Plan Review Details - Permit 04110182
Plan Review Stops For Permit 04110182
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-12-06 Cont ID  
Sent By jwitmer Date 2006-12-07 Time 10:29 Rev Time 1.00
Received By jleahy Date 2006-12-07 Time 06:34 Sent To  
Notes
2006-12-07 06:32:52INSTALL BATH FIXTURES PER 210.70A

Review Stop B BUILDING (STRUCTURAL)
Rev No 23 Status P Date 2007-05-21 Cont ID  
Sent By rbrown Date 2007-05-21 Time 18:46 Rev Time 0.00
Received By rbrown Date 2007-05-21 Time 18:46 Sent To  
Notes
2007-05-21 18:47:04REVISION SUBMITTED ON 5/4/07 FOR MULLIONS AND SUBMITTAL
 FOR SGD AND SH WINDOW ENGINEERING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 22 Status F Date 2007-04-18 Cont ID  
Sent By jwitmer Date 2007-04-18 Time 13:49 Rev Time 12.00
Received By jwitmer Date 2007-04-18 Time 13:49 Sent To PC
Notes
2007-04-18 13:52:20BUILDING PLAN REVIEW
 PERMIT: 04110182
 ADD: 3900 N FLAGLER DR BLDG 4/5
 CONT: THE WEITZ CO.
 TEL: (561)723-4084
  
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)THE REVISIONS SUBMITTEDAPRIL 13/2007 WHICH
 INCLUDE MIAMI WALL SYSTEMS :
 100 ALUMINIUM SLIDIG GLASS DOORS LARGE AND SMALL MISSLE
 IMPACT RESISTANT UNITS:
 MIAMI-DADE NOA:
 04-0908.022001 FBC- LARGE & SMALL MISSLE 100
 ALUMINUM SLIDING GLASS DOORS
 01-1108.032001 FBC- SMALL MISSLE 100 ALUMINUM
 SLIDING GLASS DOORS
 03-1008.032001 FBC- LARGE MISSLE 122 ALUMINUM
 SINGLE HUNG WINDOW
 03-1008.042001 FBC- SMALL MISSLE 122 ALUMINUM
 SINGLE HUNG WINDOW
  
 THIS MORNINGS VISIT TO THE JOBSITE WITH HAROLD PISKURA
 WE WERE ABLE TO VERIFY THE GLASS THICKNESS USED IN EACH
 OF THE INSTALLATION SINGLE HUNG WINDOWS AS WELL AS THE
 SLIDING GLASS DOORS. THE CONCERNS ARE AS FOLLOWS IN
 THIS EXAMPLE:
  
 1A) WHERE ON THE SLIDING GLASS DOORS WE ARE ABLE TO
 VERIFY THE GLASS THICKNESS OF 9/16" FOR THE SLIDING
 GLASS DOORS WE ARE NOT ABLE TO VERIFY AS TO WHICH
 LAMINATE
 WAS INSTALLED IN EACH OF THE UNITS. THE NOA 04-0908.02
 TECHNICAL SHEET 1 OF 4 CLEARLY INDICATES ALL GLASS
 TYPES ARE 9/16" THICK ONLY GLASS TYPES A & B CAN MAKE
 THE WIND
 LOADS ABOVE +/- 70. THE FRAMES OF THIS UNIT INDICATE
 THEY HAVE THE HEAVY REINFORCEMENT FOUND INNOA
 01-1108.03/ FTL# 1743.
  
 1B)THE SECOND CONCERN IS THE FRAMES LISTED UNDER
 MIAMI WALL SYSTEMS, INC SGDSMALL MISSLE LAM GLASSNOA
 01-1108.03TECHNICAL SHEETS 2-5 INDICATE THE SLIDING
 GLASS DOOR UNITS WITH NO REINFORCEMENT, LIGHT, MEDIUM
 AND HEAVY REINFORCEMENT AND THE ASSOCIATED PRESSURES.
 AGAIN WE HAVE NO WAY OF VISUALLY INSPECTING THE
 INSTALLED FRAMES AND
 VERIFYING WHAT TYPE OF REINFORCEMENT IS IN THE FRAME IF
 ANY, THUS HAVING LOW PRESSURES. NO APPROVAL LABELS ON
 DOORS OR WINDOWS.
  
 1707.4.2.1 TESTING AND LABELING. EXTERIOR WINDOWS AND
 GLASS DOORS
 SHALL BE TESTED BY AN APPROVED INDEPENDENT TESTING
 LABORATORY, AND
 SHALL BE LABELED WITH AN APPROVED LABEL IDENTIFYING
 THE MANUFACTURER,
 PERFORMANCE CHARACTERISTICS AND APPROVED PRODUCT
 CERTIFICATION AGENCY,
 TESTING LABORATORY, EVALUATION ENTITY OR MIAMI-DADE
 NOTICE OF
 ACCEPTANCE TO INDICATE COMPLIANCE WITH THE
 REQUIREMENTS OF ONE OF THE
 FOLLOWING SPECIFICATIONS:
  
 ANSI/AAMA/NWWDA 101/I.S.2-97 OR TAS 202
 (HVHZ SHALL COMPLY WITH TAS 202)
  
 2) WITH VISITING THE JOBSITE TO VERIFY THE TYPE OF
 GLASS AND THICKNESS TWO MORE CONCERNS WERE NOTICED. 2A)
 ON THE FOURTH FLOOR WE NOTICED A MULLION BETWEEN TWO
 SEPERATE SLIDING GLASS DOORS. THERE IS NO PRODUCT
 APPROVALS SUBMITTED FOR STRUCTURAL MULLIONS. PLEASE
 PROVIDE PRODUCT APPROVALS FOR THE STRUCTURAL MULLION.
  
 2B) WITH VISITING THE JOBSITE IN EACH UNITS VISITED,
 THE SLIDING GLASS DOOR TRACK WAS APPROXIMATELY 41/2"
 ABOVE THE CONCRETEFLOOR. IN RETURNING TO THE BUILDING
 DEPARTMENT
 I REVIEWED THE CITY SEET OF REVIEWED PLANS FOR
 THIS TYPE OF DETAIL, SHEET A440 DETAIL # 6 PROVIDED THE
 DETAIL THAT WS REVIEWED TO THE FAIR HOUSING STANDARDS.
 I ALSO DISCUSSED THIS ISSUE WITH BO NEIL MELICK WHICH
 HE ALSO INDICATED ALL UNITS ARE TO COMPLY WITH THE FAIR
 HOUSING STANDARDS FOR SLIDING GLASS DOORS USED AS A
 SECONDARY ENTRANCE.
 A COPY OF THIS STANDARDIS ATTACHED.
  
 3) THE SAME ISSUE AS (1A)IS THE TYPE OF LAMINATION
 USED FOR THE SINGLE HUNG WINDOWS, THERE IS NO WAY OF
 KNOWING WHAT TYPE OF LAMINATION WAS USED.
 THE ONE WAY THAT WE CAN IDENTIFY WHAT TYPE OF UNITS
 WERE SHIPPED IS BY PROVIDING A COPY OF THE BILL OF
 LADING, THIS MAY IDENTIFY THE AMOUNT OF WINDOWS AND
 DOORS
 THAT WERE SHIPPED TO THE JOB SITE?
  
 4) NOTE: JOBSITE INSPECTION OF THE LOBBY ENTRY DOORS,
 YES THE PRODUCT APPROVAL FOR SIGNATURE DOORS DOES
 INCLUDE LARGE MISSLE TESTING NOA 04-0211.09
 DOORS DO NOT HAVE ANY APPROVAL LABELS.
 1707.4.2.1 TESTING AND LABELING. EXTERIOR WINDOWS AND
 GLASS DOORS
 SHALL BE TESTED BY AN APPROVED INDEPENDENT TESTING
 LABORATORY, AND
 SHALL BE LABELED WITH AN APPROVED LABEL IDENTIFYING
 THE MANUFACTURER,
 PERFORMANCE CHARACTERISTICS AND APPROVED PRODUCT
 CERTIFICATION AGENCY,
 TESTING LABORATORY, EVALUATION ENTITY OR MIAMI-DADE
 NOTICE OF
 ACCEPTANCE TO INDICATE COMPLIANCE WITH THE
 REQUIREMENTS OF ONE OF THE
 FOLLOWING SPECIFICATIONS:
 ANSI/AAMA/NWWDA 101/I.S.2-97 OR TAS 202
 (HVHZ SHALL COMPLY WITH TAS 202)
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 21 Status P Date 2007-03-16 Cont ID  
Sent By jwitmer Date 2007-03-16 Time 15:24 Rev Time 0.55
Received By jwitmer Date 2007-03-16 Time 15:24 Sent To B
Notes
2007-03-16 15:24:46WALL FRAMING AND CALCS

Review Stop B BUILDING (STRUCTURAL)
Rev No 20 Status P Date 2007-03-16 Cont ID  
Sent By jwitmer Date 2007-03-16 Time 14:20 Rev Time 0.55
Received By jwitmer Date 2007-03-16 Time 14:20 Sent To PC
Notes
2007-03-16 14:22:09REVISION # 916'-0" OVERHEAD GARAGE DOOR

Review Stop B BUILDING (STRUCTURAL)
Rev No 19 Status F Date 2006-05-03 Cont ID  
Sent By jwitmer Date 2006-05-03 Time 07:35 Rev Time 1.55
Received By jwitmer Date 2006-05-03 Time 07:35 Sent To PC
Notes
2006-05-03 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04110182
 ADD:3900 N FLAGLER DR
 CONT: THE WEITZ CO
 TEL: (561)719-6724
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: SHORING LETTERS BLDG# 5 LEVEL(4)
 ACTION:DENIED
  
 2ND REVIEW
  
 KEEPING 2 ORIGINAL LETTERS POSSIBLY TO
 BE SENT TO THE ENGINEERS BOARD FOR
 REVIEW,FLORIDA ADMINISTRATIVE CODE
 61G15-23.002(1) A PROFESSIONAL ENGINEER
 SHALL SIGN HIS NAME AND AFFIX HIS SEAL
 TO ALL PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED OR ISSUED BY
 SAID REGISTRAINT AND BEING FILED FOR
 PUBLIC RECORD.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 18 Status F Date 2006-04-04 Cont ID  
Sent By jwitmer Date 2006-04-04 Time 10:55 Rev Time 1.66
Received By jwitmer Date 2006-04-04 Time 10:55 Sent To PC
Notes
2006-04-04 00:00:00REVISION OVERHEAD DOOR SECTIONAL STEEL
 16'-0" WIDE DOOR.
 BUILDING PLAN REVIEW
 PERMIT:04110182
 04110183
 04110184
 04110185
  
 ADD:3900 N FLAGLER BLDG 1-4
 CONT: THE WEITZ
 TEL: (561)719-6724
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVISION
 ACTION: DENIED
  
 PRODUCT APPROVAL REPORT SUBMITTED IS OUT
 OF DATE, EXPIRES 12/01/05.
  
