.
  
 27)NOTE: NOTE #27 NO.
  
 28)NOTE:NOTE #28 NO, PLEASE SEE
 INFORMATION FOR FIRE PUMP, FIRE PUMP
 CONTROLLER/ATS DISCONNECTIN MEANS WAS
 NOT SUPPLIED.
 PLEASE ALSO SEE NEW NOTES DUE TO FIRE
 PUMP FEED FROM EDP.
  
 29)NOTE: NOTE #29 NO, SPECS FOR
 GENERATOR WERE SUBMITTED , HOWEVER THEY
 DO NOT CORRELATE TO PLANS.
  
 30)NOTE: NOTE #30 NO, PLEASE SEE RISER.
  
 31)NOTE: NOTE #31 NO.
  
 32)NOTE: NOTE #32 NO.
  
 33)NOTE: NOTE #33 OK
  
 34)NOTE: NOTE #34 OK, HOWEVER SEE NEW
 NOTES PERTAINING TO EQUIPMENT GROUNDING.
  
 35)NOTE: NOTE #35, NO.
  
 36)NOTE: NOTE #36 OK.
  
 37)NOTE:NOTE #37 NO, PLEASE ALSO SEE
 NEW NOTES PERTAINING TO MISSING SHEETS.
  
 38)NOTE:NOTE #38 OK.
  
 39)NOTE: NOTE #39 NO, SEE NEW NOTES
 PERTAING TO MISSING SHEETS.
  
 40)NOTE: NOTE #40 RESPONSE NOT NEEDED,
 PLEASE SEE PLASN, ONCE AGAIN MOST AREAS
 REDLINED FOR ABOVE NOTES AND FOR NEW
 NOTES TO FOLLOW.
  
 41)NOTE: NOTE #41 NO RESPOSE NEEDED.
  
 42)NOTE: NOTE #42 NO, AS REQUESTED ON
 PREVIOUS REVIEW, PLEASE "REMOVE" ALL
 OLD/VOIDED SHEETS FROM SETSS AND ONLY
 INSERT NEW REVISED SHEETS INTO THREE
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SEE THESE SHEETS WERE NOTE
 REMOVED AND LEFT IN SETS.
  
 43)NOTE: NOTE #43 , NO RESPONSE NEEDED.
  
  
 ************** NEW NOTES *************
  
 1)NOTE: PLEASE SEE PANEL LOCATED ON
 BATHRM, UNIT L/WD-3.
  
 2)NOTE: PLEASE ALSO SEE SMALL APPLIANCE
 CIRCUIT SHOWN IN BATH. L/WD-3
 210.52C1
  
 3)NOTE: PLEASE SEE AREAS FOR DINING
 NEED TO BE CLARIFIED. PLEASE SEE
 PREVIOUS COMMENTS ABOUTAREAS WHICH
 SHOWDEVICES ON SAME CIRCUITS AS SMALL
 APPLIAANCE, HOWEVER SOME OF THESE AREAS
 ARE NOT AREA ALLOWED TO BE ON SM APPL
 CIRCUITS.
 PLEASE SEE NEC 210.52B
  
 4)NOTE: PLEASE SEE MANY LOCATION ON
 PLANS, EQUIPMENT IS LABEL AS MAIN, 1OF 2
 ETC YET, THEY ARE NOT MAINS.
 PLEASE SEE METER CENTERS WHICH ARE SHOWN
 AS MAINS, PLEASE SEE ELECTRICAL
 ROOM/AREA NEXT TO MAIN SWITCH GEAR WHICH
 SHOW ADDITIONAL MAINS ALSO.
 THE ATCUAL MAINS SHOULD BE THE ONLY
 EQUIPMENT LABELED AS SUCH. PLEASE
 RE-IDENTIFY ALL OTHER EQUIPMENT.
 215.5,230.2E ETC.
  
 5)NOTE: PLEASE CORRELATE A/C, AHU LOADS
 FOR UNITS. PLEASE SEE PANEL SCHEDULES
 AND ACTUAL LOAD CALCULATIONS.
 ONE SHOWS 7.5KW AND THE OTHER SHOWS
 10KW?
  
 6)NOTE: PLEASE SEE ELECTRICAL SYSTEMS
 FOR BLDG ELECTRICAL SEEMS TO ALL BE
 120/208V, HOWEVER, PLEASE SEE ELECTRICAL
 PANELS FOR UNIT SHOW 120/240V?
 PLEASE ADJUST.
  
 7)NOTE: PLEASE SEE MISSING SD IN L/WD-3.
  
 8)NOTE: PLEASE SEE SOME MISSING RECEPTS
 PER 210.52, 210.52C1, AS NOTED ON
 PREVIOUS COMMENT.
  
 9)NOTE: PLEASE SEE MISSING SHEETS FROM
 SETS. E-9,10 AND 19. PLEASE SEE ONNLY
 OLD/VOIDED SHEETS ARE IN SETS.
 UNABLE TO REVIEW THESE PAGES AT THIS
 TIME.
  
 10)NOTE:PLEASE VERIFY AIC RATINGS SHOWN
 ON PANEL SCHEDULESAND RISER. PLEASE
 SEE 110K ETC.
 THIS IS ONLY A NOTE AND SOME AIC RATINGS
 SEEM A LITTLE HIGH, HOWEVER THESE ARE
 PERMITTED. HOWEVER, IF SHOWN ON PLANS,
 THEN THESE WILL BE REQUIRED TO BE
 INSTALLED.
  
 11)NOTE: PLEASE SEE FPL VAULT IS NOT
 PERMITTED TO HAVE ANY ELECTRICAL IN ROOM
 WHICH IS PART OF BLDG ELECTRICAL .
 PLEASE SEE LTS, RECEPTS MUST BE REMOVED
 FROM PLANS.
 AS PER CONVERSATION WITH BILL HARTIGAN
 FROM FPL.
 PLEASE ALSO BE SURE TO CONTRACT FPL FOR
 SIZING OF FPL VAULT AND ANY OTHER
 REQUIREMENTS THERE MAY BE.
  
 12)NOTE: PLEASE SEE SOME ELEVATION
 DRAWINGS SHOW "OLD METER"??
 PLEASE CLARIFY?
 215.5
  
 13)NOTE: PLEASE SEE NOTES PERTAINING TO
 "SIGNS FOR ELEVATORS" MENTIONS HEIGHT
 REQUIREMENTS FOR LETTERING TO BE MIN OF
 1/8", PLEASE CLARIFY THIS. PLEASE SEE
 MIN SIGNAGE IN NFPA, LS 101, NEC ETC,
 ALL MENTIONS A MIN OF 1" LETTERS ON A
 CONTRASTING BACKGROUND.
  
 14)NOTE:PLEASE SEE PANEL HDP-3, WHICH
 SHOWS A FUTURE POOL PANEL, YET RISER
 SHOWS PANEL INSTALLED AT THIS TIME .
 PLEASE ALSO SEE ALL PLANS INDICATE POOL
 BEING BUILT WITH BLDG. PLEASE SEE EVEN
 THOUGH POOL IS REQUIRED UNDER SEPARATE
 PERMIT, ALL ELECTRICAL INFORMATION IS
 ALSO REQUIRED ON BASE BLDG PLANS.
 PLEASE PROVIDE INFORMATION FOR NEW PANEL
 HP. PLEASE PROVIDE FEED, OCP, CONDUIT
 ETC.
  
 15)NOTE: PLEASE CLARIFY TWO SEPARATE
 FEED TO SINGLE RTU'S. RISER SHOWS
 4-RTU'S, HOWEVER, RISER SHOWS POWER
 COMING FROM TWO DIFFERENT FEEDS AND
 EQUIPMENT.
  
 16)NOTE: PLEASE SEE SPECS AND CORRELATE
 WITH PLANS, THIS WAS NOTED ON PREVIOUS
 COMMENT ALSO.
  
 17)NOTE: PLEASE SEE DESIGN FOR FIRE PUMP
 HAS NOW COMPLETELY CHANGED. PLEASE SEE
 FIRE PUMP IS NOW BEING SHOWN BEING FED
 FROM FPL, DIRECTLY, WHICH IS FINE,
 HOWEVER FIRE PUMP IS NOW BEING FED FROM
 EDP?
 PLEASE SEE IF EDP IS SHUT DOWN IN BLDG
 DUE TO FIRE, THE FIRE PUMP WOULD NOW BE
 DISABLED DUE TO FEED COMING FROM EDP.
 PLEASE SEE 695 .
 PLEASE SEE ATS AT GENERATOR WOULD BE
 REQUIRED TO HAVE A MAIN. PLEASE SEE
 RISER ALSO INDICATES ATS AT GENERATOR
 HAVING A FEED DIRECTLY INTO FPL VAULT??
 RISER SHOWS TWO FEEDS FROM FPL TO FIRE
 PUMP AND EDP.
 PLEASE SEE THERE ARE TOO MANY ISSUES
 WITH THE WAY THE RISER SHOWS FEEDS TO
 TYPE IN A RESPONSE/PLANS REVIEW NOTES.
  
 PLEASE CALL OR MEET TO GO OVER THIS
 SCENERIO.
  
 18)NOTE: PLEASE SEE RISER INDICATES ALL
 FED INTO FPL VAULT AS OVER HEAD. PLEASE
 SEE AS PER NEC AND LOCAL AMENDMENTS, NO
 MORE THAN 8' OF "UNPROTECTED" CONDUCTORS
 MAY BE INSIDE BLDG. 230.70
 PLEASE SEE THESE APPEAR THEY MAY BE
 REQUIRED TO BE "INCASED IN CONCRETE"
 ETC.
  
 19)NOTE: PLEASE SEE ALL MAINS ARE SHOWN
 AS HAVING A SHUNT TRIP, PLEASE CLARIFY
 IF THESE MAINS ALSO CONTAIN A MANUAL
 MEANS OF DISC LOCATED ON THE OUTSIDE.
 230.76,230.79
  
 20)NOTE: PLEASE SEE ALL MAINS ARE SHOWN
 WITH GROUND FAULT PROTECTION ??
 PLEASE SEE 230.95,240.13THIS IS ONLY A
 NOTE:
  
 21)NOTE: PLEASE SEE 424.3B, OCP FOR
 AHU'S INT UNITS IS THE ONLY THING WHICH
 IS TO BE AT 125%, LOAD CALCS DO NOT HAVE
 TO BE SHOWN AT 125%.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
2005-04-14 00:00:00IN FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-11-23 Cont ID  
Sent By dpalmer Date 2004-11-23 Time 15:04 Rev Time 12.00
Received By dpalmer Date 2004-11-18 Time 20:01 Sent To  
Notes
2004-11-23 00:00:00*************** UNSAT *****************
  
 PLEASE SEE THE FOLLOWING COMMENTS CAN
 ONLY BE BASED ON PLANS SUBMITTED.
 DUE TO PLANS AND SUBMITTAL PACKAGE NOT
 BEING COMPLETE AT THE TIME OF REVIEW,
 THERE MAY BE ADDITIONAL COMMENTS WHEN
 PLANS ARE RE-SUBMITTED.
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002 FOR
 MISSING REQUIRED INFORMATION ON TITLE
 BLOCK.
 PLEASE ALSO SEE FS 471.023 FOR
 REQUIREMENTS.
 PLEASE ALSO SEE FS 471.025 FOR "RAISED"
 SEAL TO BE CLEAR AND VISABLE WITH ALL
 INFORMATION ON SEAL.
 PLEASE PROVIDE A SIGNED,DATED AND SEALED
 NOTORIZED LETTER FOR VERIFICATION OF
 LEGAL SIGNATURE. PLANS APPEAR TO BE
 SIGNED WITH INITIALS WHICH ARE NOT
 PERMITTED UNDER FS 471.025.
 IF INDEED LEGAL SIGNATURE, PLEASE
 PROVIDE LETTER FOR "SIGNATURE FILE" FOR
 FUTURE REFERENCE.
 THIS IS REQUIRED FOR ALL SHEETS AND FOR
 ALL TRADES WHEATHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 2)NOTE:PLEASE SEE 110.26 FOR ALL
 ELECTRICAL ROOMS AND DOOR REQUIREMENTS.
 PLEASE REVISE PLANS TO SHOW OUTWARD
 SWING AND PROVIDE NOTE FOR PANIC
 HARDWARE ETC.
 ** PLEASE SEE ANY EGRESSISSUE THAT MAY
 ARISE WITH DOOR SWING** THIS IS ONLY A
 NOTE:.
  
 3)NOTE: PLEASE SEE THERE ARE NUMEROUS
 LOCATIONS WHERE "COMMON AREA" LIGHTING
 IS BEING CONTROLLED BY A WALL SWITCH.
 THIS WOULD CREATE A SAFTEY ISSUE DUE TO
 LTS IN ARE BEING TURNED OUT WHEN PERSONS
 ARE IN MODE OF EGRESS.
 *TYP* LTS IN COMMON AREAS ARE HARDWIRED
 TO SYSTEMS ELECTRICAL LIKE MANY OF THE
 OTHER COMMONAREAS?
 LS 101 5-8
  
 4)NOTE: PLEASE SEE SOME ELEVATOR LOBBY
 AREAS WHICH PLASN DO NOT CONTAIN ANY
 LIGHTING? ELEV 4 LOBBY)
  
 5)NOTE: PLEASE SEE 620.24ABC FOR MISSING
 REQUIRED LTS/RECEPTS ETC.
  
 6)NOTE: PLEASE SEE RECEPT SPACING IN
 NUMEROUS UNITS. PER 210.52
 PLEASE SEE MANY ARE REDLINED AT
 LOCATIONS REQUIRED ON ONE SET OF PLANS
 SUBMITTED. PER 2',6',12' RULE.
 PLEASE ALSO SEE MEZZ AREAS.
  
 7)NOTE: PLEASE SHOW CIRCUITING ON PLANS
 FOR ALL ELECTRICAL DEVICES SHOWN AND
 CORRELATE WITH THE SUBMITTED PANEL
 SCHEDULES. (SD'S ETC.)
  
 8)NOTE: PLEASE SEE CIRCUITING OF SD'S ON
 BATH/KIT LT CIRCUITS WHICH IS OK,
 HOWEVER BATH /KIT LIGHTS WILL THEN
 REQUIRE ARC-FAULT PROTECTION.
 2002 NEC 210.12
  
 9)NOTE: PLEASE SEE SOME CONDENSING UNITS
 SHOWN IN GARAGE ON E-5, PLEASE SHOW ALL
 DISC'S/CIRCUITING PER 440.11
 PLEASE ALSO INCLUDE REQUIRED GFI PER
 210.63
  
 10)NOTE: PLEASE SEE 210.52H FOR "HALL"
 AREA RECEPT SPACING. SOME UNITS UNITS ON
 TYPICAL FLRS.
  
 11)NOTE: PLEASE SEE 700.16 FOR ALL
 ELECTRICAL/ELEVATOR/FIRE COMMAND RMS
 ETC
 FOR LIGHTING REQUIREMENTS.
  
 12)NOTE: PLEASE PROVIDE ROOM
 DESIGNATIONS ON PLANS.
  
 13)NOTE: PLEASE SEE LOCATIONS OF SD'S
 ARE TO BE INSTALLED PER NFPA-72
 8-1.4.1.6.2 AND 8-1.4.2
 3' OF BATH RM DOORS ETC. PLEASE REVISE
 NOTE ON E-19 WHICH MENTIONS SD'S OK TO
 INSTALL W/IN 20' OF COOKING APPLIANCE.
 THIS IS ONLY PERMITTED WITH EXCEPTIONS
 LISTED.
  
 14)NOTE: PLEASE SEE SOME MISSING GFI
 RECEPTS REQUIRED IN SOME UNITS PER
 210.52C1, GFI PER 210.8A6
  
 15)NOTE: PLEASE SEE CIRCUITING FOR
 DINING ROOM/AREA RECEPTS. PLEASE
 DESIGNATE AREA/RM. PLEASE SEE 210.52B1
  
 16)NOTE: PLEASE SEE UPPER ROOF LEVELS.
 PLEASE COMPLETE ELECTRICAL PLANS AS SOME
 OF THESE AREAS ON PLANS DO NOT INDICATE
 ANY ELECTRICAL.; LTS, RECEPTS ETC.
 RECEPTS REQUIRED W/IN 20' OF POOL.
 680.22A1
  
 17)NOTE: PLEASE SEE ALL COND UNITS ON
 UPPER ROOF LEVEL. PLEASE INDICATE ALL
 REQUIRED DISCONNECTS PER 440.11 AND
 GFI'S PER 210.63,210.8
  
 18)NOTE:PLEASE SEE MISSING EGRESS
 LIGHTING FOR STAIRS ON ROOF PLANS.
 LS101 5-8. PLEASE SEE POSSIBLE COMMENTS
 FROM FIRE/BLDG REVIEW FOR THIS.
  
 19)NOTE: PLEASE CORRELATE METER CENTER
 MAINS ON RISER/ PLANS / ELEVATION
 RISER.
 PLANS INDICATE 700A MAINS, HOWEVER OTHER
 AREAS INDICATE 1000A?
 215.5
  
 20)NOTE: PLEASE 240.4C FOR SIZING OF ALL
 CONDUCTORS FOR DEVICES RATED OVER
 800A'S
 PLEASE ALSO SEE 310.16,110.14 FOR RATING
 OF CONDUCTORS AND TEMP LIMITATIONS.
  
 21)NOTE: PLEASE CORRELATE # OF
 CONDUCTORSIN THE # OF SETS AND # OF
 CONDUITS ON E-17
  
 22)NOTE: PLEASE SEE "SWITCH GEAR RM",
 PLEASE SHOW LAYOUT OF ROOM WITH LOCATION
 OF ALL ELECTRICAL EQUIPMENT AND MAINS.
  
 23)NOTE: PLEASE CORRELATE RISER DIAGR
 AND PLANS WITH ELECTRICAL EQUIPMENT AND
 WHICH LEVEL EQUIPMENT IS ON.
  
