Plan Review Details - Permit 04110084
Plan Review Stops For Permit 04110084
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-01-26 Cont ID  
Sent By jwitmer Date 2005-01-26 Time 13:30 Rev Time 1.11
Received By jwitmer Date 2005-01-26 Time 13:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-11-29 Cont ID  
Sent By jwitmer Date 2004-11-29 Time 07:30 Rev Time 1.11
Received By jwitmer Date 2004-11-29 Time 07:30 Sent To  
Notes
2004-11-29 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04110084
 ADD: 901 N OLIVE AVE/ SUITE ???
 CONT: PALM COAST BUILDERS
 TEL: (561)262-2226
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL
 LETTER
 LISTING THE ORIGINAL REVIEW COMMENT
 NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR
 SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1)PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PERMIT APPLICATION DOES NOT PROVIDE
 WHAT
 UNIT OR SUITE WORK IS TO COMPLETEED
 UNDER THIS PERMIT?
  
 3) PROVIDE CURRENT PROPERTY CONTROL
 NUMBER SEE ATTACHMENT.
  
 4) 704.2.1.4 CORRIDOR PARTITIONS,
 SMOKE STOP PARTITIONS, HORIZONTAL EXIT
 PART- ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 5) 1016.3.1. EXIT SIGNS:
 EXIT SIGNS SHALL BE MARKED BY AN
 APPROVED SIGN READILY VISIBLE FROM ANY
 DIRECTION OF EXIT ACCESS. EVERY EXIT
 SIGN SHALL BE SUITABLE ILLUMINATED BY A
 RELIABLE LIGHT SOURCE. EXTERNALLY AND
 INTERNALLY ILLUMINATED SIGNS SHALL BE
 VISIBLE IN BOTH THE NORMAL & EMERGENCY
 LIGHTING.
  
  
 6)TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-12-07 Cont ID  
Sent By dpalmer Date 2006-12-07 Time 17:22 Rev Time 0.00
Received By dpalmer Date 2006-12-07 Time 16:58 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-09-17 Cont ID  
Sent By dpalmer Date 2006-09-17 Time 09:37 Rev Time 0.00
Received By dpalmer Date 2006-09-17 Time 08:52 Sent To PC
Notes
2006-09-17 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS
 REVIEW WHICH STATES TO CORRELATE RISER
 AND PANEL SHOWN FOR SIZE ETC.
 PLEASE SEE MLO, MCB??
 106.1.2 FBC ADMIN SECT.
  
 2) NOTE: THIS IS ONLY A NOTE, HOWEVER
 PLEASE VERIFY THE OCP ON THE MAIN
 DISCONNECT AS SHOWN. PLEASE SEE THE
 EQUIPMENT GROUNDING CONDUCTOR FROM THE
 MAIN TO THE SUB PANEL IS SHOWN 3 SIZES
 ALRGER THAN NEEDED BASED ON THE OCP
 SHOWN ON THE MAIN. 250.122 .
 THIS IS OK, HOWEVER IF SHOWN LIKE THIS
 ON RISER THEN THIS IS WHAT WILL BE
 REQUIRED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REWVIEW.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-02-21 Cont ID  
Sent By dpalmer Date 2006-02-21 Time 11:03 Rev Time 0.00
Received By dpalmer Date 2006-02-21 Time 10:04 Sent To  
Notes
2006-02-21 00:00:00*********** UNSAT ***********
  
 1)NOTE: PLEASE SEE FS 481.221 WHICH
 REQUIRES THE ARCHITECT TO ALSO DATE
 PLANS WHEN SIGNING AND SEALING SAID
 DOCUMENTS.
 PLEASE SEE THIS IS NOTED AS "AS-BUILTS"
 INSTEAD OF DATE?
 PLEASE SEE COMMENTS BELOW
  
 2)NOTE: PLEASE SEE AHU IS SHOWN ON A/C
 LAYOUT BUT NOT ON ELECTRICAL? PLEASE
 SHOW WITH CIRCUITING.
 215.5
  
 3)NOTE: PLEASE SEE CIRCUITING ON PLANS
 DOES NOT CORRELATE WITH NOTE FOR
 CIRCUITING OF EM/ EXT LTS. PLEASE SEE
 700.12E WHICH REQUIRES EM/EXT LTS TO BE
 CIRCUITED TO THE LOCAL BRANCH CIRCUIT OF
 NORMAL LIGHTING IN ANY ONE AREA.
 PLEASE ALSO SEE PANEL SCHEDULE.
  
