Plan Review Details - Permit 04110059
Plan Review Stops For Permit 04110059
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-12-23 Cont ID  
Sent By jwitmer Date 2004-12-23 Time 16:03 Rev Time 0.55
Received By jwitmer Date 2004-12-23 Time 16:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-11-24 Cont ID  
Sent By jwitmer Date 2004-11-24 Time 16:44 Rev Time 0.50
Received By jwitmer Date 2004-11-24 Time 16:44 Sent To  
Notes
2004-11-24 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04110059
 ADD: 2707 OKEECHOBEE BLVD
 CONT: WASTE WATER MANAGEMENT
 TEL: (561)718-3890
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PROVIDE MANUFACTURES SPEC FOR SEALING &
 PINNING OF 2" HIGH PREMANUFACRURED
 CURB.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-12-27 Cont ID  
Sent By dpalmer Date 2004-12-27 Time 10:22 Rev Time 0.30
Received By dpalmer Date 2004-12-27 Time 10:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-11-05 Cont ID  
Sent By dpalmer Date 2004-11-05 Time 08:39 Rev Time 0.50
Received By dpalmer Date 2004-11-05 Time 08:39 Sent To  
Notes
2004-11-05 00:00:00********* UNSAT************
  
 1)NOTE: PLEASE CLARIFY IS EXISTING PANEL
 IS LISTED FOR LOCATION.408.6,408.17
 PLEASE ALSO SUBMIT MORE INFORMATION ON
 NEW RECYKE PANEL. HOW IS THIS FED? ETC.
 PLEASE SUBMIT SPECS FOR THIS PANEL.
  
 2)NOTE: PLEASE SHOW GFI PROTECTION FOR
 ANY RECEPTS IN LOCATIONS PER 210.8
 PLEASE ALSO GFI PROTECTION FOR
 SUMP-PUMP
 CIRCUIT.
  
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-12-20 Cont ID  
Sent By mjacobs Date 2004-12-20 Time 15:51 Rev Time 0.00
Received By mjacobs Date 2004-12-20 Time 15:51 Sent To  
Notes
2004-12-20 00:00:00SENT TO "COMM BD#50

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-11-29 Cont ID  
Sent By kstevens Date 2004-11-29 Time 08:25 Rev Time 0.00
Received By kstevens Date 2004-11-01 Time 16:10 Sent To  
Notes
2004-11-01 00:00:00TO COMM BD#11

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-01-14 Cont ID  
Sent By kstevens Date 2005-01-14 Time 13:05 Rev Time 1.00
Received By kstevens Date 2005-01-14 Time 10:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-11-29 Cont ID  
Sent By kstevens Date 2004-11-29 Time 08:00 Rev Time 0.33
Received By kstevens Date 2004-11-29 Time 07:47 Sent To  
Notes
2004-11-29 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) INDICATE SOURCE OF MAKE UP WATER FOR
 THE CAR WASH. AN RPZ BACKFLOW IS
 REQUIRED IF WATER SERVICE TO CAR WASH IS
 DIRECTLY CONNECTED TO POTABLE WATER.
 SECTION 608.13.2
 2) ANY PROTION OF THE DRAINAGE SYSTEM
 INSTALLED UNDERGROUNG SHALL NOT BE LESS
 THAN 2 INCHES. SECTION 710.3 - PROPOSED
 1 INCH LINE CONNECTION NOT APPROVED.
 3) TWO WAY CLEANOUT IS REQUIRED AS THE
 SANITARY BLDG DRAIN EXITS THE SLAB.
 SECTION 708.3.5
 4) A TRAP IS REQUIRED FOR THE OVERFLOW
 LINE TO THE SANITARY SEWER. SECTION
 1002.1
 5) A VENT IS REQUIRED FOR THE OVERFLOW
 LINE TO THE SANITARY SEWER. SECTION
 902.1
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]