 JIM WITMER
 BUILDING PLAN REVIEW

Review Stop B BUILDING (STRUCTURAL)
Rev No 17 Status F Date 2006-03-14 Cont ID  
Sent By shill Date 2006-03-14 Time 13:37 Rev Time 0.00
Received By shill Date 2006-03-14 Time 13:37 Sent To  
Notes
2006-03-14 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 SHORING LETTERS, BLDG 5 LEVEL 4 FLOOR
  
 1.)NOTARY INFORMATION TO INCLUDE ALL
 REQUIREMENTS OF FS117(3)(A).
  
 2.)THE ENGINEER'S SIGNATURE IS A
 PHOTOCOPY; ORIGINAL REQUIRED PER FBPE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 16 Status P Date 2006-03-01 Cont ID  
Sent By shill Date 2006-03-01 Time 14:55 Rev Time 0.00
Received By shill Date 2006-03-01 Time 14:55 Sent To  
Notes
2006-03-01 00:00:00SHORING INSPECTION LETTER, 5TH LEVEL,
 FROM DUNKELBERGER ENGINEERING

Review Stop B BUILDING (STRUCTURAL)
Rev No 15 Status F Date 2006-03-01 Cont ID  
Sent By shill Date 2006-03-01 Time 14:53 Rev Time 0.00
Received By shill Date 2006-03-01 Time 14:53 Sent To  
Notes
2006-03-01 00:00:00****CORRECTIONS****
  
 SHORING COMPLIANCE LETTER, LEVEL 5
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)FS117(3)(A), NEARLY
 ALL OF THE REQUIRED INFORMATION (FOR A
 NOTARIZED SIGNATURE) IS LACKING FROM THE
 CONTRACTOR SHORING COMPLIANCE
 CERTIFICATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status P Date 2006-02-16 Cont ID  
Sent By shill Date 2006-02-16 Time 13:40 Rev Time 0.00
Received By shill Date 2006-02-16 Time 13:40 Sent To  
Notes
2006-02-16 00:00:00FIREPROOFING SUBMITTAL.ADVISED
 CONTRACTOR THAT COPIES ARE TO BE
 PROVIDED AND SUBMITTED FOR THE OTHER TWO
 BUILDINGS, PERMITS 04110183, 04110185.

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status F Date 2006-02-08 Cont ID  
Sent By shill Date 2006-02-08 Time 15:57 Rev Time 0.00
Received By shill Date 2006-02-08 Time 15:57 Sent To  
Notes
2006-02-08 00:00:00****CORRECTIONS****
  
 SHORING COMPLIANCE LETTER, LEVEL 4
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)SEE ATTACHED FROM THE FLORIDA
 NOTARY HANDBOOK.FS117(3)(A), NEARLY
 ALL OF THE REQUIRED INFORMATION (FOR A
 NOTARIZED SIGNATURE) IS LACKING FROM THE
 CONTRACTOR SHORING COMPLIANCE
 CERTIFICATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status F Date 2006-01-26 Cont ID  
Sent By shill Date 2006-01-26 Time 12:05 Rev Time 0.00
Received By shill Date 2006-01-26 Time 12:05 Sent To  
Notes
2006-01-26 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 WINDOW SHOPS
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)THIS WAS SUBMITTED AS SHOP
 DRAWINGS.THE PRODUCTS YOU ARE USING
 ARE NOT THE SAME PRODUCTS AS THE
 APPROVED PERMIT PACKAGE.THIS IS A
 REVISION, REQUIRING REVIEW.A REVISION
 FEE HAS BEEN ADDED.WHEN RESUBMITTING,
 PLEASE SUBMIT AS A REVISION.
  
 2.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED, FAC9B72, SB442.
  
 3.)EXPIRED NOAS SUBMITTED.PLEASE
 NOTE THAT THE EXPIRED NOAS BY THEMSELVES
 CANNOT BE USED TO SHOW CODE COMPLIANCE
 IF APPLYING FOR LOCAL PRODUCT APPROVAL.
  
 4.)FBC1601.2.1, THERE IS NO PROVISION
 IN THE CODE FOR A 1% WIND OVERSTRESS AS
 SHOWN FOR THE SMALL MISSILE IMPACT
 SINGLE HUNG WINDOWS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2006-01-20 Cont ID  
Sent By shill Date 2006-01-20 Time 15:06 Rev Time 0.00
Received By shill Date 2006-01-20 Time 15:06 Sent To  
Notes
2006-01-20 00:00:00SHORING/RESHORE, ROOF LEVEL

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2006-01-17 Cont ID  
Sent By shill Date 2006-01-17 Time 11:02 Rev Time 0.00
Received By shill Date 2006-01-17 Time 11:02 Sent To  
Notes
2006-01-17 00:00:00SHORING/RESHORE LETTERS, 3RD/2ND FLOORS

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status F Date 2006-01-17 Cont ID  
Sent By shill Date 2006-01-17 Time 10:54 Rev Time 0.00
Received By shill Date 2006-01-17 Time 10:54 Sent To  
Notes
2006-01-17 00:00:00****CORRECTIONS****
 TRUSS ENGINEERING
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)ORIGINAL SIGNATURES REQUIRED FOR
 THE ENGINEER AS PER FBPE.
  
 2.)PROVIDE A TITLE BLOCK AND SEAL FOR
 THE TRUSS PLACEMENT DRAWING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2005-12-16 Cont ID  
Sent By shill Date 2005-12-16 Time 13:53 Rev Time 0.50
Received By shill Date 2005-12-16 Time 13:53 Sent To  
Notes
2005-12-16 00:00:00****CORRECTIONS****
  
 SUBMITTALS; TENDON AND SUPPORT SHOPS AND
 CALCS
  
 BLDG 4, LEVELS 2, 3, 4, & ROOF
 BLDG 5, 3RD & 4TH FLOOR
 BLDG 5 ROOF
 BLDG 5 LEVEL 2
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A TITLE BLOCK IS REQUIRED,
 FAC61G15-23.003.MR. HAMID'S ADDRESS ON
 DBPE WEBSITE IS NOT THE ADDRESS ON THE
 PLAN, WHICH APPEARS TO BE FOR PTE.IF
 PTE IS PRACTICING ENGINEERING AND MR.
 HAMID IS THE INDIVIDUAL WHO IS SEALING
 THE DOCUMENT THROUGH THE COMPANY, THE
 INFORMATION FOR PTE SERVES AS THE TITLE
 BLOCK AND IS REQUIRED TO HAVE THE
 CERTIFICATE OF AUTHORIZATION FOR THE
 FIRM PRINTED ON THE PLAN.IF MR. HAMID
 IS SEALING THE PLAN INDIVIDUALLY, HIS
 TITLE BLOCK WITH ALL INFORMATION
 REQUIRED BY FAC61G15-23.002 IS REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2005-12-16 Cont ID  
Sent By shill Date 2005-12-16 Time 13:01 Rev Time 0.00
Received By shill Date 2005-12-16 Time 13:01 Sent To  
Notes
2005-12-16 00:00:00SUBMITTALS -
  
 RESHORE PLAN, BLDG 4, 2ND, 3RD, 4TH
 LEVELS PREPARED BY DANSCO ENGINEERING
 SHORING PLAN, BLDG 4 LEVEL 2
 RESHORE PLAN, BLDG 5, LEVELS 2,3,4
 SHORING PLAN, BLDG 5, LEVELS 2,3,4,ROOF
  
 BLDG 4 ELEVATION CERTIFICATE
 BLDG 5 ELEVATION CERTIFICATE
  
 SHORING INSPECTION LETTERS
 BLDG 5, 2ND FLOOR
 BLDG 4, 3RD FL SHORING, 2ND FL RESHORE
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2005-10-14 Cont ID  
Sent By hpiskura Date 2005-10-14 Time 08:39 Rev Time 0.00
Received By hpiskura Date 2005-10-14 Time 08:38 Sent To PC
Notes
2005-10-14 00:00:00SHORING LETTER FROM ENGINEER MUST STATE
 THAT THE INSPECTIONS ARE PERFORMED BY
 THE PE AND NOT THE FIRM.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-08-28 Cont ID  
Sent By jwitmer Date 2005-08-28 Time 10:15 Rev Time 0.44
Received By jwitmer Date 2005-08-28 Time 10:15 Sent To PC
Notes
2005-08-28 00:00:00SUBMITTALS 08-28-05
 FORM BOARD SURVEY BLDG# 4/5
 FLOOR ELEVATION CERTIFICATE BLDG# 4

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-06-16 Cont ID  
Sent By jwitmer Date 2005-06-16 Time 11:43 Rev Time 0.55
Received By jwitmer Date 2005-06-16 Time 11:43 Sent To PC
Notes
2005-06-16 00:00:0006-16-05 FORM BOARD SURVEY BLDG# 4JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-05-24 Cont ID  
Sent By jwitmer Date 2005-05-24 Time 12:13 Rev Time 0.00
Received By jwitmer Date 2005-05-24 Time 12:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-02-11 Cont ID  
Sent By jwitmer Date 2005-02-11 Time 15:30 Rev Time 2.22
Received By jwitmer Date 2005-02-11 Time 15:30 Sent To  
Notes
2005-02-11 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04110182
 ADD: 3900 N FLAGLER BLDG 4/5
 CONT:MANHATTEN
 TEL: (561)719-3539
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 BLDG COMMENTS FROM BUILDING #1 ARE
 COMMON TO ALL BUILDINGS.
 THREE (3) SETS OF PRODUCT APPROVAL ARE
 REQUIRED FOR THIS PROJECT.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-12-07 Cont ID  
Sent By jwitmer Date 2004-12-07 Time 15:55 Rev Time 10.00
Received By jwitmer Date 2004-12-07 Time 15:55 Sent To  
Notes
2004-12-13 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04110182
 ADD: 3900 N FLAGLER BLDG 4&5
 CONT: MANHATTEN
 TEL: (813)927-0209
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
  
 SAME COMMENTS AS FOR BLDG 3&6 SEE
 COMMENTS LISTED UNDER 04110185
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
 BUILDING PLAN REVIEW
 PERMIT: 04120431
 ADD: 333 EVERNIA ST
 CONT: SCHNELL CONTRACTORS
 TEL: (941)321-1915
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1) FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 SRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL INSPEC
 TION PLAN PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGEN-
 CY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESH-
 OLD BUILDING. THE PURPOSE OF THE SRUCTUR
 AL INSPECTION PLAN IS TO PROVIDE SPECIF-
 IC INSPECTION PROCEDURES AND SCHEDULES
 SO THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 2) WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 3)W.P.B. AMENDMENT 105.13.4.4 ALL
 PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CON-
 TAIN A STATEMENT THAT, TO THE BEST OF
 THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE,
 THE PLANS AND SPECIFICATIONS COMPLY WITH
 THE APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 4) FIRE DISTRICT THERE SHALL BE NO TYPE
 VI CONSTRUCTION IN THE FIRE DISTRICT.
  
 5) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PROVIDE WHAT MINIMUM BLDG DESIGN?
  
 6) INDICATE CODE COMPLIANCE WITH 2603.6
 EFIS SYSTEMS.
  
 7) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EFIS SYSTEMS
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 8) PROVIDE POSITIVE AND NEGATIVE
 PRESSURE ZONES FOR BUILDING 1606.2B.
  