 24)NOTE: PLEASE SEE MAIN FOR EM POWER
 DISTRIBUTION IS REQUIRED TO BE GROUPED
 CLOSER THAN SHOWN ON PLANS. TRAVEL
 DISTANCE AND PLANS INDICATING THESE
 MAINS AND SHUT-DOWNS ON DIFFERENST
 LEVELS AND XX FEET APART WILL NOT BE
 APPROVED BY FIRE MARSHAL'S OFFICE OR
 ELECTRICAL PLAN REVIEW.
 PLEASE SEE 230.72,230.70,230.76,230.79
 PLEASE BE AWARE "SHUNT-TRIPS" ARE NOT AN
 ACCEPTABLE METHOD FOR COMPLIANCE.
  
 25)NOTE: PLEASE SEE E-6, PLEASE IDENTIFY
 WHAT APPEARS TO BE TWO PIECES OF EM
 ELECTRICAL EQUIPMENT.
 215.5
  
 26)NOTE:PLEASE SEE PANEL SCHEDULES WERE
 SUBMITTED FOR MAINS 1,2,3 ON E-17, BUT
 NONE FOR MAINS 4,5 ? PLEASE SHOW
 215.5
  
 27)NOTE:PLEASE SEE RISER DIAGRAM: PLEASE
 SEE OCP/LOCKED ROTOR FOR FIRE PUMP IS
 SHOWN TO BE A MIN OF 1085A'S, YET FUSES
 ARE INDICATED AS 1000A'S?? PLEASE SEE
 695.4B1
  
 28)NOTE: PLEASE SEE RISER DIAGRAM
 INDICATES FIRE PUMP FEED COMING FROM FPL
 AND METER RM? PLEASE VERIFY WHICH ONE?
 AND WHERE FEED IS COMING FROM.
 PLEASE SUBMIT COMPLETE SPECS ON FIRE
 PUMP AND FIRE PUMP CONTROLLER.
 PLEASE BE SURE THIS IS ALL A LISTED
 UNIT.
 PLEASE BE SURE IT CONTAINS A MAN MEANS
 OF DISC AND RATED FOR LOAD SERVED AND
 MEETS 110.27, 230.76,230.79
 PLEASE ALSO SEE VOLTAGES FOR LOCK ROTOR
 IN TABLE.430.151
  
 29)NOTE: PLEASE SUBMIT COMPLETE SPECS
 FOR GENERATOR AND TRANSFER SWITCH.
 PLEASE CORRELATE PLANS WITH SUBMITTALS.
 215.5
  
 30)NOTE: PLEASE CORRELATE RISER, RISER
 EQUIPMENT SCHEDULE AND GENERATOR NOTES
 FOR TRANSFER SWITCH SIZE AND VOLTAGE.
 ONE SHOWS 1200A, THE OTHER 3500A ETC.
  
 31)NOTE: PLEASE CORRELATE RISER WITH
 GENERATOR NOTES FOR GENERATOR, SHOWS TWO
 DIFFERENT SIZES ETC.875KVA , 1200 KVA
 ETC
 PLEASE SEE PLANS ARE CALLING FOR TWO
 DIFFERENT VOLTAGES FOR SAME EQUIPMNET?
 215.5
  
 32)NOTE: PLEASE SEE ELECTRICAL RISER
 DIAGRAM EQUIPMENT SCHEDULE NOTES: ONLY
 SHOWS NOTES 1-5 YET PLANS/RISER DIAGRAM
 SHOWS MANY MORE AREAS LABELED TO SEE
 NOTES ON EQUIPMENT SCHEDULE. #'S 8,9,18
 ETC ETC.
  
 33)NOTE: PLEASE LABEL EDP ON RISER WITH
 EQUIPMENT SCHEDULE NOTES.;
 215.5
  
 34)NOTE: PLEASE SEE ELEVATOR DISC/
 EQUIPMENT ON RISER WHICH IS SHOWN ON THE
 ROOF AND COMING DIRECTLY FROM TANSFORMER
 VAULT??? MAINS? GROUPING ? OVERCURRENT-
 PROTECTION ETC.
 230.72,230.70,230.76,.230.79,215.5
  
 35)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTORS ON RISER AND OTHER
 AREAS WHICH ARE REQUIRED PER
 250.110,250.24, SIZED PER 250.122
  
 36)NOTE: PLEASE SEE 2002 NEC FOR
 GROUNDING ELECTRODE SYSTEM. 250.50,
 250.66.
  
 37)NOTE: PLEASE SEE THERE ARE NUMEROUS
 LOCATIONS ON PLANS WHICH GIVE REFERENCE
 TO CODES FROM 1996/1999 NEC.
 PLEASE SEE WE ARE UNDER THE 2002 NEC.
 JUST A NOTE: 2002 NEC WAS ADOPTED BY THE
 STATE 7/1/2003
 PLEASE ADJUST ALL LOCATION ON PLANS.
  
 38)NOTE: PLEASE SEE PLANS REFERENCE THE
 SOUTH FLORIDA BLDG CODE.
 PLEASE SEE WE ARE UNDER 2001 FBC WITH
 REVISIONS.
  
 39)NOTE: PLEASE SEE LOCAL AMENDMENST FOR
 COLOR CODING 215.5 FOR 277/480V SYSTEMS
 ETC.
  
 40)NOTE: PLEASE SEE PLANS HAVE BEEN
 REDLINED WITH MOST OF THE ABOVE ITEMS
 AND AREAS OF COMMENTS.
  
 41)NOTE: PLEASE SEE ANY POSSIBLE
 COMMENTS FROM OTHER REVIEWER(S) WHICH
 MAY HAVE AN AFFECT ON ELECTRICAL PLANS.
  
 42)NOTE: PLEASE REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
  
 43)NOTE: PLEASE SEE BLDG REVIEW
 COMMENTS: THIS IS A THRESHOLD BLDG AND
 THREE SETS OF PLANS ARE REQUIRED.
  
  
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
2004-11-18 00:00:00IN ELECTRICAL FOR REVIEW.
 NOTES TO FOLLOW.

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2005-07-01 Cont ID  
Sent By mamini Date 2005-07-01 Time 09:39 Rev Time 1.00
Received By mamini Date 2005-07-01 Time 09:39 Sent To  
Notes
2005-07-01 00:00:00PASSED WITH PROVISOS:
  
 1. PLEASE NOTE THAT ANY WORK WITHIN
 PUBLIC R.O.W REQUIRES A PERMIT FROM
 PUBLIC UTILITIES AND ENGINEERING PRIOR
 TO BEGINNING OF SUCH WORK, 494-1086.
  
 2. POLLUTION / EROSION CONTROL DEVICES
 SHALL BE IN PLACE PRIOR TO BEGINNING ANY
 CONSTRUCTION ACTIVITIES.THE DEVICES
 MUST BE MAINTAINED AND MONITORED
 THROUGHOUT THE CONSTRUCTION PERIOD.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2005-03-23 Cont ID  
Sent By mamini Date 2005-03-23 Time 14:04 Rev Time 1.00
Received By mamini Date 2005-03-23 Time 14:04 Sent To  
Notes
2005-03-23 00:00:00FAILED:
  
 1. PROPOSED SITE MUST BE DESIGNED FOR
 WATER QUALITY AND DRAINAGE PER CITY OF
 WEST PALM BEACH' CRITERIA AND
 REQUIREMENTS.PLEASE SUBMIT CALCULATION
 FOR OUR REVIEW AND APPROVAL.
 2. PLEASE VERIFY THE PROPOSED INVERT
 ELEVATIONS OF THE DRAINAGE SYS. WITH
 RELATION TO THE GARAGE FINISH FLOOR
 ELEVATIONS.
 3. CIVIL PLANS SHOWS RPZS AND DDCA
 INSIDE THE BUILDING, MECHANICAL SHOWS
 THE ASSEMBLIES OUTSIDE THE BUILDING,
 PLEASE COORDINATE.
 4. CIVIL PLANS MUST BE REVIEWED AND
 APPROVED BY THE PUBLIC UTILITIES AND
 ENGINEERING FOR ALL THE CONNECTIONS TO
 THE CITY SERVICES AND FOR THE LOCATIONS
 OF THE METERS AND BACKFLOWS.PLEASE
 CONTACT MANNY GONZALEZ AT 494-1085.
 5. FOR THE CITY' STANDARDS AND DETAILS
 CONTACT MANNY GONZALEZ AT 494-1085.
 6. CIVIL PLAN DOES SHOW THE
 RECONSTRUCTION OF THE SIDEWALKS LIMITS
 AND STREET SCAPING AND/OR ITS TYPE ALONG
 THE ROSEMARY AVE. AND BANYAN STREET.
 PLEASE COORDINATE WITH THE LANDSCAPE
 PLANS.
 7. PLEASE VERIFY THE ADEQUACY OF THE
 EXISTING 14' ALLEY FOR THE TRAFFIC BEING
 GENERATED BY THE FUTURE RESIDENTS TO
 ACCESS THE PARKING GARAGE.
 8. ANY IMPROVEMENT IN 14' ALLEY MUST BE
 COORDINATED AND APPROVED BY THE CITY WPB
 PUBLIC UTILITIES AND ENGINEERING.
 9. IS THE ALLEY GOING TO BE RE-SURFACED?
 WHO WILL BE DOING THAT?
 10. PLEASE NOTE THAT ANY WORK WITHIN THE
 PUBLIC R.O.W WILL REQUIRE A SEPARATE
 PERMIT FROM PUBLIC UTILITIES AND
 ENGINEERING, PLEASE SUBMIT M.O.T AT THE
 TIME OF APPLICATION, CONTACT 494-1086,
 WINDEL PALMER.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2004-11-10 Cont ID  
Sent By mamini Date 2004-11-10 Time 14:50 Rev Time 1.00
Received By mamini Date 2004-11-10 Time 14:50 Sent To  
Notes
2004-11-10 00:00:00FAILED:
  
 1.PROPOSED SITE MUST BE DESIGNED FOR
 WATER QUALITY AND DRAINAGE PER CITY OF
 WEST PALM BEACH' CRITERIA AND
 REQUIREMENTS, PLEASE SUBMIT
 CALCULATIONS
 FOR OUR REVIEW AND APPROVAL.
 2.CIVIL PLANS MUST BE REVIEWED FOR ALL
 THE CONNECTIONS TO THE CITY SERVICES BY
 THE PUBLIC UTILITIES AND ENGINEERING,
 ATT; MANNY GONZALEZ 494-1085.
 3. CITY' STANDARDS AND DETAILS MAY BE
 OBTAINED FROM PUBLIC UTILITIES AND
 ENGINEERING, ATT;MANNY GONZALEZ
 494-1085.
 3.PLEASE SHOW SIZE, TYPE OF PIPE FOR
 ROOF DRAINS AND ALSO DETAILS FOR
 CONNECTION TO THE EXISTING STRUCTURES.
 4.STEERT SCAPING, BANYAN & ROSEMARY
 MUST BE APPROVED BY THE PLANNING
 DEPARTMENT, 822-1435.
 5.SITE PLAN PREPARED BY THE ARCHITECT
 SHOWS PAVERS FOR THE SIDEWALK, CIVIL
 SHOWS CONCRETE, PLEASE VERIFY.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2005-08-05 Cont ID  
Sent By mwennerg Date 2005-08-05 Time 09:52 Rev Time 0.00
Received By mwennerg Date 2005-08-05 Time 09:52 Sent To  
Notes
2005-08-05 00:00:00******DENIED******
  
 PLEASE NOTE THAT COMMENTS FROM THE LAST
 FIRE REVIEW DON'T APPEAR TO HAVE BEEN
 ADDRESSED. AS INDICATED IN LAST REVIEW,
 A RESPONSE LETTER ILLUSTRATING THE
 CORRESPONDING SHEET NUMBER WOULD HELP
 EXPEDITE THE PLAN REVIEW PROCESS. THANK
 YOU IN ADVANCE FOR YOUR CONSIDERATION
 REGARDING THIS MATTER.
  
 1) FIRE PROTECTION SHEETS ARE MISSING
 WITH THIS RESUBMITTAL. PLEASE KEEP ALL
 APPROPRIATE SHEETS ATTACHED FOR EACH
 REVIEW. PLEASE SEE COMMENT #1 FROM LAST
 REVIEW.
  
 2) ALL SHAFTS THAT ARE LARGE ENOUGH FOR
 PERSONS TO FALL INTO MUST BE MARKED
 SHAFTWAY IN 6" LETTERS.
  
 3) PLEASE INDICATED PRESCRIPTIVE
 STRENGTH REQUIREMENTS FOR HANDRAILS AND
 GUARDS.
  
 4) PLEASE SUBMIT OCCUPANT LOAD
 CALCULATIONS FOR THE POOL DECK AND
 PATIO.
  
 5) ALL DOOR SWINGS SERVING AREAS OR
 ROOMS WITH OCCUPANT LOADS GREATER THAN
 50 SHALL SWING IN THE DIRECTION OF
 TRAVEL.
  
 6) PLEASE INDICATE ON PLANS THAT ALL
 SMOKE DETECTORS SHALL BE NO CLOSER THAN
 3' FROM AC DIFFUSERS.
  
 7) PLEASE ILLUSTRATE VERIFICATION
 REGARDING STANDBY POWER REQUIREMENTS.
  
 8) ELEVATOR WARNING SIGNS ARE REQUIRED.
 PLEASE INDICATE WITH NOTE ON DRAWINGS.
  
 9) EXITS SHALL BE READILY VISIBLE FROM
 ANY DIRECTION WITHIN EXIT ACCESS.
  
 10) PLEASE SHOW ON PLANS THAT THE VOICE
 EVACUATION MESSAGE SHALL COMPLY WITH THE
 REQUIREMENTS OF NFPA 72, AND NFPA 101,
 SECTION 9.6.3.
  
 WHEN RESUBMITTING PLANS FOR REVIEW, IT
 IS RECOMMENDED THAT EACH COMMENT BE
 ADDRESSED BY LETTER INDICATING THE SHEET
 NUMBER WHERE APPLICABLE.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 804-4756
 PLAN REVIEW(561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2005-05-02 Cont ID  
Sent By mwennerg Date 2005-05-02 Time 13:16 Rev Time 0.00
Received By mwennerg Date 2005-05-02 Time 13:15 Sent To  
Notes
2005-05-02 00:00:001) COMMENTS # 2,9,10,12,15,30,37,41 HAVE
 APPARENTLY BEEN ADDRESSED ON THE FIRE
 PROTECTION SHEETS. ALL SHEETS HAVE BEEN
 VOIDED. PLEASE PROVIDE CURRENT FIRE
 PROTECTION DRAWINGS FOR REVIEW. INDICATE
 YOUR RESPONSES WITH SHEET NUMBERS AND
 RERVISION CLOUDS.
  
 2) PLEASE INDICATE THE SHEET NUMBER WITH
 YOUR RESPONSE REGARDING THE MARKING OF
 SHAFTS. COMMENT #8
  
 3) PLEASE RESPOND TO COMMENT REGARDING
 PRESCRIPTIVE HANDRAIL AND GUARDRAIL
 STRENGTHS WITH REVISION CLOUD AND SHEET
 NUMBER. COMMENT #13
  
 4) PLEASE INDICATE OCCUPANT LOAD
 CALCULATIONS FOR THE POOL DECK AND
 COMMON PATIO WITH REVISION CLOUD AND
 SHEET NUMBER. COMMENT #14
  
 5) ALL DOOR SWINGS SHALL BE IN THE
 DIRECTION OF TRAVEL WHEN SERVING A ROOM
 OR AREA WITH OCCUPANT LOAD OF GREATER
 THAN 50. COMMENT #26
  
 6) PLEASE INDICATE THE SHEET NUMBER
 REGARDING THE SLIP RESISTANCE OF
 WALKWAY. COMMENT #27
  
 7) PLEASE INDICATE THE SHEET NUMBER
 REGARDING MINIMUM DISTANCE BETWEEN SMOKE
 DETECTORS AND AC DIFFUSERS. COMMENT #32
  
 8) PLEASE INDICATE SHEET NUMBER
 REGARDING STANDBY POWER REQUIREMENTS.
 COMMENT #34
  
 9) PLEASE INDICATE SHEET NUMBER
 REGARDING ELEVATOR WARNING SIGNS.
 COMMENT #35
  
 10) PLEASE PROVIDE FURTHER EXPLANATION
 REGARDING MEANS OF EGRESS THROUGH
 PARKING SPACES. HOW CAN THIS BE
 MAINTAINED ACCESSABLE AND FREE OF
 OBSTRUCTIONS AT ALL TIMES? COMMENT #36
  
 11) EXITS SHALL BE READILLY VISIBLE FROM
 ANY DIRECTION OF EXIT ACCESS. COMMENT
 #38
  
 12) VOICE EVACUATION MESSAGE SHALL
 COMPLY WITH NFPA 72 AND NFPA 101,
 SECTION 9.6.3. COMMENT #40
  
  
 PLEASE ADDRESS COMMENTS WITH SHEET
 NUMBERS AND REVISION CLOUDS TO ASSIST IN
 EXPEDITING THIS PROCESS.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910 OR 805-6722
  
  
  
  
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-12-15 Cont ID  
Sent By mcarsill Date 2004-12-15 Time 07:19 Rev Time 0.00
Received By mcarsill Date 2004-12-15 Time 07:19 Sent To  
Notes
2004-12-15 00:00:001) PLEASE INDICATE LOCATION OF FIRE
 COMMAND CENTER ON PLANS.
  
 2) KNOX-BOXES WILL BE REQUIRED.
  
 3) BUILDING IS TO MEET HIGH-RISE
 REQUIREMENTS OF THE APPLICABLE
 BUILDING AND FIRE CODES.
  
 4) A TWO-HOUR FIRE SEPARATION IS
 REQUIRED BETWEEN THE PARKING AND OTHER
 AREAS OF THE BUILDING.
  
 5) S-3 DOOR NEAR LOADING ZONE 2. PLEASE
 EXPLAIN.
  
 6) S-2 DOOR NEAR ALLEY. PLEASE EXPLAIN.
  