 4)NOTE: PLEASESEE CIRCUIT ON SCHEDULE
 MENTIONS LTS FO PANEL ROOM??
 PLEASE VERIFY WHAT THIS IS AS A PANEL
 ROOM COULD NOT BE LOCATED ON PLANS.
  
 5)NOTE: PLEASE CORRELATE THE RISER AND
 PANEL SUBMITTED AS THESE ARE SHOWN WITH
 DIFFERENT SIZES.
 215.5
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. PLEASE BE SURE TO SEE ANY
 POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-02-03 Cont ID  
Sent By dpalmer Date 2005-02-03 Time 17:09 Rev Time 0.00
Received By dpalmer Date 2005-02-03 Time 17:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-01-14 Cont ID  
Sent By dpalmer Date 2005-01-14 Time 13:44 Rev Time 0.30
Received By dpalmer Date 2005-01-14 Time 13:44 Sent To  
Notes
2005-01-14 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE SEE NOTES ON PREVIOUS
 REVIEW FROM BLDG AND ELECTRICAL REVIEW.
 ALL OLD/VOIDED SHEETS ARE TO BE REMOVED
 FROM SETS AND ANY NEW SHEETS ARE TO BE
 INSERTED INTO COMPLETE SETS FOR REVIEW
 AND STAMPING.
  
 2)NOTE: PLEASE SEE A PANEL SCHEDULE IS
 NOW SUBMITTED, HOWEVER THIS PANEL
 SCHEDULE DOES NOT INDICATE ANY WIRE
 SIZES, OVER CURRENT PROTECTION FOR
 CIRCUITS? ETC.
 215.5
 PLEASE ALSO SEE 700.12 E FOR CIRCUITING
 OF EM/EXT LTS. THE BRANCH CIRCUIT
 FEEDING THE UNIT EQUIPMENT SHALL BE THE
 SAME BRANCH CIRCUIT AS THAT SERVING THE
 NORMAL LIGHTING IN THE AREA AND
 CONNECTED AHEAD OF ANY LOCAL SWITCHES.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-11-05 Cont ID  
Sent By dpalmer Date 2004-11-05 Time 10:35 Rev Time 33.00
Received By dpalmer Date 2004-11-05 Time 10:35 Sent To  
Notes
2004-11-05 00:00:00******** UNSAT *********
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH A PANEL
 SCHEDULE TO BE SUBMITTED.215.5
  
 2)NOTE: PLEASE CLARIFY OF SERVICE SHOWN
 IS NEW OR EXISTING?
 PLEASE SHOW LOCATION OF SERVICE/PANELS
 ETC.
 IF THIS A NEW SERVICE, THIS MAY OR MAY
 NOT BE PERMITTED PER 230.2.
 230.72 ETC
 PLEASE ALSO VERIFY AIC RATING SHOWN AT
 77,000, THIS DOES NOT SEEM TO BE A
 NORMAL RATED SIZE.??
 110.9
  
 3)NOTE: PLEASE SHOW ANY AND ALL NEW A/C
 EQUIPMENT ALONG WITH REQUIRED
 DISCONNECTS PER 440.11 ON ELECTRICAL
 PLANS.
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWERS WHICH MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-03-03 Cont ID  
Sent By mwennerg Date 2006-03-03 Time 09:25 Rev Time 0.00
Received By mwennerg Date 2006-03-03 Time 09:25 Sent To  
Notes
2006-03-03 00:00:00******PROVISO******
  
  
 SUBMITTED AS REVISION SHOWING AS BUILT.
 PLANS ARE NOT DATED. PLEASE SEE OTHER
 COMMENTS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-01-25 Cont ID  
Sent By nmccray Date 2005-01-25 Time 11:30 Rev Time 0.00
Received By nmccray Date 2005-01-25 Time 11:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-12-01 Cont ID  
Sent By nmccray Date 2004-12-01 Time 15:25 Rev Time 0.00
Received By nmccray Date 2004-12-01 Time 15:25 Sent To  
Notes
2004-12-01 00:00:00DENIED**********************************
 ENIED***********************************
 NIED***********************************
  
 1) DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2) DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY.
  