 9) FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 10) THE PREMANUFACTURED ATTENDANT BOOTH
 IS CONSIDERED A MANUFACTURED BLDG,
 PROVIDE STATE APPROVED PLANS FROMTHE
 DEPARTMENT OF COMMUNITY AFFAIRS LISTING
  
 THIS STRUCTURE IS APPROVED FOR THIS WIND
 ZONE. 140 MPH / 3 SECOND GUST.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 15 Status P Date 2007-02-26 Cont ID  
Sent By jleahy Date 2007-02-26 Time 16:26 Rev Time 1.00
Received By jleahy Date 2007-02-26 Time 16:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 14 Status P Date 2007-02-12 Cont ID  
Sent By jleahy Date 2007-02-10 Time 16:22 Rev Time 1.00
Received By jleahy Date 2007-02-10 Time 16:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 13 Status P Date 2006-12-22 Cont ID  
Sent By jleahy Date 2006-12-22 Time 06:41 Rev Time 0.45
Received By jleahy Date 2006-12-22 Time 06:41 Sent To  
Notes
2006-12-22 06:41:49PAGES E-207, E-503

Review Stop E ELECTRICAL
Rev No 12 Status P Date 2006-12-07 Cont ID  
Sent By jleahy Date 2006-12-07 Time 06:26 Rev Time 1.00
Received By jleahy Date 2006-12-07 Time 06:25 Sent To  
Notes
2006-12-07 06:27:36INSTALL BATH LIGHTS PER 210.70A BEFORE FINAL
 INSPECTION.
  
 JUNCTION BOX IS NOT ALLOWED IN BATHROOM OR KITCHEN,
 MUST HAVE FIXTURE.

Review Stop E ELECTRICAL
Rev No 11 Status P Date 2006-12-07 Cont ID  
Sent By jleahy Date 2006-12-07 Time 06:37 Rev Time 1.00
Received By jleahy Date 2006-12-07 Time 06:36 Sent To  
Notes
2006-12-06 14:10:11E207

Review Stop E ELECTRICAL
Rev No 10 Status P Date 2006-10-31 Cont ID  
Sent By jleahy Date 2006-10-31 Time 16:18 Rev Time 1.00
Received By jleahy Date 2006-10-31 Time 16:15 Sent To  
Notes
2006-10-31 16:17:37NEED SIZE OF CONTROLLERS NOT SHOWN ON DRAWINGS, E503
2006-10-20 07:10:21ELECTRICAL RISER/ REVISIONS GIVEN TO JAKE LEAHY FOR
 REVIEW.

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2006-06-24 Cont ID  
Sent By dpalmer Date 2006-06-24 Time 09:59 Rev Time 0.00
Received By dpalmer Date 2006-06-24 Time 09:53 Sent To FIRE
Notes
2006-06-24 00:00:00REV FOR UNIT LAYOUT, REV #5.
 ROUTED TO FIRE.

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2006-06-16 Cont ID  
Sent By dpalmer Date 2006-06-16 Time 20:16 Rev Time 0.00
Received By dpalmer Date 2006-06-16 Time 20:16 Sent To FIRE
Notes
2006-06-16 00:00:00REV FOR LAYOUT OF UNITS ONLY.
 ROUTED TO FIRE.

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2006-05-17 Cont ID  
Sent By dpalmer Date 2006-05-17 Time 12:29 Rev Time 0.00
Received By dpalmer Date 2006-05-17 Time 06:54 Sent To  
Notes
2006-05-17 00:00:00******** UNSAT *********
  
  
 1) NOTE: PLEASE SEE COMMENTS FROM
 PREVIOUS REVIEW AS THE SD'S ARE STILL
 SHOWN BEING WIRED TO MORE THAN ONE
 CIRCUIT IN A SINGLE UNIT??
 PLEASE KNOW, THE SD'S ARE REQUIRED TO
 WIRED "INLINE", WHICH AS SHOWN ON
 MULTIPLE CIRCUITS IS NOT PERMITTED.
 THESE MAY BE WIRED TO THE ARC FAULT
 PROTECTED BEDRM CIRCUIT, HOWEVEER THESE
 CAN ONLY BE ON ONE CIRCUIT.
 NFPA-72 8-1.4.1.6.2,
  
 2) NOTE: PLEASE SEE SEC'S HAVE NOW BEEN
 DOWN SIZED TO 3/0'S FOR ONE FIRE PUMP
 SERVICE, AND 4/0'S FOR THE OTHER.
 PLEASE SEE THAT THE SEC'S SHALL ME SIZED
 ACCORDINGLY TO THE OCP, HP, AND THE SIZE
 OF THE FPC.
 PLEASE SEE 310.16, AS 3/0'S ARE ONLY
 RATED AT 200A'S AND THE 4/0'S ARE ONLY
 RATED FOR 225A'S. PLEASE SEE
 240.4,310.16.
 THE OCP SHOWN ON MAIN IS 250A'S.
 (LOOCKED ROTOR SHOULD BE SET AND PART OF
 THE FPC AND MUST BE 6X THE FLA'S.
 695.4/695.5
  
 ** NOTE **
 PLEASE KNOW, IT HAS COME TO THE
 ATTENTION OF THIS OFFICE THAT SOME OF
 THE SLIDING GLASS DOORS ON PLANS ARE
 ACTUALLY "FIXED GLASS PANELS" PLEASE SEE
 210.52 AS "FIXED GLASS" IS CONSIDERED
 WALL SPACE.
 PLEASE SEE PLANS IN MANY PLACES STILL
 INDICATE MANY OF THESE AS SLIDING GLASS
 DOORS?? AS REVIEWED ON PREVIOUS PLANS.
 ANY INSTALLATION OF FIXED GLASS PANELS,
 WILL BE VERIFIED IN THE FIELD AND PLANS
 SHALL BE REVISED ACCORDING TO ACTUAL
 WALL SPACE CONSTRUCTED.
  
  
 PLEASE REVISE AND SUBMIT THE ABOVE
 INFORMATION FOR REVIEW. IF THERE ARE ANY
 QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status N Date 2006-01-23 Cont ID  
Sent By dpalmer Date 2006-01-23 Time 15:07 Rev Time 0.00
Received By dpalmer Date 2006-01-23 Time 15:06 Sent To M
Notes
2006-01-23 00:00:00SUBMITTIAL FOR DRY-IN OF BLDG,NOT FOR
 ELEC REVIEW.

Review Stop E ELECTRICAL
Rev No 5 Status N Date 2005-12-30 Cont ID  
Sent By dpalmer Date 2005-12-30 Time 15:07 Rev Time 0.00
Received By dpalmer Date 2005-12-30 Time 15:07 Sent To M
Notes
2005-12-30 00:00:00APPLIANCE SUBMITTIALS NOT NEED FOR
 REVIEW.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-12-09 Cont ID  
Sent By dpalmer Date 2005-12-09 Time 14:43 Rev Time 0.00
Received By dpalmer Date 2005-12-09 Time 13:17 Sent To  
Notes
2005-12-09 00:00:00****** UNSAT *******
  
 1)NOTE: PLEASE SEE NOTE ON ALL PLANS
 INDICATE SD'S ARE TO BE WIRED TO
 HALL/FOYER CIRCUITS, HOWEVER CIRCUITING
 ON PLANS WAS NOT CHANGED.
 PLEASE BE SURE THAT IF THESE SD'S ARE
 NOW GOING TO CHANGE TO HALL/FOYER LTS,
 THEN THESE CIRCUITS WILL ALSO NOW BE
 REQUIRED TO BE ARC FAULT.210.12
 PLEASE ALSO SEE CIRCUITING FOR SD'S HAS
 GONE BACK TO THE SD'S OF THE SAME UNIT
 BEING WIRED TO MORE THAN ONE CIRCUIT.
 SMOKE DETECTORS ARE REQUIRED TO BE WIRED
 INLINE AND THIS WILL NOT WORK ON MORE
 THAN ONE CIRCUIT.
 PLEASE ADJUST ALL CIRCUITING.
  
 2)NOTE: PLEASE SEE FIRE PUMP
 FEEDERS/SEC'S FROM THE FPL TRANSFORMER
 TO THE METER AND FROM THE METER TO THE
 FIRST MEANS OF DISCONNECT IS NOTED AS
 HAVING AN EQUIPMENT GROUNDING CONDUCTOR.
 PLEASE REVISE SCHEDULE.
 THESE ARE ONLY INSTALLED AFTER THE FIRST
 MEANS OF DISCONNECT.
  
 3)NOTE: PLEASE SEE 302 WHICH DOES NOT
 INDICATE ANY REVISONS, HOWEVER TITLE
 BLOCK DOES INDICATE THIS.
  
 4)NOTE: PLEASE SEE 620.23 A SEPARATE
 BRANCH CIRCUIT SHALL SUPPLY THE MACHINE
 ROOM OR CONTROL ROOM/MACHINERY SPACE OR
 CONTROL SPACE LIGHTING AND
 RECEPTACLE(S).
  
 PLEASE MAKE THE ABOVE CORRECTIONS AND
 SUBMIT FOR REVIEW. IF THERE ARE ANY
 QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-04-25 Cont ID  
Sent By dpalmer Date 2005-04-25 Time 18:19 Rev Time 4.00
Received By dpalmer Date 2005-04-25 Time 15:41 Sent To  
Notes
2005-04-25 00:00:00**REDLINED **
  
 1) NO EQUIPMENT GROUNDING CONDUCTORS
 FROM TRANSFORMER TO METER OR METER TO
 FIRST MEANS OF DISCONNECT.
 250.6,250.24
 EQUIPMENT GROUNDING CONDUCTORS SHOWN TO
 FIRE PUMP SHALL NOT BE INSTALLED.
  
 ALL 12 ROLLS STAMPED FOR ELECTRICAL.
 NO REVISION NEEDED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-02-14 Cont ID  
Sent By dpalmer Date 2005-02-14 Time 09:32 Rev Time  
Received By dpalmer Date 2005-02-14 Time 09:29 Sent To  
Notes
2005-02-14 00:00:00*** NOTES ***
 THIS IS FOR BLDGS: 1,2,5 AND 6.
 THIS COMMENT DOES NOT AFFECT BLDGS: 3 OR
 4.
  
 1)NOTE:PLEASE SEE NFPA-20 IN REFERENCE
 TO FIRE PUMP ELECTRICAL SERVICE
 LOCATION.
 PLEASE SEE SERVICE SHALL BE LOCATED AS
 NOT TO BE AFFECTED IN CASE OF FIRE /
 EXPLOSION ETC WITH MAIN ELECTRICAL
 SERVICE.
 THIS FIRE PUMP SERVICE SHOULD STILL BE
 LOCATED IN CLOSE PROXIMITY TO MAIN
 ELECTRICAL RM.
 PLEASE SEE NFPA-20, 6.2.1
 6-2.1 SERVICE.
 WHERE POWER IS SUPPLIED BY A SERVICE, IT
 SHALL BE LOCATED AND ARRANGED TO
 MINIMIZE THE POSSIBILITY OF DAMAGE BY
 FIRE FROM WITHIN THE PREMISES AND
 EXPOSING HAZARDS.
 NFPA-70 695
 THE CONNECTION SHALL BE LOCATED AND
 ARRANGED SO AS TO MINIMIZE THE
 POSSIBILITY OF DAMAGE BY FIRE FROM
 WITHIN THE PREMISES AND FROM EXPOSING
 HAZARDS.
 MOST IMPORTANT IN 695.3(A)(2) IS THE
 REQUIREMENT THAT A FIRE IN ONE SOURCE
 NOT AFFECT THE RELIABILITY OF ANOTHER
 SOURCE.
  