 7) TACTILE SIGNAGE REQUIRED AT EXIT
 DOORS.
  
 8) ALL SHAFTS THAT ARE LARGE ENOUGH
 FOR PERSONS TO FALL INTO MUST
 BE MARKED SHAFTWAY IN 6" LETTERS.
  
 9) THE FIRE ALARM SYSTEM MUST MEET
 THE REQUIREMENTS FOR CENTRAL STATION
 SERVICE.
  
 10) TWO FIRE DEPARTMENT CONNECTIONS
 ARE REQUIRED FOR THE BUILDING SINCE
 IT IS A HIGH-RISE BUILDING.
  
 11) ALL NEW STAIRS AND RAMPS SHALL
 HAVE HANDRAILS ON BOTH SIDES.
  
 12) LOCKING KNOX-BOX CAPS ARE REQUIRED
 ON THE FIRE DEPARTMENT CONNECTIONS.
  
 13) PLEASE PROVIDE PRESCRIPTIVE
 STRENGTH REQUIREMENTS FOR HANDRAILS
 AND GUARDRAILS.
  
 14) PLEASE PROVIDE OCCUPANT LOADS
 FOR POOL DECK AND COMMON PATIO.
  
 15) PLEASE DISPLAY ALL EXISTING OR
 NEW FIRE HYDRANTS ON SITE.
  
 16) PARKING SPACES SURROUND STAIR # 1
 ON PAGE A-3. PLEASE EXPLAIN ACCESS.
  
 17) PARKING SPACES SURROUND STAIR # 3
 ON PAGE A-4. PLEASE EXPLAIN ACCESS.
  
 18) BUILDING LOCATED IN FIRE LIMITS.
 CERTAIN RESTRICTIONS APPLY. PLEASE
 SEE APPENDIX F, LOCAL AMENDMENTS.
  
 19) EXIT SIGN PLACEMENT SHALL NOT
 EXCEED 100 FEET.
  
 20) ENSURE THAT ALL DOOR SWINGS ARE
 INCORRECT.
  
 21) THE DOOR APPEARS TO BE MISSING
 FROM STAIR # 1ON PAGE A-7.
  
 22) PLEASE EXPLAIN EXITING FROM
 MEZZANINE LEVEL.
  
 23) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND CEILINGS.
  
 24) SIGNS REQUIRED IN STAIRWELLS
 INDICATING TOP, BOTTOM, FLOOR NUMBER,
 ROOF ACCESS, AND THE IDENTITY.
  
 25) WOOD TRELLIS NOTED ON ROOF
 TERRACE. AGAIN LOCATED IN FIRE LIMITS.
  
 26) ARE THE DOORS AT THE MAIN LOBBY
 ROOF TERRACE SWINGING IN THE PROPER
 DIRECTION.
  
 27) IS THE WALKWAY TO THE EXITS ON ROOF
 TERRACE SLIP RESISTANT.
  
 28) BUILDING ADDRESS REQUIRED. A MINIMUM
  
 OF AT LEAST 6" HIGH NUMBERS ARE
 REQUIRED.
  
 29) CANVAS AWNINGS REQUIRED TO BE
 FLAME RETARDANT.
  
 30) PLEASE DISPLAY FIRE SPRINKLER
 LOCATIONS IN TRASH CHUTE SECTION.
  
 31) SMOKE DETECTORS ARE REQUIRED ON
 EVERY LEVEL OF RESIDENTIAL UNITS.
  
 32) PLEASE INDICATE ON PLANS THAT
 ALL SMOKE DETECTORS SHALL BE PLACED
 NO CLOSER THAN THREE FEET FROM
 AIR CONDITIONER DIFFUSERS.
  
 33) PLEASE INDICATE STRETCHER
 ACCESSIBLE
 ELEVATORS IN THE BUILDING.
  
 34) PLEASE VERIFY STANDBY POWER
 REQUIREMENTS.
  
 35) ELEVATOR WARNING SIGNS REQUIRED.
  
 36) LIFE SAFETY ROUTES ON PAGE A-38
 ARE GOING THRU PARKING SPACES. PLEASE
 EXPLAIN RATIONALE.
  
 37) PLEASE PROVIDE WATER COLUMN
 REQUIREMENTS FOR THE STAIRWELL
 PRESSURIZATION SYSTEMS.
  
 38) THERE ARE NOT ENOUGH EXIT SIGNS
 SHOWN.
  
 39) THE CORRIDORS NEED MORE EXIT
 SIGNS.
  
 40) PLEASE INDICATE WHAT THE VOICE
 EVACUATION MESSAGE OF THE FIRE ALARM
 SYSTEM WILL SAY.
  
 41) ELECTRONIC SWITCHES REQUIRED ON
 FIRE LINE BACKFLOW DEVICE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-11-15 Cont ID  
Sent By adarroug Date 2005-11-15 Time 08:45 Rev Time 0.00
Received By adarroug Date 2005-11-15 Time 08:45 Sent To  
Notes
2005-11-15 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-11-14 Cont ID  
Sent By adarroug Date 2005-11-14 Time 14:11 Rev Time 0.00
Received By adarroug Date 2005-11-14 Time 14:11 Sent To  
Notes
2005-11-14 00:00:00TO "DPALMER" DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-29 Cont ID  
Sent By adarroug Date 2005-06-29 Time 15:18 Rev Time 0.00
Received By adarroug Date 2005-06-29 Time 15:18 Sent To  
Notes
2005-07-01 00:00:00TO "COMM" BD#56/PLANS ON RACK/2 ROLLS
2005-06-29 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-03-21 Cont ID  
Sent By adarroug Date 2005-03-21 Time 10:43 Rev Time 0.00
Received By adarroug Date 2005-03-21 Time 10:43 Sent To  
Notes
2005-03-21 00:00:00TO "COMM" BD#21/PLANS ON RACK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-03-21 Cont ID  
Sent By lmartine Date 2004-12-15 Time 08:10 Rev Time 0.00
Received By lmartine Date 2004-11-05 Time 10:41 Sent To  
Notes
2004-11-05 00:00:00TO COMM BD#40

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2005-08-03 Cont ID  
Sent By hmoser Date 2005-08-03 Time 14:21 Rev Time 0.00
Received By hmoser Date 2005-08-03 Time 14:21 Sent To  
Notes
2005-08-03 00:00:00PLAN DENIED
 1) EXHAUST DUCT AND DRYER DUCT TO BE
 SUMITED AS ALTERNATIVE METERIALS AND
 METHODS SECTION 301.4.2 FBC(M)
 2) PAGE M.4 REFER TO SECTION 501.3
 OUTDOOR DISCHARGE.CONDENSOR DISCHARGING
 ON PATIOS.
 3) PAGE M.5 LOBBY PROVIDE FIRE
 DAMPERS.PLEASE REFER TO SECTION 607.4
 FLOOR PENETRATION.
 4) PAGE M.5 DRYER VENT MUST BE 10FT.
 FROM SF#1
 5) REFER TO SECTION 504.6 CLOTHES DRYER
 DUCT
 6) PLEASE PROVIDE INFORMATION ON RTU#2&3
 HOW ARE THEY GETTING FRESH AIR.
 7) PLEASE REFER TO SECTION 307.2.3
 AUXILIARY DRAIN PANS.
 8) COULD NOT FIND ANCERS FOR LAST REVIEW
  
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By hmoser Date 2005-08-02 Time 18:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-04-29 Cont ID  
Sent By pkrauss Date 2005-04-28 Time 14:26 Rev Time 6.00
Received By pkrauss Date 2005-04-28 Time 14:14 Sent To  
Notes
2005-04-28 00:00:00DENIED:
 RESPONSE TO COMMENTS DATED 12-06-04:
 COMMENT #1 - INDICATE MAKEUP AIR FOR THE
 GARAGE EXHAUST.PLANS INDICATE
 CALCULATIONS BUT DO NOT ANNOTATE OR
 IDENTIFY HOW THE MAKE-UP AIR WILL BE
 ACHIEVED.
  
 COMMENT #5 - PLAN SHEET M-3, DUCT
 REDUCES IN RISER ONLY PLEASE CLARIFY. NO
 CLARFICATION GIVEN AND DUCT SIZE DID NOT
 CHANGE.
  
 COMMENT #9 - PLAN SHEET M-5, MAKE UP AIR
 TO STAIR #1 WAS EXTENDED OUT BUT IS
 STILL LOCATED AT THE GARAGE ENTRANCE.
 PROVIDE ELEVATION OF THE FRESH AIR
 INTAKE.
  
 COMMENT #12 - PROVIDE ELEVATION FOR THE
 TERMINATION OF THE MUFFLER EXHAUST.
 INDICATE DISTANCE FROM DOORS, WINDOWS
 AND FRESH AIR INTAKES.
  
 COMMENT #13 - PROVIDE DETAIL AND
 INFORMATION FOR THE FUEL PIPING AND
 STORAGE TANK.PLEASE INDICATE WHERE
 THIS ADDRESSED.INDICATE ON THE PLAN
 LOCATION AND PIPE SIZING.
  
 COMMENT #16 - PLANS SHEETS M-3 THROUGH
 M-6, STILL INDICATE THE DRYER & BATHROOM
 EXHAUST IN THE RETURN AIR PLENUM.PER
 2001 FBC/M 601.3 EXHAUST DUCTS UNDER
 POSTITIVE PRESSURE SALL NOT EXTEND INTO
 OR PASS THROUGH PLENUMS.
  
 NEW COMMENTS:
 1.PLAN SHEET M-5 8"X 6" SUPPLY AIR
 DUCT TO SECURITY OFFICE PENETRATES A 2
 HOUR RATED WALL.INDICATE COMPLIANCER
 WITH 2001 FBC/M 607.1.3 #3 OR A FIRE
 DAMPER WILL BE REQUIRED IN ACCORDANCE
 WITH 2001 FBC/M 607.1.2.
  
 2.PLAN SHEET M-11 THROUGH M-17 ARE
 VOIDED BUT THE REPLACEMENT SHEETS WERE
 NOT SUBMITTED.PLEASE CLARIFY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-12-06 Cont ID  
Sent By pkrauss Date 2004-12-06 Time 17:32 Rev Time 10.00
Received By pkrauss Date 2004-12-06 Time 17:32 Sent To  
Notes
2004-12-06 00:00:00DENIED:
 1.INDICATE HOW THE MAKE AIR FOR THE
 GARAGE AREA WILL BE ACHIEVED.
  
 2.PLAN SHEET M-1 THROUGH M-5,
 ELEVATOR LOBBY SUPPLY AIR FROM ABOVE.
 PLAN DOES NOT INDICATE ANY FIRE SMOKE
 DAMPERS OR SHAFT.PER 2001 FBC(M)607.6,
 SPECIFIC LOCATION OF FIRE DAMPERS & FIRE
 DOORS ARE TO BE IDENTIFIED ON PLANS.
 DETAIL OF FIRE DAMPERS & ACCESS DOORS
 ARE ALSO REQUIRED.
  
 3.PLEASE CLARIFY CONDENSING UNITS
 LOCATED IN THE GARAGE AREA UNDER A ROOF
 WITH NO CROSS VENTILATION.
  
 4.M-1 ELEVATOR 2 & 3 LOBBY AREA FLEX
 DUCT IS INDICATED AT THE RATED
 PENETRATION. PER 2001 FBC(M)607.1.3
 EXCEPTION #3 ITEMS 1 THROUGH 4 SHALL
 APPLY.
  
 5.DUCT FOR THIS RISER REDUCES
 DOWNWARD UNIT THE 1ST FLOOR AND THEN
 INCREASES AGAIN, PLEASE CLARIFY.
  
 6.M-2 EF5 & EF6 LOCATED AT THE FLOOR
 LEVEL IN COMPACT CAR SPACES.
 PROTECTION FROM DAMAGE REQUIRED PER
 2001
 FBC(M)303.4.
  
 7.M-3 EF-7 IS LOCATED THAT THE
 EXHAUST WILL BE RECIRCULATED BACK INTO
 THE GARAGE ENTRANCE IN VIOLATION OF
 501.3.
  
 8.M-3 EF-2,3,4,7, & 8 TERMINATING AT
 THE ALLEY.PER 2001 FBC(M)705.1.THIS
 APPLIES FOR OPENINGS INTO THE ALLEY
 WAY.
  
 9.M-5 SF-1 TO STAIR #1 MAKE-UP AIR
 SHALL NOT BE TAKEN FROM PARKING AREAS,
 STREETS OR ALLEYS PER 2001
 FBC(M)401.5.1.
  
 10. M-6 EMERGENCY GENERATOR ROOM, A
 FIRE
 DAMPER IS INDICATED ON THE GENERATOR
 INTAKE TO THE RADIATOR.PROVIDE THE
 MANUFACTURER APPROVAL FOR THIS
 APPLICATION.
  
 11. M-6 PLEASE CLARIFY 6" MUFFLER
 EXHAUST.NOTATION INDICATES 6" PIPE
 UNDER SLAB.WILL THIS BE POURED INTO
 THE SLAB BETWEEN THE FPL VAULT OR
 PENETRATING THROUGH THE VAULT
 UNDERGROUND?
  
 12. PROVIDE ELEVATION FOR THE
 TERMINATION OF THE MUFFLER EXHAUST.
 PROVIDE DISTANCE FROM THE TERMINATION
 TO
 WINDOWS AND AIR INTAKES.
  
 13. PROVIDE DETAIL FOR THE FILL PIPING
 AND LOCATION OF THE FILL FOR THE FUEL
 OIL TO THE GENERATOR.
  
 14. M-3 THROUGH M-6 INDICATE DRYER &
 TOILET EXHAUST TERMINATING INTO THE
 GARAGE.PER 2001 FBC(M)501.3, EXHAUST
 SHALL DISCHARGE OUTDOORS WHERE IT WILL
 NOT CREATE A NUISANCE OR BE
 RECIRCULATED
 BY THE VENTILATION SYSTEM.EXHAUST
 SHALL NOT BE DIRECTED ONTO WALKWAYS PER
 2001 FBC(M)401.5.2.
  
 15. M-9 & M-10 INDICATE SHEET 9 OF 21
 AND 10 OF 21.THERE ARE ONLY 17
 MECHANICAL SHEETS.
  
 16. RETURN AIR MISSING FROM UNIT
 L/WB-4.
 CERTIAN UNITS INDICATE RETURN AIR
 PLENUMS.PER 2001 FBC(M)602.2.1, NO
 COMBUSTIBLES ALLOWED ABOVE THE CEILING
 IN THE RETURN AIR PLENUM.
  
 17. M-11 INDICATE ACCESS AND CLEARANCES
 FOR THE DUCTWORK INSTALLED UNDER THE
 POOL.WILL THIS BE INSULATED?
  
 18. M-11 & M-12 CONDENSING UNITS
 LOCATED
 ON THE ROOF OR ARE THEY ENCLOSED?
 PLEASE NOTE, CONDENSING UNITS LOCATED
 ON
 THE ROOF SHALL COMPLY WITH 2001 FBC
 1511.7 FOR THE CLEARANCE BETWEEN THE
 ROOF SURFACE AND THE BOTTOM OF THE
 SUPPORT RAIL.
  
 19. M-15 CORRIDOR PRESSURIZATION DETAIL
 SHOWS 2" FIRE RATED CHASE.SHOULD THIS
 READ 2 HOUR FIRE RATED CHASE?
  
 20. M-16 RTU SCHEDULE INDICATES ALL
 UNITS 60 TONS, THIS IS COMBINED.THE
 PLAN INDICATES 2 EACH 10.5 TON & 2 EA
 13
 TON UNITS.DUCT SMOKE DETECTORS ARE
 REQUIRED IN ACCORDANCE WITH 2001
 FBC(M)606.
  
 21.M-16 SPECIFIC DRYERS INDICATED ON
 DRYER SCHEDULE - SOME MODELS WOULD
 STILL
 EXCEED THE 25 FT MAXIMUM REQUIREMENT.
 SPECIFIC DRYERS ARE TO BE INSTALLED FOR
 FINAL INSPECTION.
  
 22. M-17 PRIMARY AIR CHASE DETAIL SHOWS
 ACCESS DOOR.FIRE/SMOKE DAMPERS &
 ACCESS DOORS SHALL ALSO BE LOCATED ON
 THE PLAN PER 2001 FBC(M)607.6.
  
 23. PROVIDE OUTSIDE AIR CALCULATIONS
 FOR
 ALL AREAS, RESIDENCE, COMMON AREAS,
 EQUIPMENT RMS, MECH, ELEC, PUMP RMS,
 STORAGE RMS.SHOW COMPLIANCE WITH 2001
 FBC(M)402 OR TABLE 403.3.
  
 24. M-16 SMOKE CONTROL SEQUENCE OF
 OPERATION.SMOKE CONTROL SHALL COMPLY
 WITH ONE OF THE ITEMS DESCRIBED IN
 412.5
 OF THE 2001 FBC.INDICATE WHICH
 PROCESS
 WILL BE USED FOR REMOVAL OF PRODUCTS OF
 COMBUSTION.
  
