Plan Review Details - Permit 04110101
Plan Review Stops For Permit 04110101
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-01-18 Cont ID  
Sent By jwitmer Date 2005-01-18 Time 16:39 Rev Time 1.11
Received By jwitmer Date 2005-01-18 Time 16:39 Sent To  
Notes
2005-01-18 00:00:00BUILDING PROVISO
 PERMIT:04110101
 1851 OKEECHOBEE ROAD
 AS PER ARCHITECT HNM ARCHITECTURE, LLC
  
 1) STORAGE RACKS TO BE UNDER SEPERATE
 PERMIT.
 2) LIFE SAFETY PLAN TO ACCOMPANY
 STORAGE
 RACK PERMIT.
 3) HEIGHT OF STORAGE RACKS TO BE
 PROVIDED WITH NEW PERMIT.
 4) ALL EXIT LIGHTING AND SIGNAGE WILL BE
 RESOLVED UNDER RACK PERMIT.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-11-30 Cont ID  
Sent By jwitmer Date 2004-11-30 Time 12:45 Rev Time 1.10
Received By jwitmer Date 2004-11-30 Time 12:45 Sent To  
Notes
2004-11-30 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04110101
 ADD: 1851 OKEECHOBEE BLVD
 CONT:GLOBAL CONSTRUCTION
 ASSOCIATES
 TEL: (954)444-8463
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1)PROVIDE NOC RECORDED WITH THE CLERK OF
 COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) THE DOORS (1&2) ENTERING INTO THE
 STORAGE CLOSET ARE TO MEET :
 11-4.13.5 DOORWAYS, MINIMUM
 CLEAR WIDTH: DOORWAY SHALL HAVE A MINI-
 MUM CLEAR OPENING OF 32" WITH THE DOOR
 OPEN 90 DEGREES, MEASURED BETWEEN THE
 FACE OF THE DOOR AND THE OPPOSITE STOP.
 THE ONLY EXCEPTION TO THE MINIMUM DOOR
 WIDTH IS 11-4.13.5 DOORS NOT REQUIRING
 FULL PASSAGE, SUCH AS SHALLOW CLOSETS.
  
 3) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 4) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY.
  
 5)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 5A) PROVIDE LIFE STAFETY PLAN SHOWING
 THE ACCESS ISLES IN THE WAREHOUSE AREA.
 5B) PROVIDE INFO ON HOW HIGH THE
 STORAGE
 RACKS WILL BE FOR WAREHOUSE ? HIGH-PILED
  
 COMBUSTIBLE MAY BE A CONCERN.
 5C) DEPENDING ON THE ANSWER TO 5B EXIT
 LIGHTING AND SIGNAGE MAYBE OF CONCERN.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-12-29 Cont ID  
Sent By dpalmer Date 2004-12-29 Time 14:50 Rev Time 0.30
Received By dpalmer Date 2004-12-29 Time 14:50 Sent To  
Notes
2004-12-29 00:00:00CONTRACTOR NEEDS TO REMOVE ALL
 OLD/VOIDED SHEETS FROM SETS AND INSERT
 ALL NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 ELECTRICAL SHEETS STAMPED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-11-16 Cont ID  
Sent By dpalmer Date 2004-11-16 Time 08:00 Rev Time 0.40
Received By dpalmer Date 2004-11-16 Time 07:48 Sent To  
Notes
2004-11-16 00:00:00************** UNSAT ***********
  
 1)NOTE: PLEASE HAVE PLANS SIGNED WITH
 "LEGAL" "SIGNATURE" . INITIALS ARE NOT
 PERMITTED.
 PLANS ARE ALSO REQUIRED TO BE DATED
 UNDER THE SAME FS'S
 THIS IS REQUIRED FOR ALL SHEETS AND FOR
 ALL TRADES WHEATER OR NOT COMMENT IS
 MADE BY OTHER REVIEWERS.
 FS 471.025, FAC 61G15-23.002
  
 2)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%.
 230.42,215.3 ETC.
  