 THIS WAS NOT IN ORIGINAL REVIEW NOTES.
  
 PLEASE MAKE THE ABOVE CHANGES AND SUBMIT
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CONTACTING.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-12-01 Cont ID  
Sent By dpalmer Date 2004-12-01 Time 07:18 Rev Time 10.00
Received By dpalmer Date 2004-11-23 Time 15:40 Sent To  
Notes
2004-12-07 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04110183
 ADD: 3900 N FLAGLER BLDG# 1
 CONT: MANHATTEN CONSTRUCTION
 TEL: (813)927-0209
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)THE FINISHED FLOOR LEVEL SHALL BE
 VERIFIED BY A SIGNED AND SEALED
 ELEVATION CERTIFICATE. LOCATED IN A
 FLOOD ZONE, THE MINIMUM FINISH FLOOR
 ELEVATION IN A A5 FLOOD ZONE IS7'-6".
  
 3) 105.3** THE BUILDING OFICIAL MAY MAKE
 OR CAUSE TO HAVE A SPECIAL INSPECTOR
 PRESENT AT ALL TIMES THAT WORK IS IN
 PROGRESS FOR STRUCTURAL COMPONENTS.
  
  
 4) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 5) STRUCTURAL PLANS INDICATE THAT A
 SOILS REPORT SHALL REQUIRE 16" AUGER
 PILE, THE GEOTECHNICAL ENGINEER SHALL
 SUBMIT TO THE DESIGNER OF RECORD FOR
 REVIEW ALL DOCUMENTS BEFORE SUBMITING
 TO THE CITY.
  
 6) ENCLOSED PARKING GARAGE, 411.4.2.
 TO PROVIDE 6 AIR CHANGES PER HR. UNDER
 NORMAL USE THE VENTILATION OFTHE AUTO
 MOBILE PARKING GARAGE SHALL COMPLY WITH
  
 THE VENTILATION REQUIREMENTS FOR 411.5.
  
 THIS REVIEW WILL CONTINUE WED 12-08-04JW
2004-12-01 00:00:00************ UNSAT ******************
  
 THE FOLLOWING NOTES FOR 3900 N. FLAGLER
 BLUILDINGS 1-6
 04110182,
 04110183,
 04110184,
 04110185
 PLEASE SEE MANY OF THE FOLLOWING
 COMMENTS ARE TYPICAL FOR EACH BLDG.
  
  
 1)NOTE: PLEASE SEE BLDG REVIEW
 COMMENTS:
 EACH BLDG TO BE UNDER SEPARATE PERMITS.
 MULTIPLE BLDGS UNDER ONE PERMIT MAY
 CREATE ISSUES WITH INSPECTIONS AND
 C.O.'S.
  
 2)NOTE: PLEASE SEE FAC 61G1-16.004, FAC
 61G15-23.002 FOR ALL REQUIRED
 INFORMATION ON TITLE BLOCKS.
 CERTIFICATE
 OF AUTHORIZATION #'S PER FS
 481.219,471.023.
 THIS IS FOR ALL SHEETS AND FOR ALL
 TRADES WHEATHER OR NOT COMMENT IS MADE
 BY OTHER REVIEWER(S).
  
 3)NOTE: PLEASE PROVIDE ROOM
 DESIGNATIONS
 ON PLANS.
  
 4)NOTE: PLEASE SEE 210.52 FOR RECEPT
 SPACING IN DWELLING UNITS. PLEASE SEE
 2'
 OF WALL SPACE, W/IN 6' OF DOOR ETC.
 PLEASE SEE MANY OF THESE AREAS ARE
 REDLINED ON ONE OF THE SETS OF PLANS
 TURNED IN.
  
 5)NOTE: PLEASE SEE 210.52H FOR MISSING
 HALLWAY RECEPT.
  
 6)NOTE: PLEASE SEE 110.26 FOR SPACING
 ABOUT ELECTRICAL EQUIPMENT.
 WORKING SPACE FOR EQUIPMENT OPERATING
 AT
 600 VOLTS, NOMINAL, OR LESS TO GROUND
 AND LIKELY TO REQUIRE EXAMINATION,
 ADJUSTMENT, SERVICING, OR MAINTENANCE
 WHILE ENERGIZED SHALL COMPLY WITH THE
 DIMENSIONS OF 110.26(A)(1), (2), AND
 (3)
 OR AS REQUIRED OR PERMITTED ELSEWHERE
 IN
 THIS CODE PLEASE SEE SOME UNITS APPEAR
 TO HAVE ROOMS TOO SMALL AND/OR ITEMS
 LIKE APPLIANCES IN REQUIRED SPACE.
  
 7)NOTE: PLEASE SEE 210.8A6, ALL RECEPTS
 IN KITCHENS SERVING KITCHEN
 COUNTERSPACE
 ARE REQUIRED TO BE GFI/GFI PROTECTED.
 PLEASE INDICATE.
 PLEASE SEE SYMBOL LEGEND: SOME OF THESE
 RECEPTS AS SHOWN ON PLANS IN KITCHENS
 DO
 NOT APPEAR TO BE ON LEGEND?
 THIS SAME SYMBOL SHOWN FOR BATH
 RECETPS.
  
 THIS IS "ASSUMED" TO BE A "GFI".
  
 8)NOTE: PLEASE SEE SMOKE DETECTORS IN
 UNITS: THESE ARE REQUIRED TO BE WIRED
 "IN-LINE" , YET SD'S ARE SHOWN ON
 MULTIPLE CIRCUITS, SOME AS MANY AS 5
 CIRCUITS IN SOME UNITS.?
 THIS WOULD NOT WORK AS SHOWN.
  
  
 9)NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
 20A #12
  
 10)NOTE: PLEASE SEE FIXTURE TYPE "J" AS
 SHOWN ON LEGEND FOR CLOSETS.
 PLEASE SEE 410.8, SOME OF THESE DO NOT
 SEEM TO MEET CLEARENCE REQUIREMNTS.
 THE VOLUME BOUNDED BY THE SIDES AND
 BACK
 CLOSET WALLS AND PLANES EXTENDING FROM
 THE CLOSET FLOOR VERTICALLY TO A HEIGHT
 OF 1.8 M (6 FT) OR THE HIGHEST
 CLOTHES-HANGING ROD AND PARALLEL TO THE
 WALLS AT A HORIZONTAL DISTANCE OF 600
 MM
 (24 IN.) FROM THE SIDES AND BACK OF THE
 CLOSET WALLS, RESPECTIVELY, AND
 CONTINUING VERTICALLY TO THE CLOSET
 CEILING PARALLEL TO THE WALLS AT A
 HORIZONTAL DISTANCE OF 300 MM (12 IN.)
 OR THE WIDTH OF THE SHELF, WHICHEVER IS
 GREATER; FOR A CLOSET THAT PERMITS
 ACCESS TO BOTH SIDES OF A HANGING ROD,
 THIS SPACE INCLUDES THE VOLUME BELOW
 THE
 HIGHEST ROD EXTENDING 300 MM (12 IN.)
 ON
 EITHER SIDE OF THE ROD ON A PLANE
 HORIZONTAL TO THE FLOOR EXTENDING THE
 ENTIRE LENGTH OF THE ROD.
 PLEASE SEE SOME UNIT'S CLOSETS ARE MUCH
 SMALLER THAN OTHERS.
  
 11)NOTE: PLEASE SEE NFPA-72 8-1.4.2 FOR
 SD PLACEMENTS AND CLEARENCES FROM BATH
 DRS, KITCHEN DRS AND COOKING
 APPLIANCES.
 PLEASE ALSO SEE EXCEPTIONS.
 PLEASE PLACE NOTE ON PLANS FOR ABOVE.
  
 12)NOTE:PLEASE SEE "DINING ROOM" RECEPT
 REQUIREMENTS FOR CIRCUITING.
 PLEASE SEE THESE RECEPTS MUST BE ON A
 20A SM APPL CIRCUIT, 2 OR MORE.
 SOME SHOWN ON LIGHTINGCIRCUIT(S)?
  
 13)NOTE: PLEASE SEE UNIT H-5, BEDRM
 SHOWN W/OUT DOORS? OPEN TO KITCHEN AND
 LIVING ROOM AREA??
  
 14)NOTE: PLEASE VERIFY LOADS FOR A/C,
 AHU'S. PLEASE SEE LOAD CALCULATIONS
 INDICATE SOME AT 15KW AND OTHERS AT
 12KW
 ARE THESE SPLIT? AND IF SO PLEASE
 INDICATE LOAD ON INDIVIDUAL UNITS IN
 ORDER TO VERIFY OCP, AWG PER
 424.3B,310.16.
  
 15)NOTE: PLEASE SEE 694.4B(1)
 OVERCURRENT DEVICE SELECTION.
 THE OVERCURRENT PROTECTIVE DEVICE(S)
 SHALL BE SELECTED OR SET TO CARRY
 INDEFINITELY THE SUM OF THE
 LOCKED-ROTOR
 CURRENT OF THE FIRE PUMP MOTOR(S) AND
 THE PRESSURE MAINTENANCE PUMP MOTOR(S)
 AND THE FULL-LOAD CURRENT OF THE
 ASSOCIATED FIRE PUMP ACCESSORY
 EQUIPMENT
 WHEN CONNECTED TO THIS POWER SUPPLY.
 PLEASE VERIFY METHOD OF OVERCURRENT
 PROTECTION. PLEASE VERIFY IF OCP IS
 PROVIDED IN FIRE PUMP CONTROLLER OR
 DISCONNECT?
 TWO MEANS OF OCP ID NOT PERMITTED.
 PLEASE SUBMIT COMPLETE MANUFACTURE
 SPECS
 FOR FIRE PUMP, AND FIRE PUMP
 CONTROLLER.
  
 16)NOTE: PLEASE SEE 220.16 SMALL
 APPLIANCE AND LAUNDRY LOADS ? DWELLING
 UNIT.
 PLEASE INDICATE THE SMALL APPL CIRCUITS
 ON PANEL SCHEDULE.
 SMALL APPLIANCE CIRCUIT LOAD IN EACH
 DWELLING UNITSHALL BE COMPUTED AT
 1500
 VOLT-AMPERES FOR EACH 2-WIRE
 SMALL-APPLIANCE BRANCH CIRCUIT REQUIRED
 BY 210.11(C)(1).
  