 25. PROVIDE MANUAL J CALCULATIONS IN
 ACCORDANCE WITH 2001 FBC CHAPTER 13.
  
 26. PROVIDE DETIAL FOR THE CONDENSATE.
 INDICATE TERMINATION.
  
 PLEASE NOTE, ADDITIONAL COMMENTS NOT
 ADDRESSED IN THIS REVIEW MAY OCCUR ON
 RESUBMITTAL DUE TO THE REPONSE TO
 COMMENTS AND THE INCOMPLETION OF PLANS
 SUBMITTED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 3 Status F Date 2005-07-30 Cont ID  
Sent By kstevens Date 2005-07-30 Time 13:36 Rev Time 51.00
Received By kstevens Date 2005-07-22 Time 16:47 Sent To  
Notes
2005-07-30 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 FHA-98 DESIGN MANUAL
  
 A) COMMENTS FROM PREVIOUS REVIEW THAT
 HAVE NOT BEEN ADDRESSED, OR NOT
 ADDRESSED PROPERLY. THE COMMENT NUMBER
 WILL REMAIN THE SAME AS THE FIRST
 REVIEW:
 1) SHTS I-1, & I-2 FIRM LICENSE NUMBER
 REQUIRED ON THE TITLE BLOCK, SIGNATURE
 REQUIRED, AND PRINTED NAME REQUIRED. FAC
 61G1-16.004(2)(5)(6), 61G1-16.003 AND FS
 481.219. - SUBMIT PROOF OF A LEGAL
 SIGNATURE IN THE FORM OF A DRIVERS
 LICENSE, VOTERS REG. CARD ECT., AND
 SUBMIT A SIGNED/SEALED/DATED NOTORIZED
 LETTER WITH YOUR LEGAL SIGNATURE FOR OUR
 FILES. (TITLE BLOCK REQD ON LETTER). -
 THIS COMMENT HAS NOT BEEN ADDRESSED, NOR
 HAS A RESPONSE BEEN NOTED.
 3) SHTS A-11 & A-12 SHT INDEX STATES
 PARTIAL 3RD-7TH FLOOR PLAN 1, BUT NOTE 5
 STATES 3RD-5TH FLOOR PLAN. PLEASE
 CLARIFY. SECTION 104.2.1. - THIS HAS NOT
 BEEN ADDRESSED, NOR HAS A RESPONSE BEEN
 NOTED.
 4) SHTS A-9 & A-15 SUBMIT CALCULATIONS
 FOR PRIMARY AND SECONDARY ROOF DRAINS
 PER SECTIONS 1106, & 1107 AND ALL
 SUBSECTIONS. SHOW SF OF EACH AREA WITH
 1/2 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS AND ROOF AREA FROM ABOVE THAT
 DRAINS TO THE ROOF FROM ABOVE ADDED TO
 THE SF IN THE CALCULATIONS. SHOW THE
 LOCATION OF ALL PRIMARY AND SECONDARY
 ROOF DRAINS AND THE SCUPPERS. ALSO SEE
 SHTS A-17 & A-18. THIS APPLIES TO THE
 ROOF DECK AREAS AS WELL. THIS HAS NOT
 BEEN ADDRESSED, NOR HAS A RESPONSE BEEN
 NOTED.
 5) SHTS A-9 & A-15 SHOW THE LOCATION AND
 SIZE OF ALL SECONDARY ROOF DRAINS &
 SCUPPERS. SECTION 104.2.1. - THIS HAS
 NOT BEEN ADDRESSED, NOR HAS A RESPONSE
 BEEN NOTED.
 6) SHTS A-15 & A-16 SUBMIT CALCULATIONS
 FOR MINIMUM FACILITIES PER TABLES 1003.1
 AND 403.1. SHOW THE SF OF EACH COMMON
 AREA, AND THE TOTAL COMMON AREA IN THE
 CALCULATIONS. - THIS HAS NOT BEEN
 ADDRESSED, NOR HAS A RESPONSE BEEN
 NOTED.
 7) ARCHITECTURAL SHEETS, THE DATE
 PREPARED AND THE PRINTED NAME OF THE
 PERSON RESPONSIBLE FOR THE DOCUMENT ARE
 REQUIRED PER FAC 61G1-16.004(4)(6) AND
 FS 481.2055. - THE PRINTED NAME OF THE
 PERSON HAS NOT BEEN ADDED TO THE TITLE
 BLOCK. NO RESPONSE NOTED.
 8) SHTS A-30, A-31, & A-32 INDICATE
 SPECIFICATION "A" OR "B" FOR EACH UNIT
 OR BATHROOM AS REQUIRED ON PAGE 7.35 OF
 THE FHA DESIGN MANUAL. - SHT A-30 ONLY
 UNIT B-2 IS INDICATED. - SHT A-32 UNITS
 E-4, E-4L, & E-6 ARE NOT INDICATED. - IF
 SPECIFICATION "A" ALL BATHROOMS AND ALL
 FIXTURES SHALL COMPLY. SEE PAGE 7.34.
 9) SHTS A-30, A-31, & A-32 SHOW THE SIZE
 OF THE OPENINGS FOR ALL COVERED WATER
 CLOSETS. MINIMUM 33" REQUIRED. SEE PAGES
 6.5 AND 6.7 OF THE FHA DESIGN MANUAL. -
 THE 18" FROM THE WALL TO THE CENTERLINE
 OF THE W/C IS AN ABSOLUTE MEASURMENT.
 SEE FIGS PAGE 6.3 & 6.5. - NO RESPONSE
 NOTED AND NOT ALL OPENINGS ARE INDICATED
 AND NOT ALL OPENINGS MEET THE
 REQUIREMENTS OF FHA DESIGN MANUAL.
 10) SHT A-33 MENS AND WOMENS RESTROOMS,
 SHOW CLEAR FLOOR SPACE FOR EACH
 ACCESSIBLE FIXTURE. SECTIONS 11-4.16.2,
 11-4.19.3, & 11-4.22.3. THE TURNING AREA
 SHALL BE SHOWN IN THE TOILET ROOM, NOT
 IN THE ACCESSIBLE STALL. ALSO SHOW WATER
 CLOSET HEIGHT PER 11-4.16.3. GRAB BAR
 HEIGHT MAX. 36", SHOWN AS 48" ON DETAIL
 BEHIND W/C. SHOW FLUSH CONTROL 11-4.16.5
 SHOW URINAL HEIGHT 11-4.18.2. THE
 CENTERLINE OF THE W/C SHALL BE 18" TO
 THE WALL FROM THE CENTERLINE OF THE
 FIXTURE, NOT 20" AS SHOWN. (SEE FIG. 28)
 FOR THE LAVS SHOW KNEE CLEARANCE
 11-4.19.2, FOR THE SHOWER SHOW CONTROLS
 11-4.21.5, SHOWER UNIT 11-4.21.6, AND
 CURB HEIGHT 11-4.21.8. - BACK AND SIDE
 GRAB BARS SHALL BE AT THE SAME HEIGHT.
 SEE FIG. 29. W/C HEIGHT 17" TO 19". 20"
 DIMENSION SHOWN ON SOME W/C'S.
 11) NOT USED
 12) SHT A-33 DETAIL #1 IN BOTH THE MEN'S
 AND WOMEN'S RESTROOMS. THE DOUBLE LAVS
 TO BE 34" IN HEIGHT AND HAVE A CLEARANCE
 OF 29". SEE FIG 31. SECTION 11-4.19.2. -
 NO RESPONSE NOTED. NOT ADDRESSED.
 13) A DRINKING FOUNTAIN IS REQUIRED IN
 THE COMMON AREA. TABLE 403.1. SUBMIT A
 DETAIL COMPLYING WITH SECTIONS 11-4.15
 AND ALL SUBSECTIONS & 11-4.1.3(10)(A)
 FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING. - NO DETAIL FOUND, NOR WAS A
 RESPONSE NOTED.
 14) SHT A-36 SHOW HEIGHT AND WIDTH OF
 SCUPPER OPENINGS ON THE DETAIL. SECTIONS
 104.2.1 AND 1107.3. NO DETAIL FOUND, NOR
 WAS A RESPONSE NOTED.
 15) A PROFESSIONAL ENGINEER SHALL SIGN
 HIS NAME. INITIALS ARE NOT APPROVED PER
 FBPE RULING. SUBMIT AN EXAMPLE OF THE
 ENGINEERS LEGAL SIGNATURE BY WAY OF
 DRIVERS LICENSE, VOTERS REG. ECT., AND A
 SIGNED, SEALED, DATED, NOTORIZED LETTER
 WITH TITLE BLOCK INDICATING YOUR LEGAL
 SIGNATURE FOR OUR FILES.
 61G15-23.002(1)(2) AND FS 471.025. THIS
 IS FOR ALL ENGINEERED SHEETS. - LETTER
 WAS NOT SIGNED, SEALED, DATED, NOR DID
 THE LETTER HAVE A TITLE BLOCK ON IT.
 18) SUBMIT MANUF. SPECIFICATION SHEETS
 FOR THE STORM WATER SUMP PUMPS. PUMP
 INFORMATION SHALL SHOW THE LISTING.
 SECTION 303.4.(SUBMITTALS NOT FOUND). -
 STILL NO RESPONSE TO THIS COMMENT.
 19) SHTS P-3 & P-4 PIPE SIZING NOT
 CORRECT FOR EMERGENCY ROOF DRAIN PIPING,
 (SECONDARY ROOF DRAINS). SEE TABLES
 1106.2 & 1106.3. STAIRWAY #2 NOT ADDED
 TO THE SYSTEM. DOUBLE CHECK ALL PIPE
 SIZES AND SHOW ADDITION OF ALL SF AS
 THEY ACCUMULATE IN THE STORM BLDG.
 DRAIN. SECTION 104.2.1. - THERE ARE
 STILL SOME PIPE SIZES AND SF NOT SHOWN
 ON THESE SHEETS.
 27) SHT P-5 CHECK ALL PIPE SIZING ON THE
 STORM SYSTEM AND SHOW ALL PIPE SIZES.
 SECTION 104.2.1. & TABLES 1106.2 &
 1106.3. - THERE ARE STILL PIPE SIZES
 MISSING AND SF AS IT ACCUMULATES. NO
 RESPONSE NOTED.
 34) SHT P-11AUXILLARY HORIZONTAL DRAIN
 PIPE SIZE NOT CORRECT. TABLE 1106.3. -
 NO RESPONSE NOTED. - SEE RWL S/8.
 35) THE TRASH CHUTE BEQUIRES AN "N-36"
 VACUUM BREAKER FOR BACKFLOW PROTECTION.
 SECTION 608.13.6. NO RESPONSE. SHEET
 VOIDED BUT NO NEW SHEET SUBMITTED.
 36) SHT P-12 AUXILLARY HORIZONTAL DRAIN
 PIPE TO BE SIZED PER TABLE 1106.3. NO
 RESPONSE. SHEET VOIDED BUT NO NEW SHEET
 SUBMITTED.
 37) SHTS P-13, & P-14 AUXILLARY ROOF
 DRAIN NEAR POOL SHALL NOT BE A TRIPPING
 HAZARD. PLEASE SUBMIT A DETAIL FOR S/27,
 S/28, S/29, & S/30 SECONDARY DRAINS.
 SECTION 104.2.1. NO RESPONSE NOTED. SHT
 VOIDED, BUT NO NEW SHEET SUBMITTED.
 38) SHT P-22 NO WATER SUPPLY SHOWN TO
 THE TRASH ROOM FOR THE TRASH CHUTE.
 PLEASE SHOW ON PLANS. SECTION 104.2.1.
 NO RESPONSE NOTED. SHEET VOIDED, BUT NO
 NEW SHEET SUBMITTED. TRASH CHUTE NOTES
 ON SHT 42 INDICATES THAT A WASH DOWN
 HEAD IS LOCATED AT THE TOP OF THE CHUTE.
 39) SHTS P-24, P-25, P-26, P-27, & P-28
 DO NOT MEET CODE REQUIREMENTS. IN MANY
 CASES THESE ARE THE CODE ISSUES NOT
 ADDRESSED. - THESE COMMENTS NOW APPLY TO
 SHTS 23, 29, 30, & 31 AS NEW RISERS HAVE
 BEEN SUBMITTED, AND SHEET INFORMATION
 HAS CHANGED.
 A. OFFSET VENTS ARE REQUIRED WHEN
 HORIZONTAL OFFSET ARE USED. SECTION 915.
 RESPONSE NOT APPROVED. OFFSET VENTS
 SHALL BE SHOWN ON THE RISER DIAGRAMS.
 SEE SECTION 104.2.1. - STILL SOME NOT
 SHOWN AS REQUIRED
 B. NO HORIZONTAL DRY VENTS. SECTION
 905.3. - OK
 C. STACK DRAIN SHALL CONNECT DOWNSTREAM
 OF BATHROOM GROUP FIXTURES. SECTION
 909.1 - OK
 D. KITCHEN SINK SHALL NOT DRAIN THROUGH
 THE WET VENT. SECTION 909.1 - OK
 E. MAIN VENT REQUIRED AT TOP OF STACKS.
 SECTION 903.1. SOME STILL NOT PIPED
 CORRECTLY.
 F. CLEANOUTS REQUIRED AT THE BASE OF
 EACH STACK. SECTION 708.3.4. - OK
 G. NO HORIZONTAL BRANCH CONNECTIONS TO
 A HORIZONTAL STACK OFFSET. SECTIONS
 711.2 & 711.3. - OK
 H. VENTING REQUIRED 901.2.1.
 I. (NEW COMMENT) EVERY VENT STACK SHALL
 CONNECT TO THE BASE OF THE DRAINAGE
 STACK. THE VENT STACK SHALL CONNECT AT
 OR BELOW THE LOWEST HORIZONTAL BRANCH.
 SECTION 903.4 - SOME VENT STACKS ARE NOT
 CONNECTED TO THE STACK, BUT CONNECT TO
 THE BRANCH LINE.
 J. STACK INSTALLATION 910.2
 THE RISERS ARE NOT CLEAR AS TO THEIR
 INTENT. CHECK ALL RISERS FOR CODE
 REQUIREMENTS. - OK
 43) SHT P-31 AIR CHAMBERS ARE NOT
 APPROVED. DELETE FROM ALL RISERS. WATER
 HAMMER ARRESTORS REQUIRED BY SECTION
 604.9 SHALL BE LOCATED AT ALL QUICK
 CLOSING VALVES, (W/M, ICE MAKER, & D/W),
 AND SHALL BE LOCATED NEAR THE FIXTURE.
 PDI-WH 201 AND MANUF. INSTALL. INSTRUCT.
 - ONLY ONE SET OF AIR CHAMBERS STILL
 REMAIN TO BE DELETED. SHT P-35 UNIT
 L/W-D-2 FIXTURE P-2 2ND FLOOR.
 44) SHTS P-33 & P-34 AUXILLARY ROOF
 DRAINS ON SOME SYSTEMS ARE UNDERSIZED.
 PLEASE SIZE PIPE PER TABLE 1106.3. ROOF
 DRAINS CHANGED TO SHTS 39, 40, 41, & 42,
 AND STILL HAVE SOME AUXILLARY ROOF DRAIN
 PIPING SIZED INCORRECTLY. SOME DRAINS
 ARE STILL SIZED INCORRECTLY. ALSO SHOW
 SF AS IT ACCUMULATES.
 45) SHT P-35 STORM DRAIN RISER 111, SHOW
 ALL PIPE SIZES AND SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM. RECHECK ALL
 PIPE SIZES PER TABLES 1106.2 & 1106.3 AS
 SOME PIPE SIZES ARE INCORRECT. THERE ARE
 STILL SOME PIPE SIZES THAT ARE
 INCORRECT. RISER III CHANGED TO RISER II
 AND MOVED TO SHT 41.1. - SIZES ON SOME
 PIPES ARE INCORRECT STILL, AND SQUARE
 FOOTAGE AS IT ACCUMULATES IS STILL NOT
 SHOWN AT EACH BRANCH LINE OR RISER.
 49) SUBMIT A CONDENSATE DRAIN ISOMETRIC
 WITH ALL PIPE SIZES, LOCATION OF RISER
 CONNECTIONS, RISERS, TERMINATION POINT
 OF THE RISERS (VENTS), AND INDICATE
 WHERE THE CONDENSATE DRAINS TO THE
 OUTSIDE OF THE BUILDING. SECTION
 104.2.1. LOCATION OF TERMINATION POINT
 FOR THE CONDENSATE HAS NOT BEEN GIVEN.
 2ND REVIEW
 **************NEW COMMENTS**************
 1B) NEW FLOOR LAYOUTS, NEW REVIEW
 2B) SHTS A27 THRU A32 ALL TYPICAL UNITS
 SHOW CLEAR FLOOR SPACE FOR W/C'S PER
 PAGE 7.43 FHA DESIGN MANUAL. SEE MINIMUM
 CLEAR FLOOR SPACE SIZE REQUIREMENTS. -
 SHOWER CLEAR FLOOR SPACE SHALL BE
 PARALLEL AND FLUSH WITH THE CONTROL
 WALL. SEE PAGE 7.56.- THIS COMMENT HAS
 NOT BEEN ADDRESSED PROPERLY AS PER FHA
 DESIGN MANUAL. - NO RESPONSE NOTED.
 3B) SHTS A27 THRU A32 ALL TYPICAL UNITS
 WATER CLOSETS SHALL BE 18" OFF WALL TO
 CENERLINE OF FIXTURE. SEE PAGES 6.5,
 7.43, 7.44 & 7.45. THIS IS WHEN THE W/C
 IN NEXT TO A WALL. - THIS HAS NOT BEEN
 ADDRESSED, NOR HAS A RESPONSE BEEN
 NOTED.
 4B) SHTS A27 THRU A32 ALL TYPICAL UNITS
 SHALL SHOW THE DIMENSIONS FOR THE W/C
 OPENINGS. MINIMUM 33" REQUIRED. SEE
 PAGES 7.43 THRU 7.45. THIS HAS NOT BEEN
 ADDRESSED, NOR HAS A RESPONSE BEEN
 NOTED.
 5B) SHT A1 DRAWING INDEX DOES NOT
 REFLECT DRAWING SHEETS. SECTION 104.2.1.
 - THIS HAS NOT BEEN ADDRESSED, NOR HAS A
 RESPONSE BEEN NOTED.
 8B) SHT P-3 STORM AND AUXILLARY
 PIPING SIZE IS NOT CORRECT IN MANY
 AREAS. CHECK PIPE SIZE PER TABLES 1106.2
 AND 1106.3. SOME PIPE SIZE STILL NOT
 CORRECT.
 7B) SHT P-4 SOME PIPE SIZES ARE NOT
 SHOWN. TABLES 1106.2 & 1106.3 AND
 SECTION 104.2.1.
 11B) SHT P-6 SHOW PIPING FOR PD(3061SF).
 TABLE 1106.3 AND SECTION 104.2.1. - 4"
 SHOWN BUT 6" REQUIRED. - FLOOR PLAN DOES
 NOT REFLECT THE RISER DIAGRAM (100).
 SECTION 104.2.1. - THIS STILL DOES NOT
 REFLECT THE FLOOR PLAN.
 12B) SHT P-7 6" REQUIRED ON AUXILLARY
 DRAIN LINES AT RISERS S/28, & S/29. 5"
 REQUIRED ON AUXILLARY DRAIN LINE BETWEEN
 COL. - PIPE SIZES NOT SHOWN FOR ROOF
 DRAINS, PRIMARY AND SECONDARY FOR COMMON
 PATIO AND PRIVATE LANAI AREAS. SECTION
 104.2.1 AND TABLE 1106.3. - UNABLE TO
 FIND S/28 & 2/29. PLEASE SHOW AN INDEX
 OF ALL STORM RISER DIAGRAMS USED. - PIPE
 SIZES NOT SHOWN ON AUXILLARY ROOF DRAINS
 DOWNSTREAM OF S/44 THEN SHOWN AS 4"
 DOWN. MINIMUM 5" REQUIRED. NOT ALL PIPE
 SIZES ARE SHOWN.
 13B) SHT P-8 6" REQUIRED ON AUXILLARY
 DRAINS S/26 & S/29. 8" REQUIRED ON
 AUXILLARY DRAINS S/14, & S/18. SHOW ALL
 PIPE SIZES FOR ROOM PRIMARY & SECONDARY
 DRAINS AT COMMON PATIO AND PRIVATE LANAI
 AREAS. TABLES 1106.2 & 1106.3. - NOW
 UNABLE TO LOCATE RISER S/29 PLEASE
 CLARIFY. - NOT ALL PIPES SIZES SHOWN.
 14B) SHT P-10 UNIT C-3L MAX. 4 FU ON 2"
 WET VENT. TABLE 909.3 - UNITS C-4L,
 B-4L, & C-6L STILL SHOW NO PIPE SIZE FOR
 THE SECTION OF PIPE DOWNSTREAM OF THE
 LAST FIXTURE, (P-2 OR P-2A), 5FU.
 MINIMUM 3" REQUIRED.
 17B) SHT P-23 RISER 3,4,5,6 DOES NOT
 REFLECT THE FLOOR PLAN. SHT P-3 SHOWS
 RISER 6 CONNECTING TO RISER 345 ON THE
 FIRST FLOOR NOT AT THE MEZZ. LEVEL AS
 SHOWN ON THE RISER. SECTION 104.2.1. -
 SHT P-5 SHOWS ONLY RISER #8 WITH RISERS
 3,4,5,6 CONNECTING TO THIS RISER.
 CORRELATE RISERS AND FLOOR PLAN. -
 SHOULD BE RISER 3,4,5,6,8 WITH 3,4,5,6
 SPLITTING OFF AT MEZZ. LEVEL AND RISER 8
 OFFSETTING AT THE 2ND FLOOR TO REFLECT
 THE FLOOR PLAN.
 18B) SHT P-23 RISER #7 DOES NOT REFLECT
 FLOOR PLAN ON SHT P-5 AT LAV. - THIS HAS
 NOT BEEN ADDRESSED, NOR WAS THERE A
 COMMENT RESPONSE.
 19B) SHT P-23 RISER DOES NOT REFLECT
 FLOOR PLAN AT RISER 10 ON THE 2ND FLOOR.
 CORRELATE RISER AND FLOOR PLAN. SECTION
 104.2.1. - NOT ADDRESSED, NO COMMENT
 RESPONSE.
 23B) SHT P-35 DELETE AIR CHAMBERS
 SECTION 104.2.1. SEE RISER 11-11R AT
 FIXTURE P2. AIR CHAMBER NOT DELETED.
 25B) SHTS P-39, P-40, P-41, & P-41.1,
 CHECK ALL AUXILLARY DRAINS FOR CORRECT
 SIZE. TABLE 1106.3 @ 4.5"/HR. - SOME
 SIZES NOT SHOWN. 42, 43, 44, TO BE 5"
 DOWN.
 ****************************************
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION. -
 NO RESPONSE TO THIS REQUIRES LAST
 SUBMITTAL. - NO RESPONSE TO THIS REQUEST
 SECOND REVIEW ALSO. THIS ADDS ADDITIONAL
 TIME TO THE PLAN REVIEW AS IT CAUSES THE
 PLAN TO BE REVIEWED AS A NEW REVIEW EACH
 TIME.
 ****************************************
 ********COMMENTS FOR THIRD REVIEW*******
 ****************************************
 1C. SHT P-6 AUXILLARY DRAINS, MINIMUM 6"
 REQUIRED FOR PD 3061SF BY HDCP PARKING
 SPACE 64, 4" SHOWN. - 8" HORIZONTAL
 REQUIRED PD'S 5866 SF TOTAL COL. 11/F.
 2C. SHT P-7 AUXILLARY DRAINS, MINIMUM 5"
 REQUIRED ON HORIZONTAL FOR S/9, S/32,
 S/33, @ 842 SF, & S/42, S/43, S/44 @
 1429 SF.
 3C. SHT P-8 AUXILLARY DRAINS, MINIMUM 5"
 REQUIRED ON HORIZONTAL FOR S/54, S/55,
 S/56 @ 1142 SF AND DOWNSTREAM, AND FOR
 S/16, S/46, S/47 @ 842 SF.
 4C. SHT P-39 RISERS S/2, S/9-S/32-S/33,
 S/42-S/43-S/44 MINIMUM 5" REQUIRED FOR
 AUXILLARY DRAINS OVER 800 SF.
 5C. SHT P-40 S/28.2 SF DOES NOT REFLECT
 SF ON SHT P-11. CORRELATE RISER AND ROOF
 LAYOUT. - AUXILLARY S/18 MINIMUM 8"
 REQUIRED. - AUXILLARY S/26 MINIMUM 6"
 REQUIRED. - AUXILLARY S/54-S/55-S/56
 SHOW 5" ON HORIZONTAL DOWNSTREAM OF
 S/55.
 6C. SHT P12 2/14 & S/18 8" REQUIRED ON
 AUXILLARY DRAIN. - S/26 6" REQUIRED ON
 AUXILLARY DRAIN. TABLE 1106.3
 7C. SUBMIT A DETAIL FOR ROOF SCUPPERS.
 SHOW HEIGHT AND WIDTH AND INDICATE
 MEASUREMENT FROM ROOF TO FLOW LINE OF
 SCUPPER AS REQUIRED BY SECTION 15-3.4.2.
 8C. SHT P-23 SANT. RISER DIAGRAM 1 & 2
 SHOWS A 4" VENT LINE THAT WAS OFFSET ON
 THE 2ND FLOOR CONTINUING ON THE 3RD THRU
 7TH FLOOR AND OFFSETTING AGAIN. PLEASE
 CLARIFY. - SANT. RISER 2 STACK VENT TO
 EXTEND AND CONNECT TO VENT LINE. SECTION
 903.1. - SANT. RISERS 6, 7, & 8 VENT
 STACK SHALL CONNECT TO THE DRAINAGE
 STACK NOT THE FIXTURE BRANCH. SECTION
 903.4. - SANT. RISER 7 UPPER PORTION OF
 OFFSET VENT REQUIRED.
 9C. SHT P-24 SANT RISERS 15, 18, 17, 19,
 VENT TO CONNECT TO DRAINAGE STACK NOT
 FIXTURE BRANCH. 903.4
 10C. SHT P-24 SANT. RISERS 17 & 19,
 (TOP), OFFSET VENTS REQUIRED. SECTION
 SECTION 915.
 11C. SHT P-24 SANT. RISERS 21 & 25 STACK
 VENT TO EXTEND AND TIE INTO VENT STACK.
 SECTION 903.1.
 12C. SANT. RISER 23 VENT STACK NOT
 REQUIRED. SANT. RISER 25 CHANGE OFFSET
 VENT TO CONNECT TO DRAINAGE STACK PER
 SECTION 903.4.
 10C. SHT P-25 SANT. RISER 28 VENT STACK
 NOT REQUIRED. - SANT. RISER 27 STACK
 VENT TO EXTEND AND TIE INTO VENT STACK.
 SECTION 903.1.
 11C. SHT P-25 SANT. RISERS 30, 31, 34.
 37 VENT STACK SHALL CONNECT TO THE
 DRAINAGE STACK, NOT THE BRANCH LINE.
 SECTION 903.4. - SANT. RISER 37 SHOWS
 THE PIPING DIRECTION AWAY FROM THE
 STACK. PLEASE CLARIFY. SECTION 104.2.1.
 12C. SANT. RISER 35 MAXIMUM 4 FU ON 2"
 WET VENT. NO PIPE SIZE SHOWN. ALL
 FLOORS. TABLE 909.3
 13C. SHT P-26 SANT. RISER 38/39 IDENTIFY
 FIXTURE ON MEZZ. LEVEL, AND A VENT IS
 REQUIRED FOR SAME FIXTURE. 901.2.1.
 14C. SHT P-26 SANT. RISERS 38/39, 40,
 41, 43, 44, 46, 47, 48/49 CONNECT VENT
 STACK TO DRAINAGE STACK AT BASE OF STACK
 PER SECTION 903.4. - SANT. RISER VENT TO
 EXTEND AND TIE INTO VENT STACK. SECTION
 903.1. - SANT. RISER 46 OFFSET VENT NOT
 REQUIRED. - SANT. 48/49 EXTEND STACK
 VENT AND CONNECT TO VENT STACK. SECTION
 903.1.
 15C. SHT P-27 SANT. RISER 81/105 OFFSET
 VENT NOT REQUIRED. - MAX 4 FU ON 2" WET
 VENT. TABLE 909.3 - ALL FLOORS. -
 CONNECT VENT STACK TO DRAINAGE STACK PER
 SECTION 903.4.
 16C. SHT P-27 SANT. RISER 79 CONNECT
 VENT STACK TO DRAINAGE STACK PER SECTION
 903.4 - STACK VENT TO CONNECT TO VENT
 STACK AT TOP OF RISER. SECTION 903.1.
 17C. SANT. RISERS 82.106 & 85 MAXIMUM 4
 FU ON 2" WET VENT. TABLE 903.3. ALL
 FLOORS.
 18C. SANT RISER 84 CONNECT VENT STACK TO
 DRAINAGE STACK NOT BRANCH LINE PER
 SECTION 903.4.
 19C. SHT P-28 ALL SANT. RISERS CONNECT
 THE VENT STACKS TO THE DRAINAGE STACKS
 PER SECTION 903.4.
 20C. SHT P-28 SANT. RISER 51/52 SHOW 3
 STACKS, BUT ONLY 2 STACK NUMBERS. PLEASE
 CLARIFY. SECTION 104.2.1. - OFFSET VENT
 SHALL CONNECT TO SOIL STACK (52) NOT
 STACK 51.
 21C. SHT P-28 SANT. RISER 53 OFFSET VENT
 REQUIRED FOR OFFSET BETWEEN MEZZ. & 2ND
 FLOOR. SECTION 915. - MAXIMUM 4 FU ON 2"
 WET VENT. TABLE 903.3.
 22C. SHT P-28 SANT. RISER 54-55-55.1
 OFFSET VENT REQUIRED BETWEEN MEZZ. LEVEL
 AND 2ND FLOOR.
 23C. SHT P-28 OFFSET VENT & VENT LINE
 ARE NOT REQUIRED.
 24C. SHT P-28 INDICATE STACK NUMBER FOR
 STACK BETWEEN RISERS 57 & 58. SECTION
 104.2.1.
 25C. SANT. RISER 57 EXTEND STACK VENT
 AND TIE INTO VENT STACK. SECTION 903.1.
 26C. SHT P-28 SANT. RISER 59 MAXIMUM 4
 FU ON 2" WET VENT. TABLE 903.3. ALL
 FLOORS.
 27C. SHT P-29 SANT. RISERS 62, 64, 66,
 71, 73, 74, 99, & 102 CONNECT THE VENT
 STACK TO THE DRAINAGE STACK PER SECTION
 903.4.
 28C. SHT P-29 SANT. RISER 73 EXTEND
 STACK VENT AND CONNECT TO VENT STACK.
 SECTION 903.4.
 29C. SHT P-29 SANT. 100 OFFSET VENT AND
 VENT LINE NOT REQUIRED. SECTION 104.2.1.
 30C. SHT P-31 SANT. RISERS 92, 95, 97/98
 CONNECT VENT STACK TO DRAINAGE STACK PER
 SECTION 903.4.
 31C. SHT P-31 SANT. RISER 93 INDICATE
 VENT SIZE. TABLE 916.1.
 32C. SHT P-31 SANT. RISER 97 EXTEND
 STACK VENT AND CONNECT TO VENT STACK.
 SECTION 903.1.
 33C. SHT P-38 A/C CLOSET IS SHOWN AS A
 PLENUM. PVC OR CPVC IS NOT ALLOWED IN
 THE PLENUM. INDICATE MATERIAL TYPE FOR
 CONDENSATE LINES IN THE PLENUM. SECTIONS
 303.2. AND 602.2.1 OF THE MECHANICAL
 CODE.
 34C. SHT P-42 WATER HEATER DIAGRAM SHOWS
 P/T TO HEATER PAN, BUT STATES 3/4" DRAIN
 TO OUTSIDE. PLEASE CLARIFY. SECTION
 104.2.1.
 35C. SHT P-1 STORM SHOWS 12" HORIZONTAL,
 THEN 10" UP TO FIRST FLOOR AT COL. LINE
 5/G. PIPING SHALL NOT BE REDUCED IN THE
 DIRECTION OF FLOW PER SECTION 704.2.
 36C. SUBMIT AN ISOMETRIC STORM DRAIN
 RISER DIAGRAM FOR THE PD DRAIN SYSTEMS
 SHOWING ALL PIPE SIZES AND SF AS IT
 ACCUMULATES IN THE SYSTEM TO REFLECT THE
 FLAT PD DRAINAGE SYSTEM. SECTION
 104.3.1.1.
 37C. SHT P-11 RISER S/8, 8" MINIMUM
 REQUIRED ON AUXILLARY. TABLE 1106.3.
 38C. SHT P-12 RISERS S/14, & S/18, 8"
 MINIMUM REQUIRED ON AUXILLARY. TABLE
 1106.3.
 39C. SHT P-12 RISER S/26, 6" MINIMUM
 REQUIRED ON AUXILLARY. TABLE 1106.3.
 40C. SHT P-12 RISERS S17, & S/17.1 DOWN
 AND DOWN AUXILLARY MISLABELED. SECTION
 104.2.1.
 41C. SHTS P13 & P14 SHOWS "THRU SCUPPER"
 PLEASE CLARIFY. POOL DECK REQUIRES
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106 & 1107. SHOW THE LOCATION
 OF ALL REQUIRED DRAINS.
 42C. SHT P-32 RISER 3/4/5/6/8 DOES NOT
 REFLECT THE FLOOR PLAN. ALL VENT STACKS
 SHALL CONNECT TO THE DRAINAGE STACK PER
 SECTION 903.4.
 43C. SHTS P-33 & P-34 ALL VENT STACKS
 SHALL CONNECT TO THE DRAINAGE STACK.
 SECTION 903.4.
 44C. SHT P-35 UNIT L/W-D-2 DELETE
 AIR CHAMBERS FROM FIXTURE P-2, 2ND
 FLOOR. SECTION 604.9.
 45C. SHTS P-39 & P-40 SEE COMMENT NUMBER
 5 FROM PREVIOUS REVIEW CONCERNING
 DRAWING INDEX. SECTION 104.2.1.
 46C. SHTS P-41 & P41.1 SHOW ALL PIPE
 SIZES, AND RECHECK ADDITION ON SF. -
 DOWNSTREAM OF 8" @ 1/8"/FT 8615 SF SHOWS
 10" @ 1/8"/FT 10713 SF AND NO BRANCH
 LINES INBETWEEN. PLEASE CLARIFY. -
 DOWNSTREAM OF S/49-S/50 AUXILLARY SHOWS
 A LINE CONNECTING INTO THE STORM LINE.
 DELETE FROM SHEETS.
 47C. SHT P-42 SUMP PUMP DETAIL, PUMP AND
 WASTE LINE NOT APPROVED. OIL SHALL BE
 RECLAIMED AND RECYCLED. DELETE FROM
 DETAIL.
 48C. SHT P-42 CONDENSATE DRAIN TRAP
 DETAIL. MATERIAL TO BE USED FOR THE TRAP
 AND CONDENSATE LINE IS STATED AS PVC IN
 THE GENERAL PLUMBING NOTES #4(C). THIS
 IS NOT APPROVED IN THE PLENUM. INDICATE
 MATERIAL TO BE USED IN THE PLENUM.
 SECTION 606.2.1 (MECH).
 49C. SHT P-42 TRASH CHUTE SPECIFICATION
 #6 INDICATES A FLUSHING HEAD. AN N36
 VACUUM BREAKER IS REQUIRED AT THE
 HIGHEST POINT OF THE WATER SUPPLY. SHOW
 WATER LINE TO TRASH CHUTE ON THE WATER
 RISER DIAGRAM. SHOW PIPE SIZE AND VACUUM
 BREAKER. SECTIONS 104.3.1. & 608.13.8.
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION. -
 THIS HAS BEEN REQUESTED EACH REVIEW AND
 NO RESPONSE TO THIS REQUEST HAS BEEN
 NOTED. NO COMMENT RESPONSE AND NOT
 RETURNING THE PREVIOUS PLANS ADDS MANY
 HOURS TO THE REVIEW PROCESS AND SLOWS
 THE PERMIT PROCESS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-05-19 Cont ID  
Sent By kstevens Date 2005-05-19 Time 17:31 Rev Time 43.00
Received By kstevens Date 2005-05-14 Time 17:00 Sent To  
Notes
2005-05-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 FHA-98 DESIGN MANUAL
  