 3) EXIT SIGNS AND EMERGENCY LIGHTS ARE
 REQUIRED.
  
 4) NFPA 101 LIFE SAFETY CODE 2000
 EDITION CH 38.3.3.2 INTERIOR WALL AND
 CEILING FINISH COMPLYING WITH 10.2.3
 SHALL BE CLASS A OR CLASS B IN EXITS AND
 IN ENCLOSED CORRRIDORS FURNISHING ACCESS
 TO EXITS; AND CLASS A, CLASS B, OR CLASS
 C IN OFFICE AREAS.
  
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-12-01 Cont ID  
Sent By adarroug Date 2006-12-01 Time 16:54 Rev Time 0.00
Received By adarroug Date 2006-12-01 Time 16:54 Sent To E
Notes
2006-12-01 16:55:01TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-09-08 Cont ID  
Sent By adarroug Date 2006-09-08 Time 13:52 Rev Time 0.00
Received By adarroug Date 2006-09-08 Time 13:52 Sent To E
Notes
2006-09-08 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-01-26 Cont ID  
Sent By adarroug Date 2006-01-26 Time 15:58 Rev Time 0.00
Received By adarroug Date 2006-01-26 Time 15:58 Sent To  
Notes
2006-02-17 00:00:00TO "COMM" BD#15
2006-01-26 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-01-31 Cont ID  
Sent By mjacobs Date 2005-01-31 Time 12:58 Rev Time 0.00
Received By mjacobs Date 2005-01-31 Time 12:58 Sent To  
Notes
2005-01-31 00:00:00TO "COMM BD#36/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status P Date 2005-01-10 Cont ID  
Sent By mjacobs Date 2005-01-10 Time 11:53 Rev Time 0.00
Received By mjacobs Date 2005-01-10 Time 11:53 Sent To  
Notes
2005-01-10 00:00:00TO "COMM BD#32" /RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-02 Cont ID  
Sent By kstevens Date 2004-12-02 Time 07:00 Rev Time 0.00
Received By kstevens Date 2004-11-04 Time 10:36 Sent To  
Notes
2004-11-01 00:00:00TO COMM BD#10

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2006-02-22 Cont ID  
Sent By hmoser Date 2006-02-22 Time 15:23 Rev Time 0.00
Received By hmoser Date 2006-02-22 Time 15:23 Sent To  
Notes
2006-02-22 00:00:00NO CHANGES ON MECHANICAL
 PLANS.HM.2/22/06

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-01-21 Cont ID  
Sent By pkrauss Date 2005-01-21 Time 15:09 Rev Time 0.35
Received By pkrauss Date 2005-01-21 Time 15:01 Sent To  
Notes
2005-01-21 00:00:00PROVISO:
 AUXILIARY DRAIN LINE SHALL TERMINATE AT
 A CONSPICUOUS POINT PER 2001
 FBC(M)307.2.3.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-11-30 Cont ID  
Sent By pkrauss Date 2004-11-30 Time 17:26 Rev Time 0.40
Received By pkrauss Date 2004-11-30 Time 17:21 Sent To  
Notes
2004-11-30 00:00:00DENIED:
 1.RETURN AIR JUMPER FROM RM #102 & 103
 IS NOT SIZED.PROVIDE DUCT AND GRILLE
 SIZE.PER 2001 FBC(M)601.4 EXCEPTION
 #1, RETURN AIR JUMPER SHALL BE A MINIMUM
 OF 1 1/2 TIMES THE SQUARE INCHES OF
 SUPPLY (12").
  
 2.RETURN AIR GRILLE FROM RM #103 IS
 NOT SIZED.PLEASE REVISE.
  
 3.PROVIDE OUTSIDE OUTSIDE AIR
 CALCULATIONS PER 2001 FBC(M) TABLE
 403.3.
  
 4.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 1 Status N Date 2004-12-02 Cont ID  
Sent By kstevens Date 2004-12-02 Time 06:59 Rev Time 0.25
Received By kstevens Date 2004-12-02 Time 06:59 Sent To  
Notes
2004-12-02 00:00:00NO PLUMBING PLANS/WORK SHOWN