 17)NOTE: PLEASE VERIFY LOCATIONS OF
 "SHUNT-TRIP" PUSHBUTTONS ON PLANS?
 PLEASE VERFIY IF MAINS IN METER BANKS
 CONTAIN DISCONNECTION MEANS PER
 230.76,230.79?
 THE SERVICE DISCONNECTING MEANS FOR
 UNGROUNDED SERVICE CONDUCTORS SHALL
 CONSIST OF EITHER (1) A MANUALLY
 OPERABLE SWITCH OR CIRCUIT BREAKER
 EQUIPPED WITH A HANDLE OR OTHER
 SUITABLE
 OPERATING MEANS OR (2) A POWER-OPERATED
 SWITCH OR CIRCUIT BREAKER, PROVIDED THE
 SWITCH OR CIRCUIT BREAKER CAN BE OPENED
 BY HAND IN THE EVENT OF A POWER SUPPLY
 FAILURE.
 THE SERVICE DISCONNECTING MEANS SHALL
 HAVE A RATING NOT LESS THAN THE LOAD TO
 BE CARRIED, DETERMINED IN ACCORDANCE
 WITH ARTICLE 220. IN NO CASE SHALL THE
 RATING BE LOWER THAN SPECIFIED IN
 230.79(A), (B), (C), OR (D).
  
 18)NOTE: PLEASE SEE 250.104
 THIS NOTE IS FOR ANY POSSIBLE "METAL"
 FIRE SPRINLER PIPE(S).
 THE METAL WATER PIPING SYSTEM SHALL BE
 BONDED AS REQUIRED IN (1), (2), (3), OR
 (4) OF THIS SECTION. THE BONDING
 JUMPER(S) SHALL BE INSTALLED IN
 ACCORDANCE WITH 250.64(A), (B), AND
 (E).
 THE POINTS OF ATTACHMENT OF THE BONDING
 JUMPER(S) SHALL BE ACCESSIBLE.
 METAL WATER PIPING SYSTEM(S) INSTALLED
 IN OR ATTACHED TO A BUILDING OR
 STRUCTURE SHALL BE BONDED TO THE
 SERVICE
 EQUIPMENT ENCLOSURE, THE GROUNDED
 CONDUCTOR AT THE SERVICE, THE GROUNDING
 ELECTRODE CONDUCTOR WHERE OF SUFFICIENT
 SIZE, OR TO THE ONE OR MORE GROUNDING
 ELECTRODES USED. THE BONDING JUMPER(S)
 SHALL BE SIZED IN ACCORDANCE WITH TABLE
 250.66 EXCEPT AS PERMITTED IN
 250.104(A)(2) AND (A)(3).
  
 19)NOTE: PLEASE SEE FPL REQUIREMENST
 FOR
 ELECTRICAL SERVICE INSTALLATIONS.
 METERING EQUIPMENT "INDOORS" MAY BE A
 MAX OF 72"/6' AND A MIN OF 22" ABOVE
 FLR
 TO THE CENTELINE OF THE METER.
 PLEASE SEE RISER DIAGRAM APPEARS TO
 SHOW
  
 METER CENTERS ON THE FLOORS.
  
 20)NOTE: PLEASE SEE 250.106 LIGHTNING
 PROTECTION SYSTEMS.
 THE LIGHTNING PROTECTION SYSTEM GROUND
 TERMINALS SHALL BE BONDED TO THE
 BUILDING OR STRUCTURE GROUNDING.
 ELECTRODE SYSTEM.
 PLEASE SEE IF ANY SYSTEM(S) ARE
 INSTALLED THEN THEY MUST MEET NFPA-780
  
 21)NOTE: PLEASE GIVE INDICATION OF THE
 ARC FAULT PROTECTION PER 2002 NEC
 210.12, WHICH REQUIRES PROTECTION FOR
 ALL "OUTLETS", SD'S LTS, RECEPTS, FANS
 ETC.
 IT IS NOTED ON PANEL SCHEDULES ABOUT
 ARC
 FAULT PROTECTION, HOWEVER PLEASE ADD TO
 TO THE EXISTING NOTE.
  
 22)NOTE: PLEASE SEE FIRE REVIEW, PLEASE
 SEE THAT A "KNOX-BOX" WILL BE REQUIRED
 FOR EACH BLDG.
 PLEASE SEE FIRE FOR SPECIFICS.
  
 23)NOTE: PLEASE REMOVE ALL OLD/VOIDED
 SHEETS FROM SETS AND ONLY INSERT NEW
 REVISED SHEETS INTO THREE COMPLETE SETS
  
 FOR REVIEW AND STAMPING.
  
 24)NOTE: PLEASE SEE ANY POSSIBLE
 COMMENTS FROM OTHER REVIEWER(S) WHICH
 MAY AFFECT ELECTRICAL PLANS.
  
  
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
2004-11-30 00:00:00IN ELECTRICAL FOR REVIEW,NOTES WILL
 FOLLOW.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status N Date 2005-02-23 Cont ID  
Sent By mamini Date 2005-02-23 Time 11:15 Rev Time 0.00
Received By mamini Date 2005-02-23 Time 11:15 Sent To  
Notes
2005-02-23 00:00:00N:
  
 1. SEE PERMIT# 05021226 FOR
 UNDERGROUND UTILITIES AND SITE WORK.
 THIS PERMIT INCLUDES BUILDING PADS
 PREPARATION FOR ALL BUILDINGS.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2004-11-15 Cont ID  
Sent By mamini Date 2004-11-15 Time 16:18 Rev Time 0.00
Received By mamini Date 2004-11-15 Time 16:18 Sent To  
Notes
2004-11-15 00:00:00PASSED WITH PROVISOS:
  
 1. EROSION AND SEDIMENTATION CONTROL
 DEVICES SHALL BE IN PLACE PRIOR TO
 BEGINNING CLEARING OR GRUBBING,
 DEMOLITION, OR OTHER SUCH CONSTRUCTION
 ACTIVITIES.THE DEVICES SHALL BE
 INSTALLED, MONITORED, AND MAINTAINED IN
 ACCORDANCE WITH ALL APPLICABLE FEDERAL,
 STATE, AND LOCAL REQUIREMENTS.
  
 2. WORK WITHIN PUBLIC R.O.W REQUIRES A
 PERMIT FROM PUBLIC UTILITIES AND
 ENGINEERING, PLEASE SUBMIT M.O.T PLANS
 ALSO AT THE TIME OF APPLICATION ATT:
 WINDEL PALMER, 494-1086.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 8 Status P Date 2006-07-21 Cont ID  
Sent By mwennerg Date 2006-07-21 Time 10:19 Rev Time 0.00
Received By mwennerg Date 2006-07-21 Time 10:19 Sent To  
Notes
2006-07-21 00:00:00REVISION DATED 6/12/06

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2006-06-29 Cont ID  
Sent By nmccray Date 2006-06-29 Time 13:37 Rev Time 0.00
Received By nmccray Date 2006-06-29 Time 13:34 Sent To  
Notes
2006-06-29 00:00:00REVISION DATED 06-06-06. ROUTED BACK TO
 ELECTRICAL.

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status N Date 2006-06-21 Cont ID  
Sent By mwennerg Date 2006-06-21 Time 10:23 Rev Time 0.00
Received By mwennerg Date 2006-06-21 Time 10:23 Sent To  
Notes
2006-06-21 00:00:00REVISIONS BASED ON PREVIOUS REVIEW
 COMMENTS. NO COMMENTS FROM LAST FIRE
 REVIEW. NO FIRE PROTECTION SHEETS
 SUBMITTED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status N Date 2006-01-26 Cont ID  
Sent By nmccray Date 2006-01-26 Time 12:21 Rev Time 0.00
Received By nmccray Date 2006-01-26 Time 12:20 Sent To I
Notes
2006-01-26 00:00:00FIRE PROOFING AND FIRESTOPPING CUT
 SHEETS PLEASE ROUTE TO BUILDING
 REVIEWER.
  
 THIS PERMIT# 04110182, 04110183,
 04110184, AND 04110185

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2005-12-13 Cont ID  
Sent By nmccray Date 2005-12-13 Time 14:29 Rev Time 0.00
Received By nmccray Date 2005-12-13 Time 14:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-05-17 Cont ID  
Sent By mwennerg Date 2005-05-17 Time 13:04 Rev Time 0.00
Received By mwennerg Date 2005-05-17 Time 13:03 Sent To  
Notes
2005-05-17 00:00:00REVIEW PASSED ON 2/24/05
  
 1) NFPA 13, AND NFPA 14 TO COMPLY WITH
 THE 2002 AND 2003 EDITIONS.
 THE PLANS REFER TO THE 1999 EDITION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-02-24 Cont ID  
Sent By nmccray Date 2005-02-24 Time 15:04 Rev Time 0.00
Received By nmccray Date 2005-02-24 Time 15:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-12-31 Cont ID  
Sent By pkrauss Date 2004-12-31 Time 09:25 Rev Time 0.00
Received By pkrauss Date 2004-12-31 Time 09:25 Sent To  
Notes
2004-12-31 00:00:00SEE COMMENTS ON PERMIT 04110184

Review Stop I INCOMING/PROCESSING
Rev No 50 Status N Date 2007-05-21 Cont ID  
Sent By shill Date 2007-05-21 Time 16:29 Rev Time 0.00
Received By shill Date 2007-05-21 Time 16:29 Sent To B
Notes
2007-05-21 16:30:20TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 49 Status N Date 2007-05-04 Cont ID  
Sent By adarroug Date 2007-05-04 Time 14:53 Rev Time 0.00
Received By adarroug Date 2007-05-04 Time 14:53 Sent To B
Notes
2007-05-04 14:54:06TO "JWITMER' DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 48 Status N Date 2007-04-16 Cont ID  
Sent By adarroug Date 2007-04-16 Time 14:23 Rev Time 0.00
Received By adarroug Date 2007-04-16 Time 14:23 Sent To B
Notes
2007-04-16 14:23:44TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 47 Status N Date 2007-03-15 Cont ID  
Sent By adarroug Date 2007-03-15 Time 13:46 Rev Time 0.00
Received By adarroug Date 2007-03-15 Time 13:46 Sent To B
Notes
2007-03-15 13:50:22TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 46 Status N Date 2007-02-16 Cont ID  
Sent By adarroug Date 2007-02-16 Time 16:04 Rev Time 0.00
Received By adarroug Date 2007-02-16 Time 16:04 Sent To E
Notes
2007-02-16 16:04:51TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 45 Status N Date 2007-02-02 Cont ID  
Sent By adarroug Date 2007-02-02 Time 14:29 Rev Time 0.00
Received By adarroug Date 2007-02-02 Time 14:29 Sent To  
Notes
2007-02-08 11:34:20TO "COMM" BD#43
2007-02-02 14:30:12WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 44 Status N Date 2006-12-18 Cont ID  
Sent By adarroug Date 2006-12-18 Time 10:10 Rev Time 0.00
Received By adarroug Date 2006-12-18 Time 10:10 Sent To E
Notes
2006-12-18 10:10:24TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 43 Status N Date 2006-12-18 Cont ID  
Sent By adarroug Date 2006-12-18 Time 10:07 Rev Time 0.00
Received By adarroug Date 2006-12-18 Time 10:07 Sent To E
Notes
2006-12-18 10:08:06TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 42 Status N Date 2006-12-18 Cont ID  
Sent By adarroug Date 2006-12-18 Time 09:45 Rev Time 0.00
Received By adarroug Date 2006-12-18 Time 09:45 Sent To M
Notes
2006-12-18 09:45:28TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 41 Status N Date 2006-11-29 Cont ID  
Sent By mmiller Date 2006-11-29 Time 17:24 Rev Time 0.00
Received By mmiller Date 2006-11-29 Time 17:24 Sent To E
Notes
2006-11-29 17:24:46SENT TO DEWEY PALMER'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 40 Status N Date 2006-10-10 Cont ID  
Sent By adarroug Date 2006-10-10 Time 17:54 Rev Time 0.00
Received By adarroug Date 2006-10-10 Time 17:54 Sent To E
Notes
2006-10-10 17:55:08TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 39 Status N Date 2006-07-21 Cont ID  
Sent By adarroug Date 2006-07-21 Time 09:09 Rev Time 0.00
Received By adarroug Date 2006-07-21 Time 09:09 Sent To M
Notes
2006-07-21 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 38 Status N Date 2006-07-19 Cont ID  
Sent By adarroug Date 2006-07-19 Time 09:52 Rev Time 0.00
Received By adarroug Date 2006-07-19 Time 09:52 Sent To FIRE
Notes
2006-07-19 00:00:00TO "F" BOX/REV
 7/19/06--CONTRACTOR PULLED PLANS FROM
 REVIEW PROCESS--SEE FRONT SCREEN NOTE.
 ADARROUGH