 A) COMMENTS FROM PREVIOUS REVIEW THAT
 HAVE NOT BEEN ADDRESSED, OR NOT
 ADDRESSED PROPERLY. THE COMMENT NUMBER
 WILL REMAIN THE SAME AS THE FIRST
 REVIEW:
 1) SHTS I-1, & I-2 FIRM LICENSE NUMBER
 REQUIRED ON THE TITLE BLOCK, SIGNATURE
 REQUIRED, AND PRINTED NAME REQUIRED. FAC
 61G1-16.004(2)(5)(6), 61G1-16.003 AND FS
 481.219. - SUBMIT PROOF OF A LEGAL
 SIGNATURE IN THE FORM OF A DRIVERS
 LICENSE, VOTERS REG. CARD ECT., AND
 SUBMIT A SIGNED/SEALED/DATED NOTORIZED
 LETTER WITH YOUR LEGAL SIGNATURE FOR OUR
 FILES. (TITLE BLOCK REQD ON LETTER).
 2) SHT I-1, AN RPZ BACKFLOW, INSTALLED
 BY A LICENSED PLUMBING CONTRACTOR, IS
 REQUIRED FOR THE IRRIGATION SYSTEM. SHOW
 THE LOCATION ON THE IRRIGATION PLANS.
 SECTIONS 608.13.2 & 104.2.1.
 3) SHTS A-11 & A-12 SHT INDEX STATES
 PARTIAL 3RD-7TH FLOOR PLAN 1, BUT NOTE 5
 STATES 3RD-5TH FLOOR PLAN. PLEASE
 CLARIFY. SECTION 104.2.1.
 4) SHTS A-9 & A-15 SUBMIT CALCULATIONS
 FOR PRIMARY AND SECONDARY ROOF DRAINS
 PER SECTIONS 1106, & 1107 AND ALL
 SUBSECTIONS. SHOW SF OF EACH AREA WITH
 1/2 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS AND ROOF AREA FROM ABOVE THAT
 DRAINS TO THE ROOF FROM ABOVE ADDED TO
 THE SF IN THE CALCULATIONS. SHOW THE
 LOCATION OF ALL PRIMARY AND SECONDARY
 ROOF DRAINS AND THE SCUPPERS. ALSO SEE
 SHTS A-17 & A-18. THIS APPLIES TO THE
 ROOF DECK AREAS AS WELL.
 5) SHTS A-9 & A-15 SHOW THE LOCATION AND
 SIZE OF ALL SECONDARY ROOF DRAINS &
 SCUPPERS. SECTION 104.2.1.
 6) SHTS A-15 & A-16 SUBMIT CALCULATIONS
 FOR MINIMUM FACILITIES PER TABLES 1003.1
 AND 403.1. SHOW THE SF OF EACH COMMON
 AREA, AND THE TOTAL COMMON AREA IN THE
 CALCULATIONS.
 7) ARCHITECTURAL SHEETS, THE DATE
 PREPARED AND THE PRINTED NAME OF THE
 PERSON RESPONSIBLE FOR THE DOCUMENT ARE
 REQUIRED PER FAC 61G1-16.004(4)(6) AND
 FS 481.2055.
 8) SHTS A-30, A-31, & A-32 INDICATE
 SPECIFICATION "A" OR "B" FOR EACH UNIT
 OR BATHROOM AS REQUIRED ON PAGE 7.35 OF
 THE FHA DESIGN MANUAL.
 9) SHTS A-30, A-31, & A-32 SHOW THE SIZE
 OF THE OPENINGS FOR ALL COVERED WATER
 CLOSETS. MINIMUM 33" REQUIRED. SEE PAGES
 6.5 AND 6.7 OF THE FHA DESIGN MANUAL. -
 THE 18" FROM THE WALL TO THE CENTERLINE
 OF THE W/C IS AN ABSOLUTE MEASURMENT.
 SEE FIGS PAGE 6.3 & 6.5.
 10) SHT A-33 MENS AND WOMENS RESTROOMS,
 SHOW CLEAR FLOOR SPACE FOR EACH
 ACCESSIBLE FIXTURE. SECTIONS 11-4.16.2,
 11-4.19.3, & 11-4.22.3. THE TURNING AREA
 SHALL BE SHOWN IN THE TOILET ROOM, NOT
 IN THE ACCESSIBLE STALL. ALSO SHOW WATER
 CLOSET HEIGHT PER 11-4.16.3. GRAB BAR
 HEIGHT MAX. 36", SHOWN AS 48" ON DETAIL
 BEHIND W/C. SHOW FLUSH CONTROL 11-4.16.5
 SHOW URINAL HEIGHT 11-4.18.2. THE
 CENTERLINE OF THE W/C SHALL BE 18" TO
 THE WALL FROM THE CENTERLINE OF THE
 FIXTURE, NOT 20" AS SHOWN. (SEE FIG. 28)
 FOR THE LAVS SHOW KNEE CLEARANCE
 11-4.19.2, FOR THE SHOWER SHOW CONTROLS
 11-4.21.5, SHOWER UNIT 11-4.21.6, AND
 CURB HEIGHT 11-4.21.8.
 11) NOT USED
 12) SHT A-33 DETAIL #1 IN BOTH THE MEN'S
 AND WOMEN'S RESTROOMS. THE DOUBLE LAVS
 TO BE 34" IN HEIGHT AND HAVE A CLEARANCE
 OF 29". SEE FIG 31. SECTION 11-4.19.2.
 13) A DRINKING FOUNTAIN IS REQUIRED IN
 THE COMMON AREA. TABLE 403.1. SUBMIT A
 DETAIL COMPLYING WITH SECTIONS 11-4.15
 AND ALL SUBSECTIONS & 11-4.1.3(10)(A)
 FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
 14) SHT A-36 SHOW HEIGHT AND WIDTH OF
 SCUPPER OPENINGS ON THE DETAIL. SECTION
 104.2.1.
 15) A PROFESSIONAL ENGINEER SHALL SIGN
 HIS NAME. INITIALS ARE NOT APPROVED PER
 FBPE RULING. SUBMIT AN EXAMPLE OF THE
 ENGINEERS LEGAL SIGNATURE BY WAY OF
 DRIVERS LICENSE, VOTERS REG. ECT., AND A
 SIGNED, SEALED, DATED, NOTORIZED LETTER
 WITH TITLE BLOCK INDICATING YOUR LEGAL
 SIGNATURE FOR OUR FILES.
 61G15-23.002(1)(2) AND FS 471.025. THIS
 IS FOR ALL ENGINEERED SHEETS.
 16) ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, LICENSE NUMBER & CERTIFICATE
 OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS ON EACH SHEET. FAC
 61G15-23.002(2). (WHITE OUT USED ON THE
 PLANS IS NOT APPROVED PER SECTION
 104.2.1.3.
 17) SHTS P-1 & P-2 PD'S SIZING AND
 PIPING SIZING ARE NOT CORRECT FOR ALL
 PD'S. RECHECK SIZING PER TABLES 1106.2 &
 1106.3. SHOW ALL SF AND PIPE SIZES.
 (THIS HAS NOT BEEN ADDRESSED, AND NEW
 SHEETS P-1 & P-2 WERE NOT SUBMITTED).
 18) SUBMIT MANUF. SPECIFICATION SHEETS
 FOR ELEVATOR SUMP PUMPS AND THE STORM
 WATER SUMP PUMPS. PUMP INFORMATION SHALL
 SHOW THE LISTING. SECTION 303.4.
 (SUBMITTALS NOT FOUND).
 19) SHTS P-3 & P-4 PIPE SIZING NOT
 CORRECT FOR EMERGENCY ROOF DRAIN PIPING,
 (SECONDARY ROOF DRAINS). SEE TABLES
 1106.2 & 1106.3. NO SF SHOWN FOR PD'S AT
 COL. LINE 5/G-F1 AND COL. LINE 6/F-E2.
 PD BETWEEN COLS. 8.1 & 8.3 NORTH OF
 STAIRWAY #2 NOT ADDED TO THE SYSTEM.
 DOUBLE CHECK ALL PIPE SIZES AND SHOW
 ADDITION OF ALL SF AS THEY ACCUMULATE IN
 THE STORM BLDG. DRAIN. SECTION 104.2.1.
 *** NEW COMMENT ** (ON PD LINE 8"PD
 (88185SF) NOTHING IS SHOWN ADDED TO
 10713SF) CLARIFY. - ALL PD LINES REQUIRE
 A CLEANOUT AS LINE EXITS BLDG.
 27) SHT P-5 CHECK ALL PIPE SIZING ON THE
 STORM SYSTEM AND SHOW ALL PIPE SIZES.
 SECTION 104.2.1. & TABLES 1106.2 &
 1106.3.
 34) SHT P-11AUXILLARY HORIZONTAL DRAIN
 PIPE SIZE NOT CORRECT. TABLE 1106.3. -
 NO RESPONSE NOTED. SHEET VOIDED BUT NO
 NEW SHEET SUBMITTED.
 35) THE TRASH CHUTE BEQUIRES AN "N-36"
 VACUUM BREAKER FOR BACKFLOW PROTECTION.
 SECTION 608.13.6. NO RESPONSE. SHEET
 VOIDED BUT NO NEW SHEET SUBMITTED.
 36) SHT P-12 AUXILLARY HORIZONTAL DRAIN
 PIPE TO BE SIZED PER TABLE 1106.3. NO
 RESPONSE. SHEET VOIDED BUT NO NEW SHEET
 SUBMITTED.
 37) SHTS P-13, & P-14 AUXILLARY ROOF
 DRAIN NEAR POOL SHALL NOT BE A TRIPPING
 HAZARD. PLEASE SUBMIT A DETAIL FOR S/27,
 S/28, S/29, & S/30 SECONDARY DRAINS.
 SECTION 104.2.1. NO RESPONSE NOTED. SHT
 VOIDED, BUT NO NEW SHEET SUBMITTED.
 38) SHT P-22 NO WATER SUPPLY SHOWN TO
 THE TRASH ROOM FOR THE TRASH CHUTE.
 PLEASE SHOW ON PLANS. SECTION 104.2.1.
 NO RESPONSE NOTED. SHEET VOIDED, BUT NO
 NEW SHEET SUBMITTED.
 39) SHTS P-24, P-25, P-26, P-27, & P-28
 DO NOT MEET CODE REQUIREMENTS. IN MANY
 CASES THESE ARE THE CODE ISSUES NOT
 ADDRESSED. - THESE COMMENTS NOW APPLY TO
 SHTS 23, 29, 30, & 31 AS NEW RISERS HAVE
 BEEN SUBMITTED, AND SHEET INFORMATION
 HAS CHANGED.
 A. OFFSET VENTS ARE REQUIRED WHEN
 HORIZONTAL OFFSET ARE USED. SECTION 915.
 RESPONSE NOT APPROVED. OFFSET VENTS
 SHALL BE SHOWN ON THE RISER DIAGRAMS.
 SEE SECTION 104.2.1.
 B. NO HORIZONTAL DRY VENTS. SECTION
 905.3.
 C. STACK DRAIN SHALL CONNECT DOWNSTREAM
 OF BATHROOM GROUP FIXTURES. SECTION
 909.1
 D. KITCHEN SINK SHALL NOT DRAIN THROUGH
 THE WET VENT. SECTION 909.1
 E. MAIN VENT REQUIRED AT TOP OF STACKS.
 SECTION 903.1.
 F. CLEANOUTS REQUIRED AT THE BASE OF
 EACH STACK. SECTION 708.3.4.
 G. NO HORIZONTAL BRANCH CONNECTIONS TO
 A HORIZONTAL STACK OFFSET. SECTIONS
 711.2 & 711.3.
 H. VENTING REQUIRED 901.2.1.
 I. (NEW COMMENT) EVERY VENT STACK SHALL
 CONNECT TO THE BASE OF THE DRAINAGE
 STACK. THE VENT STACK SHALL CONNECT AT
 OR BELOW THE LOWEST HORIZONTAL BRANCH.
 SECTION 903.4
 J. STACK INSTALLATION 910.2
 THE RISERS ARE NOT CLEAR AS TO THEIR
 INTENT. CHECK ALL RISERS FOR CODE
 REQUIREMENTS.
 40) SHTS P-24, P-25, P-26, P-27, &P-28
 SANITARY RISER DIAGRAMS DO NOT REFLECT
 THE FLOOR PLAN. THE FIXTURES FOR THE
 MEZZANINE LEVEL ARE SHOWN ABOVE THE
 MEZZANINE LEVEL, WHEN THE PIPING WILL BE
 BELOW THE MEZZANINE LEVEL. FIXTURES FOR
 THE SECOND FLOOR ARE SHOWN ABOVE THE
 SECOND FLOOR WHEN THE PIPING WILL BE
 BELOW THE SECOND FLOOR. THE FIXTURES FOR
 THE THIRD THRU THE EIGHT FLOORS ARE
 SHOWN BELOW THE TERRACE FLOOR. THE
 PIPING SHOULD BE BELOW THE EIGHT FLOOR.
 SECTION 104.2.1. - NO RESPONSE NOTED,
 AND THIS COMMENT IS NOW FOR SHEETS P-23,
 P-29, P-30, & P-31 AS NEW RISERS HAVE
 BEEN SUBMITTED AND SHEET INFORMATION HAS
 CHANGED.
 42) SHTS P-28 & P-29 SANT. BLDG. DRAIN
 ISOMETRIC, SHOW ALL PIPE SIZES AND SHOW
 THE DFU'S AS THEY ACCUMULATE IN THE
 SYSTEM. SECTION 104.2.1. & TABLE
 710.1(1). - NO RESPONSE NOTED. PART OF
 THE BLDG DRAIN ISOMETRIC HAS BEEN
 DELETED AND THE ISOMETRIC IS INCOMPLETE.
 PLEASE SUBMIT A COMPLETE ISOMETRIC.
 43) SHT P-31 AIR CHAMBERS ARE NOT
 APPROVED. DELETE FROM ALL RISERS. WATER
 HAMMER ARRESTORS REQUIRED BY SECTION
 604.9 SHALL BE LOCATED AT ALL QUICK
 CLOSING VALVES, (W/M, ICE MAKER, & D/W),
 AND SHALL BE LOCATED NEAR THE FIXTURE.
 PDI-WH 201 AND MANUF. INSTALL. INSTRUCT.
 NO RESPONSE NOTED. WATER RISER DIAGRAMS
 HAVE CHANGED TO SHEETS P-35 & P-38.
 44) SHTS P-33 & P-34 AUXILLARY ROOF
 DRAINS ON SOME SYSTEMS ARE UNDERSIZED.
 PLEASE SIZE PIPE PER TABLE 1106.3. ROOF
 DRAINS CHANGED TO SHTS 39, 40, 41, & 42,
 AND STILL HAVE SOME AUXILLARY ROOF DRAIN
 PIPING SIZED INCORRECTLY.
 45) SHT P-35 STORM DRAIN RISER 111, SHOW
 ALL PIPE SIZES AND SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM. RECHECK ALL
 PIPE SIZES PER TABLES 1106.2 & 1106.3 AS
 SOME PIPE SIZES ARE INCORRECT. THERE ARE
 STILL SOME PIPE SIZES THAT ARE
 INCORRECT. RISER III CHANGED TO RISER II
 AND MOVED TO SHT 41.1.
 46) SHT P-36 WATER HEATER DETAIL.
 THERMAL EXPANSION CONTROL IS REQUIRED
 PER SECTION 607.3.2. PLEASE INDICATE HOW
 THIS WILL BE ACCOMPLISHED. NO RESPONSE
 NOTED.
 47) SHT P-36 GENERAL PLUMBING NOTES:
 #2 1/4"/FT FOR 2-1/2" & SMALLER PIPE.
 TABLE 704.1. INDICATE ON NOTE. NO
 RESPONSE NOTED.
 #16 AIR CHAMBERS ARE NOT APPROVED.
 DELETE SYMBOL & REFERENCE. SECTIONS
 604.9 AND 104.2.1. - NO RESPONSE NOED.
 49) SUBMIT A CONDENSATE DRAIN ISOMETRIC
 WITH ALL PIPE SIZES, LOCATION OF RISER
 CONNECTIONS, RISERS, TERMINATION POINT
 OF THE RISERS (VENTS), AND INDICATE
 WHERE THE CONDENSATE DRAINS TO THE
 OUTSIDE OF THE BUILDING. SECTION
 104.2.1.
 50) SUBMIT RISERS AND BLDG ISOMETRIC FOR
 THE EMERGENCY T&P VALVE DISCHARGE LINE
 AND EHT EMERGENCY PAN DRAIN LINE FOR THE
 WATER HEATERS. SHOW ALL PIPE SIZES FOR
 ALL PIPING. SECTIONS 104.2.1, &
 104.3.1.1.
 51) PLANS DO NOT APPEAR TO BE 100% AND
 MORE COMMENTS MAY FOLLOW ON THE NEXT
 REVIEW DEPENDING ON THE RESPONSE OF THIS
 REVIEW. - PLANS STILL ARE NOT 100% AND
 MORE COMMENTS MAY FOLLOW.
 **************NEW COMMENTS**************
 1B) NEW FLOOR LAYOUTS, NEW REVIEW
 2B) SHTS A27 THRU A32 ALL TYPICAL UNITS
 SHOW CLEAR FLOOR SPACE FOR W/C'S PER
 PAGE 7.43 FHA DESIGN MANUAL. SEE MINIMUM
 CLEAR FLOOR SPACE SIZE REQUIREMENTS. -
 SHOWER CLEAR FLOOR SPACE SHALL BE
 PARALLEL AND FLUSH WITH THE CONTROL
 WALL. SEE PAGE 7.56.
 3B) SHTS A27 THRU A32 ALL TYPICAL UNITS
 WATER CLOSETS SHALL BE 18" OFF WALL TO
 CENERLINE OF FIXTURE. SEE PAGES 6.5,
 7.43, 7.44 & 7.45. THIS IS WHEN THE W/C
 IN NEXT TO A WALL.
 4B) SHTS A27 THRU A32 ALL TYPICAL UNITS
 SHALL SHOW THE DIMENSIONS FOR THE W/C
 OPENINGS. MINIMUM 33" REQUIRED. SEE
 PAGES 7.43 THRU 7.45
 5B) SHT A1 DRAWING INDEX DOES NOT
 REFLECT DRAWING SHEETS. SECTION 104.2.1.
 6B) SHT P-3 8" PD(8393SF) TURNS INTO 8"
 PD(8818SF) IN UNIT L/W-D-1, COL. LINE 6
 THEN BACK TO 8" PD(8393SF). CLARIFY.
 SECTION 104.2.1.
 7B) MANY SHEETS ON FLOOR PLAN AND RISERS
 FOR MANY UNITS STATES "ISLEND VENT SEE
 DETAIL ON SHEET P-36 OR SHEET P-42. NO
 NEW SHT 36 SUBMITTED, AND NO SHT 42
 SUBMITTED. PLEASE CLARIFY. SECTION
 104.2.1.
 8B) SHT P-3 15" REQUIRED FOR SANITARY
 BLDG. DRAIN (3907 FU), 10" REQUIRED ON
 SANITARY BLDG. DRAIN (1507 FU) COL. LINE
 5/I, 5" MIN. (231 FU) UNIT L/W-C-1.
 TABLE 701.1(1). - STORM AND AUXILLARY
 PIPING SIZE IS NOT CORRECT IN MANY
 AREAS. CHECK PIPE SIZE PER TABLES 1106.2
 AND 1106.3.
 7B) SHT P-4 STORM DRAIN RISERS S14.2,
 S14.3, & S14.4 NO PIPING TO STORM DRAIN
 SHOWN. SECTION 104.2.1. STORM &
 AUXILLARY PIPE SIZES INCORRECT, AND SOME
 PIPE SIZES ARE NOT SHOWN. TABLES 1106.2
 & 1106.3 AND SECTION 104.2.1.
 8B) SHT P-4 UNITS L/W-E-2 & L/W-E-3
 WATER CLOSETS ARE NOT VENTED, AND
 KITCHEN SINK AND FIXTURES FROM UPPER
 FLOORS SHALL NOT DRAIN THROUGH BATHROOM
 FIXTURES. SECTIONS 901.2.1 & 909.1
 9B) THE FOLLOWING SHEETS HAVE BEEN
 VOIDED, BUT NO NEW SHEETS HAVE BEEN
 SUBMITTED. P-1, P-2, P-11 THRU P-22,
 P-32, P-36, P-37, & P-42. PLANS
 INCOMPLETE. SECTION 104.2.1.
 10B) SHT P-5 6" REQUIRED FROM PD(3080SF)
 - 6" REQUIRED FROM PD(3719SF) - 6"
 REQUIRED FROM PD(3361SF) - RISER 10, 11,
 16, 10.1, SHOW RISER DESIGNATION NUMBER
 ON PLAN. TABLE 1106.3 & SECTION 104.2.1.
 UNIT L/W-B-1 WASH MACHINE SHALL NOT
 DRAIN INTO THE WET VENT FOR THE BATHROOM
 FIXTURES. SECTION 909.1
 11B) SHT P-6 5" MINIMUM REQUIRED PD
 (2343SF), 6" REQUIRED PF(3080SF) SHOW
 PIPING FOR PD(3061SF). TABLE 1106.3 AND
 SECTION 104.2.1. - UNIT L/W-B-1 WASH
 MACHINE SHALL NOT DRAIN INTO THE WET
 VENT FOR THE BATHROOM FIXTURES. SECTION
 909.1. - RISER DIAGRAM DESIGNATION 56 IS
 POINTING TO CONDENSATE LINE, NOT SANT.
 RISER. - FLOOR PLAN DOES NOT REFLECT THE
 RISER DIAGRAM (100). SECTION 104.2.1.
 12B) SHT P-7 6" REQUIRED ON AUXILLARY
 DRAIN LINES AT RISERS S/28, & S/29. 5"
 REQUIRED ON AUXILLARY DRAIN LINE BETWEEN
 COL. LINES 5 & 7/D & C. 8" REQUIRED ON
 AUXILLARY DRAINS S/8 & S/12. SHOW RISERS
 70 & 98 LOCATIONS ON FLOOR PLAN. - PIPE
 SIZES NOT SHOWN FOR ROOF DRAINS, PRIMARY
 AND SECONDARY FOR COMMON PATIO AND
 PRIVATE LANAI AREAS. SECTION 104.2.1 AND
 TABLE 1106.3. - UNITS C-3L MAX. 4 FU ON
 2" WET VENT TABLE 909.3.
 13B) SHT P-8 6" REQUIRED ON AUXILLARY
 DRAINS S/26 & S/29. 8" REQUIRED ON
 AUXILLARY DRAINS S/14, & S/18. SHOW ALL
 PIPE SIZES FOR ROOM PRIMARY & SECONDARY
 DRAINS AT COMMON PATIO AND PRIVATE LANAI
 AREAS. TABLES 1106.2 & 1106.3.
 14B) SHT P-10 UNIT C-3L MAX. 4 FU ON 2"
 WET VENT. TABLE 909.3 - BLDG DRAIN
 ISOMETRIC ON VOID SHT P-28 HAS BEEN
 DELETED. NEW SHEET DO NOT HAVE ALL THE
 BLDG. DRAIN ISOMETRIC SHOWN AND IS
 INCOMPLETE. SUBMIT A COMPLETE BLDG.
 DRAIN ISOMETRIC AS REQUIRED IN SECTION
 104.3.1.1. SHOW ALL PIPE SIZES,
 CLEANOUTS, RISERS ECT. SECTION 104.2.1.
 15B) SHT P-23 RISERS INDICATE TYPICAL
 3RD THRU 8TH FLOORS, BUT 3RD THRU 7TH
 FLOORS ARE DIFFERENT FROM 8TH FLOOR AS
 THE 8TH FLOOR SHOWS THE REVENTING. THIS
 IS NOT TYPICAL ON 3RD THRU 7TH FLOORS.
 SECTION 104.2.1.
 16B) ALL RISERS THAT SHOW RELIEF VENTS,
 RELEIF VENTS ARE ONLY REQUIRED IN SOIL &
 WASTE STACKS IN BUILDINGS HAVING MORE
 THAN 10 BRANCH INTERVALS. THESE ARE NOT
 REQUIRED. PLEASE DELETE FROM RISERS.
 SECTIONS 104.2.1 & 914.1.
 17B) SHT P-23 RISER 3,4,5,6 DOES NOT
 REFLECT THE FLOOR PLAN. SHT P-3 SHOWS
 RISER 6 CONNECTING TO RISER 345 ON THE
 FIRST FLOOR NOT AT THE MEZZ. LEVEL AS
 SHOWN ON THE RISER. SECTION 104.2.1. -
 SHT P-5 SHOWS ONLY RISER #8 WITH RISERS
 3,4,5,6 CONNECTING TO THIS RISER.
 CORRELATE RISERS AND FLOOR PLAN.
 18B) SHT P-23 RISER #7 DOES NOT REFLECT
 FLOOR PLAN ON SHT P-5 AT LAV. - RISER
 #10/11/10.1 STARTS OFF ON THE FLOOR PLAN
 SHT P-3 AS RISER 10/11/16, THEN CHANGES
 TO 10/11/10.1. PLEASE CLARIFY. WHY WAS
 10.1 NOT SHOWN AT BASE OF RISER, & WHY
 WAS RISER 16 NOT INDICATED ON SHT P-5 OR
 ON SHT P-23 RISER DESIGNATION? SECTION
 104.2.1.
 19B) SHT P-23 RISER 16 SHOWS NOTHING, &
 STOPS AT 2ND FLOOR. PLEASE CLARIFY.
 RISER 10/11/16/10.1 SHOWS VENT RISER #7.
 PLEASE CLARIFY. RISER DOES NOT REFLECT
 FLOOR PLAN AT RISER 10 ON THE 2ND FLOOR.
 CORRELATE RISER AND FLOOR PLAN. SECTION
 104.2.1.
 20B) TITLE BLOCK ON SOME SHEETS HAS
 WHITE OUT ON THEM AND THIS IS NOT
 APPROVED. SECTION 104.2.1.3
 21B) SHTS P-23, P-24, P-25, P-26, P-27,
 P-29, P-30, & P-31 CHECK ALL RISERS FOR
 COMPLIANCE WITH SECTIONS 903.1, 903.4,
 915, MAKE SURE THEY REFLECT THE FLOOR
 PLAN, 909.1, 909.3, RELIEF VENTS NOT
 REQUIRED 914, 905.3, 708.3.4, 711.2,
 711.3, 901.2.1. 910.2 AS THERE ARE
 NUMEROUS CODE VIOLATIONS AND ALL RISERS
 HAVE NOT BEEN CHECKED ON REVIEW. PLANS
 ARE MISSING FLOOR PLAN FOR NUMEROUS
 RISERS AND CAN NOT BE CHECKED TO SEE IF
 THEY REFLECT THE FLOOR PLAN. THESE WILL
 ALL BE CHECKED NEXT SUBMITTAL.
 22B) SHT P-34 W/C NOT VENTED AT UNITS
 L/W-E-2 & L/W-E-3 AND RISERS 96, 97,
 97.1, & 98 AND KITCHEN SINKS SHALL NOT
 DRAIN THROUGH THE WET VENT OF THE
 BATHROOM FIXTURES. 909.1
 23B) SHT P-35 SHOW ALL PIPE SIZES,
 DELETE AIR CHAMBERS, & SHOW ALL WATER
 HAMMER ARRESTORS REQUIRED BY SECTION
 604.9. SECTION 104.2.1.
 24B) SHT P-38 AIR CHAMBERS NOT APPROVED.
 DELETE FROM MENS AND WOMENS TOILET ROOMS
 ON ROOF TERRACE LEVEL. 604.9
 25B) SHTS P-39, P-40, P-41, & P-41.1,
 CHECK ALL AUXILLARY DRAINS FOR CORRECT
 SIZE. TABLE 1106.3 @ 4.5"/HR.
 ****************************************
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION. -
 NO RESPONSE TO THIS REQUIRES LAST
 SUBMITTAL.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-12-06 Cont ID  
Sent By kstevens Date 2004-12-06 Time 09:36 Rev Time 33.00
Received By kstevens Date 2004-11-29 Time 18:50 Sent To  
Notes
2004-12-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 FHA-98 DISIGN MANUAL
  