 3)NOTE: PLEASE CLARIFY IF THERE IS AN
 EXISTING OR NEW SIGN CIRCUIT(S). 600.5
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWERS WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW, IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-01-07 Cont ID  
Sent By mcarsill Date 2005-01-07 Time 13:37 Rev Time 0.00
Received By mcarsill Date 2005-01-07 Time 13:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-11-12 Cont ID  
Sent By mcarsill Date 2004-11-12 Time 14:58 Rev Time 0.00
Received By mcarsill Date 2004-11-12 Time 14:58 Sent To  
Notes
2004-11-12 00:00:001) FIRE ALARM CIRCUITS SHALL BE CLASS
 A, STYLE D NOT CLASS B, STYLE C AS
 SHOWN ON PAGE FAO.1.
  
 2) DUCT SMOKE DETECTORS WHEN
 ACTIVATED SHALL CAUSE AN ALARM NOT
 A SUPERVISORY SIGNAL AS SHOWN ON
 PAGE FA0.1.
  
 3) PROVIDE SEPARATE PLANS AND PERMITS
 FOR FIRE SPRINKLERS AND FIRE ALARM
 REMODELS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-08 Cont ID  
Sent By adarroug Date 2005-02-08 Time 12:38 Rev Time 0.00
Received By adarroug Date 2005-02-08 Time 12:38 Sent To P
Notes
2005-02-08 00:00:00TO KSTEVENS DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-12-21 Cont ID  
Sent By mjacobs Date 2004-12-21 Time 07:34 Rev Time 0.00
Received By mjacobs Date 2004-12-21 Time 07:34 Sent To  
Notes
2004-12-21 00:00:00SENT TO "COMM BD#40

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-11-05 Cont ID  
Sent By csiegber Date 2004-11-05 Time 11:14 Rev Time 0.00
Received By csiegber Date 2004-11-05 Time 11:16 Sent To  
Notes
2004-11-05 00:00:00TO COMM BD#15

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-01-11 Cont ID  
Sent By pkrauss Date 2005-01-11 Time 13:51 Rev Time 0.45
Received By pkrauss Date 2005-01-11 Time 11:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-11-30 Cont ID  
Sent By pkrauss Date 2004-11-30 Time 17:54 Rev Time 0.55
Received By pkrauss Date 2004-11-30 Time 17:43 Sent To  
Notes
2004-11-30 00:00:00DENIED:
 PLANS ARE TO BE SIGNED BY THE ENGINEER
 NOT INITIALED IN ACCORDANCE WITH FS
 471.025 & FAC 61G15-23.002.PLANS ARE
 OTHERWISE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-02-14 Cont ID  
Sent By kstevens Date 2005-02-14 Time 16:31 Rev Time 0.75
Received By kstevens Date 2005-02-14 Time 16:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-01-24 Cont ID  
Sent By kstevens Date 2005-01-24 Time 11:38 Rev Time 1.50
Received By kstevens Date 2005-01-19 Time 16:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-11-29 Cont ID  
Sent By kstevens Date 2004-11-29 Time 09:20 Rev Time 0.50
Received By kstevens Date 2004-11-29 Time 09:20 Sent To  
Notes
2004-11-29 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE. SECTION 608.13.2
 2) THERMAL EXPANSION CONTROL IS REQUIRED
 PER SECTION 607.3.2
 3) SHT PO.1 WATER RISER DIAGRAM, THE
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE
 RANGE", NOT IN THE CEILING AS SHOWN.
 PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS. (SEE PLUMBING NOTES 13)
 4) A PROFESSIONAL ENGINEER SHALL SIGN
 HIS NAME. INITIALS ARE NOT APPROVED. FAC
 61G15-23.002(1) & FS 471.025 - THIS IS
 FOR ALL M.E.P. SHEETS.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]