Review Stop I INCOMING/PROCESSING
Rev No 37 Status N Date 2006-07-03 Cont ID  
Sent By adarroug Date 2006-07-03 Time 15:58 Rev Time 0.00
Received By adarroug Date 2006-07-03 Time 15:58 Sent To M
Notes
2006-07-03 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 36 Status N Date 2006-06-26 Cont ID  
Sent By adarroug Date 2006-06-26 Time 10:27 Rev Time 0.00
Received By pkrauss Date 2006-06-26 Time 10:27 Sent To M
Notes
2006-06-26 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 35 Status N Date 2006-06-19 Cont ID  
Sent By adarroug Date 2006-06-19 Time 15:38 Rev Time 0.00
Received By adarroug Date 2006-06-19 Time 15:38 Sent To E
Notes
2006-06-19 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 34 Status N Date 2006-06-09 Cont ID  
Sent By adarroug Date 2006-06-09 Time 16:13 Rev Time 0.00
Received By adarroug Date 2006-06-09 Time 16:13 Sent To  
Notes
2006-06-23 00:00:00TO "COMM" BD#60
2006-06-09 00:00:00WAITING FOR "COMM" BD--REV

Review Stop I INCOMING/PROCESSING
Rev No 33 Status N Date 2006-06-09 Cont ID  
Sent By adarroug Date 2006-06-09 Time 16:09 Rev Time 0.00
Received By adarroug Date 2006-06-09 Time 16:09 Sent To E
Notes
2006-06-09 00:00:00TO "DPALMER' DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 32 Status N Date 2006-05-02 Cont ID  
Sent By adarroug Date 2006-05-02 Time 12:36 Rev Time 0.00
Received By adarroug Date 2006-05-02 Time 12:36 Sent To B
Notes
2006-05-02 00:00:00TO "JWITMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 31 Status N Date 2006-04-21 Cont ID  
Sent By adarroug Date 2006-04-21 Time 15:02 Rev Time 0.00
Received By adarroug Date 2006-04-21 Time 15:02 Sent To  
Notes
2006-05-11 00:00:00TO "COMM" BD#35
2006-04-21 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 30 Status N Date 2006-04-21 Cont ID  
Sent By adarroug Date 2006-04-21 Time 11:53 Rev Time 0.00
Received By adarroug Date 2006-04-21 Time 11:53 Sent To B
Notes
2006-04-21 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 29 Status N Date 2006-03-02 Cont ID  
Sent By adarroug Date 2006-03-02 Time 14:02 Rev Time 0.00
Received By adarroug Date 2006-03-02 Time 14:02 Sent To B
Notes
2006-03-02 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 28 Status N Date 2006-02-24 Cont ID  
Sent By adarroug Date 2006-02-24 Time 08:21 Rev Time 0.00
Received By adarroug Date 2006-02-24 Time 08:21 Sent To B
Notes
2006-02-24 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 27 Status N Date 2006-01-30 Cont ID  
Sent By adarroug Date 2006-01-30 Time 13:40 Rev Time 0.00
Received By adarroug Date 2006-01-30 Time 13:39 Sent To B
Notes
2006-01-30 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 26 Status N Date 2006-01-26 Cont ID  
Sent By adarroug Date 2006-01-26 Time 13:31 Rev Time 0.00
Received By adarroug Date 2006-01-26 Time 13:31 Sent To B
Notes
2006-01-26 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 25 Status N Date 2006-01-19 Cont ID  
Sent By adarroug Date 2006-01-19 Time 11:15 Rev Time 0.00
Received By adarroug Date 2006-01-19 Time 11:15 Sent To B
Notes
2006-01-19 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 24 Status N Date 2006-01-18 Cont ID  
Sent By adarroug Date 2006-01-18 Time 14:42 Rev Time 0.00
Received By adarroug Date 2006-01-18 Time 14:41 Sent To E
Notes
2006-01-18 00:00:00TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 23 Status N Date   Cont ID  
Sent By   Date 2005-12-30 Time   Rev Time 0.00
Received By adarroug Date 2005-12-29 Time 16:47 Sent To  
Notes
2005-12-29 00:00:00TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 22 Status N Date 2005-12-29 Cont ID  
Sent By adarroug Date 2005-12-29 Time 16:32 Rev Time 0.00
Received By adarroug Date 2005-12-29 Time 16:32 Sent To M
Notes
2005-12-29 00:00:00TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2005-12-29 Cont ID  
Sent By adarroug Date 2005-12-29 Time 16:01 Rev Time 0.00
Received By adarroug Date 2005-12-29 Time 16:01 Sent To FIRE
Notes
2005-12-29 00:00:00TO "F" BOX

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2005-12-29 Cont ID  
Sent By adarroug Date 2005-12-29 Time 15:58 Rev Time 0.00
Received By adarroug Date 2005-12-29 Time 15:58 Sent To B
Notes
2005-12-29 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2005-12-29 Cont ID  
Sent By adarroug Date 2005-12-29 Time 15:53 Rev Time 0.00
Received By adarroug Date 2005-12-29 Time 15:53 Sent To B
Notes
2005-12-29 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2005-12-29 Cont ID  
Sent By adarroug Date 2005-12-29 Time 15:28 Rev Time 0.00
Received By adarroug Date 2005-12-29 Time 15:28 Sent To B
Notes
2005-12-29 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2005-11-30 Cont ID  
Sent By adarroug Date 2005-11-30 Time 17:34 Rev Time 0.00
Received By adarroug Date 2005-11-30 Time 17:33 Sent To B
Notes
2005-11-30 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2005-11-22 Cont ID  
Sent By adarroug Date 2005-11-22 Time 15:46 Rev Time 0.00
Received By adarroug Date 2005-11-22 Time 15:46 Sent To B
Notes
2005-11-22 00:00:00TO "JWITMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2005-10-13 Cont ID  
Sent By adarroug Date 2005-10-13 Time 16:17 Rev Time 0.00
Received By adarroug Date 2005-10-13 Time 16:17 Sent To B
Notes
2005-10-13 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2005-09-26 Cont ID  
Sent By adarroug Date 2005-09-26 Time 18:24 Rev Time 0.00
Received By adarroug Date 2005-09-26 Time 18:24 Sent To B
Notes
2005-09-26 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2005-09-19 Cont ID  
Sent By adarroug Date 2005-09-19 Time 15:31 Rev Time 0.00
Received By adarroug Date 2005-09-19 Time 15:30 Sent To  
Notes
2005-09-22 00:00:00TO "COMM" BD#1/PLANS ON RACK/4 ROLLS
2005-09-19 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2005-09-08 Cont ID  
Sent By adarroug Date 2005-09-08 Time 18:33 Rev Time 0.00
Received By adarroug Date 2005-09-08 Time 18:33 Sent To B
Notes
2005-09-08 00:00:00TO "JWITMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2005-08-19 Cont ID  
Sent By adarroug Date 2005-08-19 Time 08:57 Rev Time 0.00
Received By adarroug Date 2005-08-19 Time 08:57 Sent To B
Notes
2005-08-19 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-08-10 Cont ID  
Sent By adarroug Date 2005-08-10 Time 10:08 Rev Time 0.00
Received By adarroug Date 2005-08-10 Time 10:08 Sent To B
Notes
2005-08-10 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-06-10 Cont ID  
Sent By shill Date 2005-06-10 Time 15:50 Rev Time 0.00
Received By shill Date 2005-06-10 Time 15:50 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-06-08 Cont ID  
Sent By mjacobs Date 2005-06-08 Time 07:49 Rev Time 0.00
Received By shill Date 2005-06-08 Time 07:49 Sent To B
Notes
2005-06-09 00:00:00SENT TO J.WITMER DESK
  
  
2005-06-08 00:00:00TO 'MAMINI' DESK.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-06-02 Cont ID  
Sent By adarroug Date 2005-06-02 Time 16:08 Rev Time 0.00
Received By adarroug Date 2005-06-02 Time 16:08 Sent To Z
Notes
2005-06-02 00:00:00TO "Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-05-12 Cont ID  
Sent By adarroug Date 2005-05-12 Time 14:01 Rev Time 0.00
Received By adarroug Date 2005-05-12 Time 14:01 Sent To B
Notes
2005-05-12 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-04-27 Cont ID  
Sent By adarroug Date 2005-04-27 Time 14:27 Rev Time 0.00
Received By adarroug Date 2005-04-27 Time 14:27 Sent To B
Notes
2005-04-27 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-04-21 Cont ID  
Sent By adarroug Date 2005-04-21 Time 09:51 Rev Time 0.00
Received By adarroug Date 2005-04-21 Time 09:51 Sent To  
Notes
2005-04-21 00:00:00TO "COMM" BD#61/PLANS ON RACK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-01-26 Cont ID  
Sent By ptjomsto Date 2005-01-26 Time 15:01 Rev Time 0.00
Received By ptjomsto Date 2005-01-26 Time 15:01 Sent To  
Notes
2005-01-26 00:00:00SUBMITTAL GIVEN TO NEIL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-20 Cont ID  
Sent By mjacobs Date 2005-01-20 Time 11:20 Rev Time 0.00
Received By mjacobs Date 2005-01-20 Time 11:20 Sent To  
Notes
2005-01-20 00:00:00TO "COMM BD#61/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-31 Cont ID  
Sent By pkrauss Date 2004-12-31 Time 09:26 Rev Time 0.00
Received By pkrauss Date 2004-11-05 Time 10:44 Sent To  
Notes
2004-11-05 00:00:00TO COMM BD#

Review Stop M MECHANICAL (A/C)
Rev No 10 Status P Date 2007-03-06 Cont ID  
Sent By rregueir Date 2007-03-06 Time 17:16 Rev Time 0.00
Received By rregueir Date 2007-03-06 Time 16:37 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2007-01-30 Cont ID  
Sent By rregueir Date 2007-01-30 Time 13:25 Rev Time 0.00
Received By rregueir Date 2007-01-30 Time 13:25 Sent To PC
Notes
2007-01-30 13:26:33PAGE M207 REVISED TO SHOW NEW LOCATION OF BATH AND
 DRYER EXHAUST OUTLETS IN J UNIT.