 1) SHTS I-1 & I-2 FIRM LICENSE NUMBER
 REQUIRED ON THE TITLE BLOCK, SIGNATURE
 REQUIRED, AND PRINTED NAME REQUIRED.
 FAC
 61G1-16.004(2)(5)(6, 61G1-16.003 AND FS
 481.219. - SUBMIT PROOF OF LEGAL
 SIGNATURE IN THE FORM OF A DRIVERS
 LICENSE, VOTERS REG. CARD ECT., AND
 SUBMIT A SIGNED/SEALED/DATED NOTORIZED
 LETTER WITH YOUR LEGAL SIGNATURE FOR
 OUR
 FILES.
 2)SHT I-1, AN RPZ BACKFLOW, INSTALLED
 BY
 A LICENSED PLUMBING CONTRACTOR IS
 REQUIRED FOR THE IRRIGATION SYSTEM.
 SHOW
 LOCATION ON PLANS. SECTIONS 608.13.2
 AND
 104.2.1
 3) SHTS A-11 & A-12 SHT INDEX STATES
 PARITAL 3RD-7TH FLOOR PLAN 1, BUT NOTE
 5
 STATES 3RD-5TH FLOOR PLAN. PLEASE
 CLARIFY. SECTION 104.2.1
 4) SHTS A-9, A-15 SUBMIT CALCULATIONS
 FOR PRIMARY AND SECONDARY ROOF DRAINS
 PER SECTIONS 1106, AND 1107 AND ALL SUB
 SECTIONS. SHOW SF OF EACH AREA WITH 1/2
 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS AND ROOF AREA FROM ABOVE THAT
 DRAINS ON TO THE ROOF ADDED TO THE
 CALCULATIONS. SHOW THE LOCATION OF ALL
 PRIMARY AND SECONDARY ROOF DRAINS AND
 THE SCUPPERS. ALSO SEE SHTS A-17 &
 A-18.
 THIS APPLIES TO THE ROOF DECK AREAS.
 5) SHTS A-9 & A-15 SHOW THE LOCATION
 AND
 SIZE OF ALL SECONDARY ROOF DRAINS AND
 THE SCUPPERS. SECTION 104.2.1.
 6) SHTS A-15 & A-16 SUBMIT CALCULATIONS
 FOR MINIMUM FACILITIES PER TABLES
 1003.1
 AND 403.1. SHOW THE SF OF EACH COMMON
 AREA AND TOTAL COMMON AREA IN
 CALCULATIONS.
 7) ARCHITECTURAL SHEETS, THE DATE
 PREPARED AND THE PRINTED NAME OF THE
 PERSON RESPONSIBLE FOR THE DOCUMENT ARE
 REQUIRED PER FAC 61G1-16.004(4)(6) AND
 FS 481.2055
 8) SHTS A30, A-31, & A-32 INDICATE
 SPECIFICATION "A" OR "B" FOR EACH UNIT
 OR BATHROOM AS REQUIRED ON PAGE 7.35
 FHA
 DESIGN MANUAL.
 9) SHTS A30, A-31, & A-32 SHOW THE SIZE
 OF THE OPENINGS FOR ALL COVERED WATER
 CLOSETS. MINIMUM 33" REQUIRED. SEE
 PAGES
 6.5 AND 6.7 FHA DESIGN MANUAL. - THE
 18"
 FROM THE WALL TO THE CENTERLINE OF THE
 W/C IS AN ABSOLUTE MEASURMENT. SEE
 FIGS.
 PAGE 6.3 AND 6.5
 10) SHT A33 MENS & WOMENS RESTROOMS,
 SHOW CLEAR FLOOR SPACE FOR EACH
 ACCESSIBLE FIXTURE. SECTIONS 11-4.16.2,
 11-4.19.E, & 11-4.22.3. THE TURNING
 AREA
 SHALL BE SHOWN IN THE TOILET ROOM, NOT
 IN THE ACCESSIBLE STALL. ALSO SHOW
 WATER
 CLOSED HEIGHT 11-4.16.3. GRAB HEIGHT
 MAX
 36". SHOWN AS 48" ON DETAIL BEHIND W/C.
 SHOW FLUSH CONTROL 11-4.16.5. SHOW
 URINAL HEIGHT 11-4.18.2. THE CENTERLINE
 OF THE W/C SHALL BE 18" TO THE WALL,
 NOT
 20" AS SHOWN. (SEE FIG 28). FOR THE
 LAVS
 SHOW KNEE CLEARANCE 11-4.19.2, FOR THE
 SHOWER SHOW CONTROLS 11-4.21.5, SHOWER
 UNIT 11-4.21.6, AND CURB 11-4.21.8.
 12) SHT A33 DETAIL #1 IN BOTH MENS AND
 WOMENS RESTROOM. THE DOUBLE LAVS TO BE
 34" IN HEIGHT AND HAVE A CLEARANCE OF
 29". SEE FIG 31 - SECTION 11-4.19.2
 13) A DRINKING FOUNTAIN IS REQUIRED IN
 THE COMMON AREA. SUBMIT A DETAIL
 COMPLYING WITH SECTION 11-4.15 AND ALL
 SUBSECTIONS & 11-4.1.3(10)(A) FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
 14) SHT A36 SHOW HEIGHT AND WIDTH OF
 SCUPPER OPENINGS ON THE DETAIL.
 15) A PROFESSIONAL ENGINEER SHALL SIGN
 HIS NAME. INITIALS ARE NOT APPROVED PER
 THE RULING BY FBPE. SUBMIT AN EXAMPLE
 OF
 THE ENGINEERS LEGAL SIGNATURE BY WAY OF
 DRIVERS LICENSE, VOTERS REG. ECT, AND A
 SIGNED SEALED NOTORIZED LETTER
 INDICATING YOUR LEGAL SIGNATURE FOR OUR
 FILES. FAC 61G15.23.002(1)(2) AND FS
 471.025. - THIS IS FOR ALL ENGINEERED
 SHEETS.
 16) ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, LICENSE NUMBER AND
 CERTIFICATE OF AUTHORIZATION NUMBER OF
 THE ENGINEERING BUSINESS ON EACH SHEET.
 FAC 61G15-23.002(2)
 17) SHTS P-1 & P-2 PD'S SIZING AND
 PIPING SIZING NOT CORRECT FOR ALL PD'S.
 RECHECK SIZING PER TABLES 1106.2 &
 1106.3 - SHOW ALL SF AND PIPE SIZES.
 18) SUBMIT MANUF. SPECIFICATION SHEETS
 FOR ELEVATOR SUMP PUMPS AND THE STORM
 WATER SUMP PUMPS. PUMPS INFORMATION
 SHALL SHOW LISTING. SECTION 303.4
 19) SHTS P-3, & P-4 STORM PIPE SIZING
 NOT CORRECT AS WELL AS THE EMERGENCY
 ROOF DRAIN PIPING (SECONDARY ROOF
 DRAINS). SEE TABLES 1106.2 & 1106.3. NO
 SF SHOWN FOR PD'S AT COL. LINE 5/G-F1
 AND COL. LINE 6/F-E2. PD BETWEEN COLS.
 8.1 & 8.3 NORTH OF STAIRWAY #2 NO ADDED
 TO THE SYSTEM. DOUBLE CHECK ALL PIPE
 SIZES AND SHOW ADDITION OF ALL SF AS
 THEY ACCUMULATE IN THE STORM BLDG
 DRAIN.
 SECTION 104.2.1.
 20) SHT P-3 MANY UNITS INDICATE 1-1/2"
 TRAP FOR THE W/M. MINIMUM 2" TRAP
 REQUIRED. TABLE 709.1
 21) SHT P-3 UNIT L/W-B-1 SHOWS 2" 2FU
 FROM KIT. SINK, BUT CHANGES TO 4" 91 FU
 DOWNSTREAM. PLEASE CLARIFY. SECTION
 104.2.1.
 22) SHT P-4 STORM RISER DIAGRAM, SF FOR
 PD AT COL. LINES 10/C2, 12/C2, 11/E2, &
 TRASH ROOM BY STAIR #3 NOT SHOWN.
 PLEASE
 INDICATE SF FOR EACH PER TABLES 1106.2
 AND 1106.3. SECTION 104.2.1
 23) SHT P-4 UNITS L/W-E-2 & L/W-E-3
 FITTING NOT INSTALLED PER SECTION
 706.3.
 EACH UNIT SHOWS 76 FU, BUT FLOOR PLAN
 SHOWS 2 RISERS EACH UNIT ONE WITH 68 FU
 AND THE OTHER WITH 76 FT. PLEASE
 CLARIFY
 24) SHT P-4 MOST W/M'S SHOW 1-1/2"
 TRAPS
 BUT TABLE 709.1 REQUIRES 2" TRAPS.
 25) SHT P-4 UNABLE TO FIND SOME RISERS
 SHOWN ON THE FLOOR PLAN. PLEASE SUBMIT
 A
 SANT. RISER DIAGRAM FOR EACH RISER
 SHOWN
 ON THE FLOOR PLAN. SECTIONS 104.2.1 AND
 104.3.1.1
 26) ALL AAV'S INSTALLED BELOW THE 5TH
 FLOOR SHALL HAVE A RELIEF VENT
 INSTALLED
 PER SECTION 607.3.2. (SHOW ON THE SANT.
 RISER DIAGRAM).
 27) SHT P-5 CHECK ALL PIPE SIZING ON
 THE
 STORM SYSTEM AND SHOW ALL PIPE SIZES.
 SECTION 104.2.1 AND TABLES 1106.2 AND
 1106.3.
 28) SHT P-5 UNIT L/W-B-4 W/C NOT
 VENTED,
 AND UNIT L/W-B-5 W/C AND TUB NOT
 VENTED.
 SECTION 902.1.
 29) SHT P-6 RECHECK ALL PIPE SIZES AND
 SHOW ALL PIPE SIZES ON PLANS. - UNITS
 L/W-B-4 AND L/W-A-1 W/C'S ARE NOT
 VENTED. SECTION 902.1.
 30) ALL SHTS ALL AAV'S 4TH FLOOR AND
 BELOW REQUIRE A RELIEF VENT. SECTION
 607.3.2. SHOW ON FLOOR PLAN AND SANT.
 RISER DIAGRAM. SECTION 607.3.2.
 31) SHT P-8 UNIT C-5 W/C NOT VENTED 2ND
 BATH. SECTION 902.1 - SHOW ALL STORM
 PIPING SIZES. UNIT C-4L BATHROOM GROUP
 CONNECTED TO VENT STACK. SHALL BE
 CONNECTED TO DRAIN STACK. - STORM AT
 COL
 10 BY THE M/B UNIT B-4 IS INCORRECTLY
 IDENTIFIED. SECTION 104.2.1.
 32) SHT P-9 UNITS C-5 BATHROOM EITH
 SIDE
 OF STAIRWAY #2, W/C'S NOT VENTED AND
 LAVS/TUBS ARE CONNECTED TO THE VENT
 LINE
 NOT THE DRAIN STACK AS REQUIRED.
 33) SHT P-10 UNITS C-5, C-6L &D-1A, W/C
 NOT VENTED SECTION 902.1. LAV/TUB
 CONNECTED TO THE VENT STACK, NOT THE
 WASTE STACK AS REQUIRED.
 34) SHT P-11 AUXILLORY HORIZONTAL DRAIN
 PIPE SIZE NO SIZED CORRECTLY. TABLE
 11106.3.
 35) THE TRASH CHUTE REQUIRES AN "N36"
 VACUUM BREAKER FOR BACKFLOW PROTECTION.
 SECTION 608.13.6.
 36) SHT P-12 AUXILLARY HORIZONTAL DRAIN
 PIPE SIZE PER 1106.3.
 37) SHTS P-13, & P-14 AUXILLARY ROOF
 DRAIN NEAR POOL CAN NOT BE A TRIPPING
 HAZARD. PLEASE SUBMIT A DETAIL FOR S/27,
 S/28, S/29, & S/30 SECONDARY DRAINS.
 SECTION 104.2.1.
 38) SHT P-22 NO WATER SUPPLY SHOWN TO
 THE TRASH ROOM FOR THE TRASH CHUTE.
 PLEASE SHOW ON PLANS. SECTION 104.2.1
 39) SHTS P-24, P-25, P-26, P-27, & P-28
 DO NOT MEET CODE REQUIREMENTS. IN MANY
 CASES THESE ARE THE CODE ISSUES NOT
 ADDRESSED.
 A) OFFSET VENTS ARE REQUIRED WHEN
 HORIZONTAL OFFSETS ARE USED. SECTION
 915
 B) NO HORIZ. DRY VENTS. SECTION 905.3
 C) STACK DRAIN SHALL CONNECT DOWNSTREAM
 OF THE BATHROOM GROUP FIXTURES. SECTION
 909.1
 D) KITCHEN SINK SHALL NOT DRAIN THROUGH
 THE WET VENT. SECTION 909.1.
 E) MAIN VENT REQUIRED AT TOP OF STACKS.
 SECTION 903.1.
 F) CLEANOUTS REQUIRED AT THE BASE OF
 EACH STACK. SECTION 708.3.4.
 G) HORIZONTAL BRANCH CONNECTION TO A
 HORIZONTAL STACK OFFSET. SECTIONS 711.2
 & 711.3.
 H) VENTING REQUIRED 901.2.1
 I) STACK INSTALLATION 910.2
 THE RISERS ARE NOT CLEAR TO THEIR INTENT
 AND THE USE OF TEE FITTINGS AS SHOWN ON
 THE RISERS ARE NOT APPROVED. (BULL HEAD
 TEES ARE SHOWN WHERE THE SEWAGE IS NOT
 DIRECTED IN THE DIRECT OF FLOW. CHECK
 ALL RISERS FOR CODE REQUIREMENTS.
 40) SHTS P-24, P-25, P-26, P-27, 7 P-28.
 SANITARY RISER DIAGRAMS DO NOT REFLECT
 THE FLOOR PLAN. THE FIXTURES FOR THE
 MEZZANINE LEVEL ARE SHOWN ABOVE THE
 MEZZANINE LEVEL WHEN THE PIPING WILL BE
 BELOW THE MEZZANINE LEVEL. FIXTURES FOR
 THE SECOND FLOOR ARE SHOWN ABOVE THE
 SECOND FLOOR WHEN THE PIPING WILL BE
 UNDER THE SECOND FLOOR. THE FIXTURES FOR
 THE THIRD THRU THE EIGHT FLOOR ARE SHOWN
 BELOW THE TERRACE FLOOR. SHOULD BE BELOW
 THE EIGHT FLOOR. SECTION 104.2.1
 41) NO INFORMATION CAN BE READ ON THE
 ENGINEER'S SEAL. THE SEAL SHALL BE AN
 IMPRESSION TYPE THAT IMPARTS THE
 REQUIRED INFORMATION ON THE PLANS. FAC
 61G15-23.001(1) & FS 471.025
 42) SHTS P-28 & P-29 SANT. BLDG. DRAIN
 ISOMETRIC, SHOW ALL PIPE SIZES AND SHOW
 THE DFU'S AS THEY ACCUMULATE IN THE
 SYSTEM. SECTION 104.2.1 & TABLE
 710.1(1)
 43) SHT P-31 AIR CHAMBERS ARE NOT
 APPROVED. DELETE FROM ALL RISERS. WATER
 HAMMER ARRESTORS REQUIRED BY SECTION
 604.9 SHALL BE LOCATED AT ALL QUICK
 CLOSING VALVES, (W/M, ICE MAKER, AND
 DISH WASHER), AND SHALL BE LOCATED NEAR
 THE FIXTURE. PDI-WH 201 & MANUF.
 INSTALLATION INSTRUCTIONS.
 44) SHTS P-33 & P-34 AUXILLARY ROOF
 DRAINS ON SOME SYSTEMS ARE UNDERSIZED.
 PLEASE SIZE PER TABLE 1106.3.
 45) SHT P-35 STORM DRAIN RISER III, SHOW
 ALL PIPE SIZES AND SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM. RECHECK ALL
 PIPE SIZES PER TABLES 1106.2 & 1106.3 AS
 SOME PIPE SIZES ARE NOT CORRECT.
 46) SHT P-36 WATER HEATER DETAIL.
 THERMAL EXPANSION CONTROL IS REQUIRED
 PER SECTION 607.3.2. PLEASE INDICATE HOW
 THIS WILL BE ACCOMPLISHED.
 47) SHT P-36 GENERAL PLUMBING NOTES:
 #2 1/4" FOR 2-1/2" & SMALLER PIPE.
 TABLE 704.1 INDICATE ON NOTE.
 #16 AIR CHAMBERS ARE NOT APPROVED.
 DELETE SYMBOL & REFERENCE. SECTIONS
 604.9 AND 104.2.1.
 48) SUBMIT A WATER RISER DIAGRAM IN
 ISOMETRIC FORM FOR THE BLDG WATER PIPING
 SHOWING ALL PIPE SIZES, VALVES, WATER
 HAMMER ARRESTORS, AND LOCATION OF ALL
 RISER CONNECTIONS TO THE DISTRIBUTION
 PIPING.
 49) SUBMIT A CONDENSATE DRAIN ISOMETRIC
 WITH ALL PIPE SIZES, LOCATION OF RISER
 CONNECTIONS, RISERS, TERMINATION POINT
 OF THE RISERS (VENTS), AND INDICATE
 WHERE THE CONDENSATE DRAINS TO OUTSIDE
 OF THE BUILDING. SECTION 104.2.1.
 50) SUBMIT RISERS AND BLDG ISOMETRIC FOR
 THE EMERGENCY T&P VALVE DISCHARGE LINE
 AND THE EMERGENCY PAN DRAIN LINE FOR THE
 WATER HEATER. SHOW ALL PIPE SIZE FOR ALL
 PIPING. SECTIONS 104.2.1 & 104.3.1.1.
 51) PLANS DO NOT APPEAR TO BE 100% AND
 MORE COMMENTS MAY FOLLOW ON THE NEXT
 REVIEW DEPENDING ON THE RESPONSE OF THIS
 REVIEW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2005-08-31 Cont ID  
Sent By aaponte Date 2005-08-31 Time 16:40 Rev Time 0.00
Received By aaponte Date 2005-08-31 Time 16:39 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2005-07-26 Cont ID  
Sent By aaponte Date 2005-07-26 Time 12:36 Rev Time 0.00
Received By aaponte Date 2005-07-26 Time 12:36 Sent To  
Notes
2005-07-26 00:00:001.PARKING RAMP TO ACCESS SECOND LEVEL OF
 PARKING SHALL BE 12 FEET CLEAR ON EACH
 DIRECTION.
 2. ALLEY SHALL BE 20 FEET CLEAR TO
 ACCESS PARKING ENTRANCE.
 3. PLEASE REVISE CALCULATION OF OPEN
 SPACE. TOTAL AMOUNT PROVIDED IS 3,796SF
 AND REQUIRED AMOUNT IS 4,288SF.
 4. PLEASE DEFINE THE TYPE OF UNITS
 PROVIDED ON THE FIRST FLOOR. RESIDENTIAL
 USES REQUIRE TO BE 18 INCHES ABOVE
 GRADE; LIVE/WORK TYPE MUST BE AT GRADE.
 5.PLEASE PROVIDE A SAMPLE FOR THE WINDOW
 TINTING.

