Plan Review Details - Permit 04110174
Plan Review Stops For Permit 04110174
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-12-03 Cont ID  
Sent By jwitmer Date 2004-12-03 Time 13:30 Rev Time 1.11
Received By jwitmer Date 2004-12-03 Time 13:30 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-12-03 Cont ID  
Sent By jwitmer Date 2004-11-03 Time 13:29 Rev Time 0.00
Received By jwitmer Date 2004-11-03 Time 13:29 Sent To  
Notes
2004-11-03 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04110174
 ADD: 700 NORTHPOINT PKY
 CONT: PLAN REVIEW
 CHRISTOPHER BERGA
 TEL: (305)416-3180
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
  
 1)PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS FIXED & OPERTABLE
 B) STOREFRONT
 C) DOORS
 D) LOUVERS
 E) ROOFING (TILE)
 PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE
 REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 3) PROVIDE POSITIVE & NEGATIVE
 PRESSURES
 FOR THE INTERIOR ZONES AND END ZONES,
 SHOW ON WINDOW AND DOOR ELEVATIONS
 SEE TABLE 1606.2B.
 IF MEAN ROOF HEIGHT IS OVER 30' USE
 TABLE 1606.2D FOR HEIGHT & EXPOSURE
 ADJUSTMENT COEFICIENTS.
  
  
 4) FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 5) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PLANS INDICATE THE USSE OF WIRE LATH &
 FRY REGLET ( REVELS) INDICATE HOW THE
 PAPER BACKING WILL BE INSTALLED AT THESE
  
 INTERSECTIONS, SEE ASTM C-1063.7.8.3.1.
  
 6)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 VARIOUS SHEETS OF PLANS INDICATE THE
 DELETION OF LOUVERS IN THE GABLE WALLS,
 PROVIDE CALCS FOR VENTILATION FOR ATTIC
 SPACE, SEE 2309.7.1.
  
 7) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 WILL ANY BRACING OCCUR ON THE GABLE
 ENDS?
  
 8) SHEET A501 DETAIL# 3, INDICATES THE
 USE OF 15/32 APA PLYWOOD, WITH NAILING
 @
 6" O.C. EDGES AND 12" IN THE FIELD. SEE
 2301.1.2 CHARTS 2306,2307,2308 AND
 2309 ARE TO BE USED ONLY IN WIND AREAS
 WHERE WIND SPEEDS DO NOT EXCEED 100
 MPH.
 PROVIDE ADDITIONAL INFORMATION FOR
 NAILING.
  
 9) A502 DETAIL# 5, INDICATES A WINDOW
 FLUSH WITH WALL. NOTE IF NON-IMPACT
 WINDOWS ARE USED SHUTTERS WILL NEED TO
 STAY APPROX 2 1/2 " FROMGLAZING.
 ALSO SEE IMPACT STANDARD FOR CITY.
  
 10) 1404.1.1 TRIM SHALL BE SECURED TO
 THE WALL WITH METAL OR OTHER APROVED
 BRACKETS OR FASTENERS.(EFIS TRIM).
  
 11)
 ) FBC* 105.13.1SPECIAL INSPECTOR.
 A STRUCTURAL INSPECTION PLAN MUST BE
 SUBMITTED PRIOR TO THE ISSUANCE OF A
 BUILDING PERMIT. THREE COPIES OF THE
 PLANS AND OTHER DOCUMENTS WILL BE
 REQUIRED FOR PERMITTING PURPOSES.
 CALL HAROLD PISKURA @ (561)805-6711 TO
 CONFIRM A SPECIAL INSPECTOR WILL BE
 REQUIRED.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-03 Cont ID  
Sent By mjacobs Date 2004-11-19 Time 10:54 Rev Time 1.11
Received By jwitmer Date 2004-11-19 Time 10:54 Sent To  
Notes
2004-11-19 00:00:00SENT TO JW DESK.