Review Stop M MECHANICAL (A/C)
Rev No 8 Status F Date 2006-07-12 Cont ID  
Sent By hmoser Date 2006-07-12 Time 09:48 Rev Time 0.00
Received By hmoser Date 2006-07-12 Time 09:48 Sent To  
Notes
2006-07-12 00:00:00PLAN DENIED
 1) PLEASE PROVIED THREE SETS OF PLANS.
 2) PAGE NUMBER M-205 IS MARKED REVISON
 NUMBER 4,PLEASE MARK REVISON # 6.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2006-06-29 Cont ID  
Sent By hmoser Date 2006-06-29 Time 08:54 Rev Time 0.00
Received By hmoser Date 2006-06-29 Time 08:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2006-06-20 Cont ID  
Sent By hmoser Date 2006-06-20 Time 09:39 Rev Time 0.00
Received By hmoser Date 2006-06-20 Time 09:39 Sent To  
Notes
2006-06-20 00:00:00PLAN DENIED
 PLEASE PROVIDE THREE COPEYS OF EQUIPMENT
 SUBMITTALS AND THREE COPEYS OF COOLING
 HEATING LOAD SUMMARY SHEETS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2006-07-28 Cont ID  
Sent By hmoser Date 2006-07-28 Time 14:21 Rev Time 0.00
Received By hmoser Date 2006-07-28 Time 14:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2005-12-02 Cont ID  
Sent By pkrauss Date 2005-12-02 Time 10:33 Rev Time 0.00
Received By pkrauss Date 2005-12-02 Time 10:33 Sent To  
Notes
2005-12-02 00:00:00DENIED:
 1.MECHANICAL PLANS SUBMITTED FOR
 REVISION INDICATE THE UNITS ARE BEING
 REDUCED BY A 1/2 TO 1 TON OF AIR.
 CONDENSER UNITS ARE ALSO REDUCED (UNITS
 214, 224, & 234) ARE THE AHU'S ALSO
 BEING REDUCED?UNIT NUMBERS FOR THE AHU
 DO NOT MATCH THE CONDENSING UNIT
 NUMBERS.THE CONDO UNITS ARE MARKED A1,
 C3, ETC.PLEASE CORRELATE.
  
 2.PLEASE NOTE ENERGY & MANUAL J
 CALCULATIONS SUBMITTED ARE THE MINIMUM.
 THE REVISED A/C PLANS DO NOT CORRELATE
 WITH THE ENERGY CALCULATIONS. A/C
 SYSTEMS SHALL NOT BE LESS THAN WHAT IS
 DICTATED BY THE ENERGY & MANUAL J CALCS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-05-20 Cont ID  
Sent By pkrauss Date 2005-05-20 Time 13:58 Rev Time 0.40
Received By pkrauss Date 2005-05-20 Time 13:58 Sent To  
Notes
2005-05-20 00:00:00SEE COMMENTS ON PERMIT 04110483

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-02-17 Cont ID  
Sent By pkrauss Date 2005-02-17 Time 09:52 Rev Time 4.00
Received By pkrauss Date 2005-02-14 Time 14:08 Sent To  
Notes
2005-02-17 00:00:00DENIED:
 1.AS PER CONVERSATION WITH JIM MULLEN,
 DRYER SUBMITTAL TO BE CHANGED AND THE
 PLANS WILL BE REVISED DELETING THE
 BOOSTER FANS INSTALLED IN THE DRYER
 EXHAUST DUCT.SPECIFIC DRYERS ARE TO BE
 INSTALLED BY FINAL INSPECTION.
  
 2.PLAN SHEET M203 THE TRASH CHUTE ROOM
 DOES NOT INDICATE A C0 SENSOR AS
 REQUIRED PER PREVIOUS REVIEW.
  
 3.PLEASE NOTE IN THE RESIDENTIAL UNITS
 AS WELL AS COMMON AREAS, SYSTEMS THAT
 HAVE THE DESIGN CAPAPCITY TO PRODUCE
 GREATER THAN 2,000 CFM, DUCT SMOKE
 DETECTORS WILL BE REQUIRED IN THE SUPPLY
 AIR DUCT.AS AN ALTERNATE TO THE DUCT
 SMOKE DETECTORS, THE UPON ACTIVATION OF
 A SMOKE DETECTOR, THE A/C UNIT WILL SHUT
 DOWN. 2001 FBC(M)606.2.1, 606.2.2 AND
 606.4.
  
 4.FAN SHUTDOWN SHALL HAVE NOTIFICATION
 PER 2001 FBC(M)606.4.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-12-03 Cont ID  
Sent By pkrauss Date 2004-12-02 Time 14:04 Rev Time 8.00
Received By pkrauss Date 2004-12-02 Time 07:09 Sent To  
Notes
2004-12-02 00:00:00DENIED:
 1.PLANS INDICATE SOME ROOMS OFF THE
 ENCLOSED GARAGE ARE USING THE AIR IN
 THE GARAGE FOR MAKE-UP OR OUTSIDE AIR.
 PER 2001 FBC(M)401.5, FRESH AIR/MAKE-UP
 AIR SHALL NOT BE LOCATED 10 FT FROM
 NOXIOUS CONTAMINANTS SUCH AS PARKING
 LOTS OR LOADING DOCKS.
  
 2.A MINIMUM OF 4" CLEARANCE REQUIRED
 AROUND THE AHU IN ACCORDANCE WITH 2001
 FBC(M)603.1.3.
  
 3.PLEASE PROVIDE A SCHEMATIC
 INDICATING ELECTRICAL WIRING SHOWING
 HOW THE BOOSTER FAN FAILURE WILL
 PROHIBIT THE DRYER FROM FUNCTIONING.
 PLEASE NOTE, SUBMITTAL FOR THE BOOSTER
 FANS SHALL BE SUMITTED TO THE BUILDING
 OFFICIAL AS ALTERNATE MEANS & METHODS,
 FOR HIS APPOVAL.
  
 4.PLAN SHEET M202 THE CONDENSING UNIT
 RACK, THE MINIMUM CLEARANCE BETWEEN THE
 ROOF SURFACE AND BOTTOM OF THE SUPPORT
 RAIL SHALL COMPLY WITH 2001 FBC 1511.7.
 PLEASE INDICATE CLEARANCE ON THE PLAN.
  
 5.RETURN AIR JUMPERS FOR THE MASTER
 SUITE ARE NOT SIZED PROPERLY.PER 2001
 FBC(M)601.4 EXCEPTION #1 & 3, RETURN
 AIR
 JUMPERS SHALL BE A MINIIMUM OF 1 1/2
 TIMES THE SQUARE INCHES OF THE SUPPLY.
 ALL AIR INTO THE MASTER SUITE IS TO BE
 INCLUDED FOR THE TOTAL AIR SUPPLIED TO
 THE SUTIE, THE R/A JUMPER SHALL BE 1
 1/2
 TIMES THE TOTAL SUPPLY AIR INTO THE
 SUITE.
  
 6.PLEASE NOTE CONDENSATE SHALL NOT
 TERMINATE INTO THE SANATARY PER CITY
 CODE SECTION 90-125 (5).
  
 7.PROVIDE OUTSIDE AIR CALUCALTIONS FOR
 ALL AREAS - RESIDENTIAL, GARAGE, AND ALL
 COMMON AREAS.2001 FBC(M)403.3.
  
 8.PLEASE PROVIDE CALUCLATIONS FOR
 GARAGE VENTILATION SHOWING COMPLIANCE
 WITH 2001 FBC411.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 7 Status P Date 2006-07-08 Cont ID  
Sent By pschmitz Date 2006-07-08 Time 13:01 Rev Time 0.00
Received By pschmitz Date 2006-07-08 Time 13:01 Sent To  
Notes
2006-07-08 00:00:00REVISION:SHT P208,P301
 1-1/2" CPVC PAN & T/P DRAIN DOWN TO
 SPLASH BLOCK OUTSIDE.

Review Stop P PLUMBING
Rev No 6 Status F Date 2006-06-19 Cont ID  
Sent By kstevens Date 2006-06-19 Time 08:17 Rev Time 0.00
Received By kstevens Date 2006-06-16 Time 20:50 Sent To  
Notes
2006-06-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1. SHT P206 VENT REQUIRED AT URINAL.
 SECTION 901.2.1.
  
 2. SHT P208 TUB NOT VENTED AS PIPED.
 VENT REQUIRED FOR TUB. SECTION 901.2.1.
  
 3. SHTS P210 & P211 SHALL BE SUBMITTED
 UNDER THE CORRECT PERMIT NUMBER. SECTION
 104.2.1.
  
 4. SHT P310 SAN/10 RISER, TUB NOT
 VENTED. SECTION 901.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 5 Status F Date 2005-12-23 Cont ID  
Sent By kstevens Date 2005-12-23 Time 07:35 Rev Time 0.00
Received By kstevens Date 2005-12-22 Time 18:25 Sent To  
Notes
2005-12-23 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1. SHTS P201, P203, P205, P209, & P210
 SHALL BE SUBMITTED FOR REVISION UNDER
 THE APPROPRIATE PERMIT NUMBER FOR THOSE
 SHEETS. SECTION 104.2.1.
 2. SHTS P206 & 207 REVISION REQUIRED FOR
 THE ARCHITECTURAL SHEETS SHOWING THE
 DELETION OF THE SCUPPERS. SEE COMMENT #1
 FROM LAST REVISION SUBMITTAL (6-23-5).
 3. SHT P210 LEVEL 2-4. LEVEL 2 IS
 DIFFERENT THAN LEVELS 3 & 4. REVISE
 SEPARATELY. INDICATE UNIT DESIGNATION ON
 EACH SHEET. SECTION 104.2.1.
 - E6 OPP. REVISION REQUIRED FOR THE
 FLOOR PLAN. ONLY E6 FLOOR PLAN HAS BEEN
 REVISIED. IF FLOOR PLAN NOT REVISED,
 SUBMIT A RISER DIAGRAM TO REFLECT
 UNCHANGED FLOOR PLAN. SECTION 104.3.1.1.
 - G6 TUB NOT VENTED. WHAT RISER HAS BEEN
 REVISED TO REFLECT THIS CHANGE?
 - H6 INDICATE RISER NUMBER TO REFLECT
 CHANGE.
 - K6 2ND FLOOR INDICATE RISERS FOR
 THESE CHANGES.
 - F6 3RD & 4TH FLOORS
 4. SHT P301 WHERE IS WATER HEATER DRAIN
 PAN - WASTE WATER DETAIL? HAVE THE WATER
 HEATERS BEEN DELETED? DETAIL TO BE SHOWN
 ON REVISION.
 - WHERE IS RISERS SAN/6 & SAN/9? THESE
 RISERS ARE STILL SHOWN ON THE FLOOR
 PLAN. SECTION 104.2.1.
 - SAN/7 DOES NOT REFLECT THE FLOOR
 PLAN.
 - UNIT B-2 MASTER BATH SANT FITTINGS
 SHALL BE INSTALLED TO GUIDE SEWAGE AND
 WASTE IN THE DIRECTION OF FLOW. SECTION
 706.3.
 - UNIT E-5/6 MASTER BATH, SHOW ALL PIPE
 SIZES. MAX 4FU ON 2" WET VENT. SECTION
 104.2.1 AND TABLE 909.3.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  
  