Review Stop Z ZONING
Rev No 2 Status F Date 2005-05-12 Cont ID  
Sent By aaponte Date 2005-05-11 Time 16:54 Rev Time 0.00
Received By aaponte Date 2005-05-11 Time 16:54 Sent To  
Notes
2005-05-12 00:00:001. LOADING DOCK IS LOCATED ON A DEAD END
 ALLEY. PLEASE PROVIDE ALTERNATIVE EXIT
 OR WIDEN THE ALLEY FOR A TWO TRAFFIC
 WAY.
 2. SIDEWALK ON ROSEMARY AVENUE SHALL BE
 MINIMUM 8 FEET WIDE.
 3. ENTRY DOORS FOR UNITS AT THE SOUTH
 SIDE OF THE OPEN SPACE SHALL BE MODIFIED
 TO FACE THE OPEN SPACE.
 4. PLEASE PROVIDE A TABLE TO CONFIRM
 COMPLIANCE WITH 15% LANDSCAPE
 REQUIREMENT FOR THE ROOFTOP TERRACE.
 5. TREES PLANTED ON ROSEMARY AVENUE
 SHALL BE CONSISTENT WITH EXISTING TREES
 ON THE SAME STREET. RECOMMENDED SPECIE:
 CATHEDRAL OR HIGH RISE LIVE OAK.
 6. BANYAN BOULEVARD SHALL PROVIDE SHADE
 TREES ALONG THE SIDEWALK. RECOMMENDED
 SPECIE: DAHOON HOLLY.
 7.PLEASE DEFINE WHAT TYPE OF UNITS ARE
 YOU LOCATING ON THE FIRST FLOOR
 (RESIDENTIAL OR LIVE/WORK).
 8. PLEASE SHOW ACCESIBLE ROUTE FROM THE
 PARKING GARAGE FOR THE TWO UNITS ON THE
 SOUTH SIDE OF ROSEMARY AVENUE.
 9.LIVE/WORK TYPE UNITS MUST HAVE A
 HANDICAP ADAPTABLE RESTROOM ON THE FIRST
 FLOOR (ACCORDING TO THE FLORIDA BUILDING
 CODE).
 10. ENTRANCE DOOR FOR LIVE/WORK TYPE
 UNITS MUST BE MINIMUM 3 FEET.
 11.ARCHITECTURAL DESIGN GUIDELINES:
 - FIRST FLOOR WINDOWS SHALL HAVE A KICK
 PLATE BETWEEN 18 AND 42 INCHES MINIMUM.
 - ARCHES ON THE TOP FLOOR ARE NOT
 CONSISTENT WITH THE OVERALL BUILDING
 DESIGN. PLEASE MODIFY AND ENHANCE THE
 TREATMENT OF THE BUILDING TOP.