Review Stop P PLUMBING
Rev No 4 Status F Date 2005-06-23 Cont ID  
Sent By kstevens Date 2005-06-23 Time 08:22 Rev Time 1.00
Received By kstevens Date 2005-06-22 Time 18:51 Sent To  
Notes
2005-06-23 00:00:00REVISION DENIED
  
 1. SHTS P206 & P207 MORE INFORMATION IS
 REQUIRED FOR REVISION. ARE DOWNSPOUTS
 BEING DELETED? IF SO A REVISION WILL BE
 REQUIRED SHOWING THE DOWNSPOUTS BEING
 DELETED ON THE ARCHITECTURAL SHEETS.
 SECTION 104.2.1.
 2. SHTS P206 & P207 REVISIONS 2 & 3 WERE
 NOT FOUND. LAST REVISION ON THE STAMPED
 ISSUED SET OF PLANS WAS REVISION 1.
 PLEASE CLOUD AND NUMBER ALL REVISIONS.
 SECTION 104.2.1.
 3. SHT P207 INDICATE SQUARE FOOTAGE OF
 EACH DOWNSPOUT AND COMBINED SF FOR
 HORIZONTAL SITE STORM LINE WHERE THE 2
 DOWNSPOUTS ARE NOW CONNECTING TOGETHER.
 ALSO SHOW PIPE SIZE FOR THE HORIZONTAL
 SIET STORM LINE. TABLE 1106.3
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-05-14 Cont ID  
Sent By kstevens Date 2005-05-14 Time 18:43 Rev Time 0.33
Received By kstevens Date 2005-05-14 Time 18:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-02-08 Cont ID  
Sent By kstevens Date 2005-02-08 Time 16:16 Rev Time 2.57
Received By kstevens Date 2005-02-08 Time 16:16 Sent To  
Notes
2005-02-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A) FROM PREVIOUS REVIEW:
 1) A TITLE BLOCK MUST CONTAIN THE
 FOLLOWING INFORMATION.
 61G1-16.004(2)(6)
 THE FIRM LICENSE NUMBER, AND THE
 PRINTED
 NAME OF THE PERSON SEALING THE
 DOCUMENT.
 ALSO THE CERTIFICATE OF AUTHORIZATION
 OF
 THE FIRM. SEE SHEETS L1 THRU L6 AND
 SHEETS I-1 THRU I-3.
 **************NEW COMMENT*************
 1B) SHT P202 BUILDING 1 STORM RISER
 DIAGRAM. MAXIMUM 730 SF @ 1% SLOPE. 4"
 PIPE REQUIRED ON THE HORIZONTAL PIPING
 OR INDICATE 4% SLOPE. INDICATE ON
 PLANS.
 TABLE 1106.3.
 2B) SHT P202 SCUPPERS THRU THE MANSARD
 ROOF REQUIRES A MINIMUM OF 21.195 SQ IN
 6" PIPE IS REQUIRED. TABLE 1106.3 AND
 SECTION 1107.3.
 3B) SHT P204 MINIMUM 4" PIPE REQUIRED
 ON
 STORM RISER HORIZONTAL PIPING. TABLE
 1106.3.
 4B) SHT P204 MINIMUM 6" PIPE REQUIRED
 ON
 THE SCUPPER DRAINS. SECTION 1107.3
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-12-08 Cont ID  
Sent By kstevens Date 2004-12-08 Time 17:05 Rev Time 15.25
Received By kstevens Date 2004-12-08 Time 17:05 Sent To  
Notes
2004-12-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) A TITLE BLOCK MUST CONTAIN THE
 FOLLOWING INFORMATION. 61G1-16.004(2)
 FIRM LICENSE NUMBER. FS 481.219
 2) SEE BLDG REVIEW FOR INFORMATION ABOUT
 SEPARATE PERMITS FOR EACH BUILDING AND
 C.O.'S - 6 BLDGS - 4 PERMITS.
 3) SHTS A104, A108, 120, P202, & P204
 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106
 AND 1107 AND ALL SUBSECTIONS. SHOW THE
 SF FOR ALL ROOFS, 1/2 AREA OF ALL
 VERTICAL WALLS, INCLUDING PARAPETS AND
 ALL AREAS OF ROOFS THAT DRAIN ONTO THE
 ROOF AREA FROM ABOVE.
 4) SHT A106 UNITS A1A & A1B MASTER BATH
 TOILET ROOMS A1A.14 & A1B.14. THE
 MANEUVERING SPACE WITHIN THE BATHROOM TO
 PERMIT A PERSON TO ENTER THE ROOM, CLOSE
 THE DOOR AND REOPEN THE DOOR AND EXIT IS
 REQUIRED. SEE PAGE 7.33 FHA DESIGN
 MANUAL, USABLE BATHROOM(4). IT APPEARS
 THE DOOR WILL BE BLOCKED WHEN THE
 WHEELCHAIR ENTERS. PLEASE CLARIFY.
 5) SHT A110 MASTER BATH BOTH UNITS,
 TOILET ROOMS B2.14 & A2.15 SEE NOTE #4.
 THE SAME ISSUE OCCURS WITH THE DOOR.
 6) SHTS P201, P206 & P207 ALL TRASH
 CHUTES SHALL HAVE BACKFLOW PROTECTION ON
 THE WATER LINES THAT SPRAY THE CHUTES.
 SECTION 608.13.6
 7) SHT A701 DETAIL #10 W/C SHALL BE M OF
 18" OFF THE WALL TO THE CENTERLINE OF
 THE FIXTURE. SEE PAGE 6.5 FIRST
 PARAGRAPH.
 8) SHT P704 DETAIL #3 MINIMUM OPENING
 FOR THE W/C SHALL BE 33" SEE PAGE 7.43
 9) SUBMIT MANUF. SPECIFICATION SHEETS
 FOR THE DOMESTIC PUMPS AND THE INSTANT
 WATER HEATER. SECTION 303.4
 10) SHT P201 BUILDING 1 PLUMBING PLAN
 GARAGE LEVEL SAYS "3/4 IN. COLD WATER TO
 EXT. HOSE BIBB", BUT NO COLD WATER LINE
 IS SHOWN. PLEASE CLARIFY. SECTION
 104.2.1.
 11) SHT P205 BLDG. 3 PLUMBING PLAN
 GARAGE LEVEL.:
 INDICATES RWL IN 2 LOCATIONS, BUT RWL
 RISER AND PIPING ARE NOT SHOWN.
 LEVEL 2 & 4 RWL'S ARE NOT SHOWN.
 COLD WATER LINE FROM DOMESTIC PUMP
 SHOWS 1-1/2" CW, THEN CHANGES TO 2"
 DOWNSTREAM. - PLEASE CLARIFY SECTION
 104.2.1.
 12) SHT P301 SANT. RISER #2 STANDPIPES
 ARE REQUIRED AT W/M. SECTION 1002.1 -
 SANT. RISER #5 S-1 SINK NOT VENTED AND
 PIPED AS SUCH CREATES AN "S" TRAP
 SECTION 1002.3(5). PLEASE INDICATE WHAT
 A S-1 SINK IS AS IT IS NOT SHOWN ON THE
 FIXTURE SCHEDULE. SECTION 104.2.1. -
 SANT. RISER DIAGRAM #6 S-X & S-1 SINKS
 ARE NOT VENTED AND PIPED AS SUCH CREATE
 AN "S" TRAP. SECTION 1002.3(5). PLEASE
 INDICATE WHAT A S-X AND A S-1 SINK ARE
 AS THEY ARE NOT SHOWN ON THE FIXTURE
 SECHEDULE. SECTION 104.2.1. - SANT.
 RISER #8 BT-1 NOT VENTED. SECTION
 901.2.1. - SANT. RISER #1 DOES NOT
 REFLECT THE FLOOR PLAN. NOT ALL THE
 PIPING FOR SANT. RISER #1 IS THE SAME ON
 EACH FLOOR PLAN. EACH RISER SHALL
 REFLECT THE FLOOR PLAN PIPING. SECTION
 104.2.1.
 13) SUBMIT A STORM RISER DIAGRAM FOR ALL
 RISERS AND BUILDING STORM DRAINS. SHOW
 ALL PIPE SIZES AND SQUARE FOOTAGE AS IN
 ACCUMULATES IN THE SYSTEMS. SECTION
 104.3.1.1.
 14) SUBMIT A CONDENSATE RISER AND BLDG
 CONDENSATE DRAIN ISOMETRIC SHOWING ALL
 PIPE SIZES AND CONNECTION POINT FOR EACH
 RISER. SECTION 104.3.1.1.
 15) SUBMIT A WATER DISTRIBUTION
 ISOMETRIC SHOWING ALL PIPE SIZES, POINTS
 ON CONNECTION FOR EACH RISER, VALVES,
 WATER HAMMER ARRESTORS ECT. FOR EACH
 BUILDING. SECTION 104.3.1.1,
 16) RPZ BACKFLOW REQUIRED FOR WATER
 SERVICE TO POOL.
 17) SEPARATE PERMIT REQUIRED FOR THE
 POOL.
 18) SUBMIT ISOMETRIC RISER DIAGRAM FOR
 THE WATER HEATER P&T VALVE DISCHARGE
 LINES AND EMERGENCY PAN DRAIN LINES.
 SHOW ALL PIPE SIZES AND THE TERMINATION
 POINT FOR EACH SYSTEM. SECTION
 104.3.1.1.
 19) SHT 401 DETAIL #8 WATER SHOWS A
 FLOOR DRAIN NOT SHOWN ON THE RISER
 DIAGRAM. PLEASE CLARIFY. SECTION
 104.2.1
 20) FLOOR DRAINS ARE NOT AN APPROVED
 INDIRECT WASTE RECEPTOR. SECTIONS 802.3
 AND 802.3.2.
  
  
  
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2005-05-24 Cont ID  
Sent By mmclean Date 2005-05-13 Time 12:32 Rev Time 0.00
Received By mmclean Date 2005-05-13 Time 12:32 Sent To  
Notes
2005-05-24 00:00:00GRACE JOYCE, PLANNER 822-1435

Review Stop Z ZONING
Rev No 1 Status P Date 2006-10-31 Cont ID  
Sent By mmclean Date 2005-01-20 Time 15:10 Rev Time 0.00
Received By jleahy Date 2005-01-20 Time 15:10 Sent To  
Notes
2005-01-20 00:00:00DENIED, MUST APPLY FOR A MINOR AMENDMENT
 FOR THE CHANGES THAT IS BEING DONE.
 APPLICATION SHOULD BE IN 1/24/05.
  
 CALL GRACE JOYCE, PLANNER 822-1447 FOR
 ANY QUESTIONS.