Review Stop Z ZONING
Rev No 1 Status F Date 2004-11-24 Cont ID  
Sent By aaponte Date 2004-11-24 Time 08:47 Rev Time 0.00
Received By aaponte Date 2004-11-24 Time 08:47 Sent To  
Notes
2004-11-24 00:00:001. FIRST FLOOR IS EXCEEDING THE MAXIMUM
 20 FEET FROM FINISHED FLOOR TO FINISHED
 FLOOR ALLOWED BY ART. IV SECTION 94-113
 (A)(6). PLEASE MODIFY DIMENSION OR
 PROCEED FOR DAC VARIANCE.
 2.PLEASE CONFIRM MEZZANINES ARE IN
 COMPLIANCE WITH PEMISSIBLE PERCENTAGE OF
 FLOOR AREA ACCORDING WITH THE CITY'S
 BUILDING CODE.
 3.PLEASE REVISE LOCATION OF PROPERTY ON
 SITE PLAN AND LANDSCAPE DRAWING TO
 CONFIRM COMPLIANCE WITH MAXIMUM 5 FEET
 SETBACK; AND OVERHANG OF BALCONIES ON
 ROW.
 4.SIDEWALK SHALL BE A MINIMUM OF 8 FEET.
 PLEASE CONFIRM COMPLIANCE WITH THIS
 REQUIREMENT.
 5.PLEASE PROVIDE A TABLE TO SPEFIFY THE
 NUMBER OF RESIDENTIAL UNITS AND THE
 NUMBER OF PARKING SPACES PROVIDED.
 6. TRAVEL LANES IN PARKING GARAGE SHALL
 BE 24 FEET WIDE MINIMUM.
 7. NORTH ELEVATION WAS NOT INCLUDED WITH
 SUBMITTED DRAWINGS.
 8.PLEASE PROVIDE A TABLE TO CONFIRM
 COMPLIANCE WITH OPEN SPACE REQUIREMENT.
 9.OPEN SPACE SHALL BE DESIGN ACCORDING
 WITH OPEN SPACE DESIGN GUIDELINE; AND
 SHALL INCLUDE SEATING AREA FOR THE
 PUBLIC, LIGHTING AND AT LEAST ONE
 DRINKING FOUNTAIN.
 10.PLEASE PROVIDE A TABLE TO CONFIRM
 COMPLIANCE WITH 15% LANDSCAPE
 REQUIREMENT FOR THE ROOFTOP TERRACE.
 11.ON ROOFTOP TERRACE, CLIMATE
 CONTROLLED STRUCTURES ARE LIMITED TO THE
 MINIMUM AREA NECESSARY TO ACCOMODATE
 STRUCTURES THAT ARE SECONDARY AND
 INCIDENTAL TO THE PRIMARY ROOFTOP
 AMENITY.
 11. TREES PLANTED ON ROSEMARY AVENUE
 SHALL BE CONISTENT WITH EXISTING TREES
 ON THE SAME STREET. RECOMMENDED SPECIE:
 CATHEDRAL OR HIGH RISE LIVE OAK.
 12. BANYAN BOULEVARD SHALL PROVIDE SHADE
 TREES ALONG THE SIDEWAK. RECOMMENDED
 SPECIE: DAHOON HOLLY.
 13.ARCHITECTURAL DESIGN GUIDELINES:
 - DOOR OR WINDOWS SHALL BE CENTERED WITH
 THE ASSOCIATED BALCONY.
 - FISR FLOOR WINDOWS SHALL HAVE A KICK
 PLATE BETWEEN 18 AND 42 INCHES MINIMUM.
 - ARCHES ON THE TOP FLOOR ARE NOT
 CONSISTENT WITH THE OVERALL BUILDING
 DESIGN.
 - CANTILEVERED BALCONIES SHALL EXTEND NO
 MORE THAN 3 FEET FROM THE BUILDING
 FACADE AND SHALL BE VISIBLY SUPPORTED BY
 BRACKETS.
 - ALL WINDOWS SHALL BE OPERABLE AS HUNG
 OR CASEMENT.
  
  
  