Plan Review Details - Permit 04101262
Plan Review Stops For Permit 04101262
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-06-28 Cont ID  
Sent By alange Date 2005-06-28 Time 15:55 Rev Time 0.75
Received By alange Date 2005-06-28 Time 15:55 Sent To  
Notes
2005-06-28 00:00:00BATHROOM REVISION ON PAGE A-1 OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-04-01 Cont ID  
Sent By alange Date 2005-04-01 Time 08:12 Rev Time 0.75
Received By alange Date 2005-04-01 Time 08:12 Sent To  
Notes
2005-04-01 00:00:00REVISION OKALANGE

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-12-15 Cont ID  
Sent By alange Date 2004-12-15 Time 11:16 Rev Time 0.75
Received By alange Date 2004-12-15 Time 11:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-11-05 Cont ID  
Sent By alange Date 2004-11-05 Time 09:45 Rev Time 2.00
Received By alange Date 2004-11-05 Time 09:45 Sent To  
Notes
2004-11-05 00:00:00DENIED
  
  
 1.DOORS IN HALLWAY AT BATHROOMS AND
 HVAC CLOSET SHALL COMPLY WITH THE
 FOLLOWING.
 1012.1.4. DURING ITS SWING, ANY
 DOOR IN A MEANS OF EGRESS SHALL LEAVE
 UNOBSTRUCTED AT LEAST 1/2 OF THE REQUIRE
 REQUIRED WIDTH OF AN AISLE, CORRIDOR,
 PASSAGEWAY, OR LANDING, NOR PROJECT MORE
 THAN 7" INTO THE REQUIRED WIDTH.
  
 2.PANTRY SINK HEIGHT SHALL COMPLY WITH
  
 FBC 11-4.24.2 ALSO KNEE CLEARANCE SHALL
 COMPLY WITH FBC 11-4.24.3
 SHOW DETAIL ON PLANS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
  
 BUILDING PLAN REVIEW
 ART LANGE
 TEL: (561)805-6672
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-04-04 Cont ID  
Sent By dpalmer Date 2005-04-04 Time 13:11 Rev Time 1.00
Received By dpalmer Date 2005-04-04 Time 12:55 Sent To  
Notes
2005-04-04 00:00:00REV'S FOR E-1, AND E-2 ONLY.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-01-19 Cont ID  
Sent By dpalmer Date 2005-01-19 Time 18:46 Rev Time 0.50
Received By dpalmer Date 2005-01-19 Time 18:43 Sent To  
Notes
2005-01-19 00:00:00 

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-12-23 Cont ID  
Sent By dpalmer Date 2004-12-23 Time 14:39 Rev Time 0.25
Received By dpalmer Date 2004-12-23 Time 14:37 Sent To  
Notes
2004-12-23 00:00:00*********** UNSAT ************
  
 1)NOTE: PLEASE SEE PERMIT APPLICATION IS
 FOR 405 NORTHWOOD, RE-SUB SHEET MENTIONS
 403, PLANS INDICATE 403 ALSO AND LAND
 FILE SHOWS ADDRESS AS BEING 405????
 PLEASE CORRELATE WHICH IS CORRECT.
  
 2)NOTE: PLEASE SEE RESPONSE LTR MENTIONS
 AN "ELECTRICAL" SIGN IS NOT GOING TO BE
 INSTALLED, HOWEVER, 600.5 REQUIRES A
 CIRCUIT AT FRONT LOCATION WHEATHER OR
 NOT AN ELECTRICAL SIGN IS INSTALLED.
 PLEASE ADJUST PLANS AND PANEL SCHEDULE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-11-04 Cont ID  
Sent By dpalmer Date 2004-11-04 Time 11:17 Rev Time 0.75
Received By dpalmer Date 2004-11-04 Time 09:12 Sent To  
Notes
2004-11-04 00:00:00******* UNSAT ********
  
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 RATINGS ARE GIVEN FOR PANELS AND BRANCH
 BRKRS.
  
  
 2 )NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
 PLEASE ALSO SEE LARGEST MOTOR.
 TRK LT LOADING TO BE SHOWN PER 220.12B
  
 3)NOTE: PLEASE VERIFY NEW OR EXISTING
 SIGN CIRCUIT. 600.5
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWERS WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT ONLY NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-04-12 Cont ID  
Sent By mwennerg Date 2005-04-12 Time 10:55 Rev Time 0.00
Received By mwennerg Date 2005-04-12 Time 10:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-12-27 Cont ID  
Sent By mcarsill Date 2004-12-27 Time 14:17 Rev Time 0.00
Received By mcarsill Date 2004-12-27 Time 14:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-11-10 Cont ID  
Sent By mcarsill Date 2004-11-10 Time 16:58 Rev Time 0.00
Received By mcarsill Date 2004-11-10 Time 16:58 Sent To  
Notes
2004-11-10 00:00:001) PLEASE PROVIDE PRESCRIPTIVE
 STRENGTH REQUIREMENTS FOR HANDRAIL.
  
 2) WILL ANY STORAGE BE PERMITTED
 UNDERNEATH THE PLATFORM. ANY
 MECHANICAL OR ELECTRICAL PLANNED
 FOR UNDERNEATH THE PLATFORM.
  
 3) SOFFITS ARE NOT TO INTERFERE
 WITH ANY FIRE SPRINKLER HEADS.
  
 4) PLEASE ILLUSTRATE ALL EXIT SIGNS
 AND EMERGENCY LIGHTING.
  
 5) PLEASE DISPLAY ALL PORTABLE
 FIRE EXTINGUISHER LOCATIONS.
  
 6) SEPARATE PLANS AND PERMITS
 REQUIRED FOR FIRE ALARM AND FIRE
 SPRINKLER REMODEL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-06-27 Cont ID  
Sent By adarroug Date 2005-06-27 Time 16:52 Rev Time 0.00
Received By adarroug Date 2005-06-27 Time 16:52 Sent To B
Notes
2005-06-27 00:00:00TO "ALANGE" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-03-31 Cont ID  
Sent By adarroug Date 2005-03-31 Time 09:22 Rev Time 0.00
Received By adarroug Date 2005-03-31 Time 09:22 Sent To  
Notes
2005-03-31 00:00:00TO "COMM" BD#45

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-01-11 Cont ID  
Sent By mjacobs Date 2005-01-11 Time 14:19 Rev Time 0.00
Received By mjacobs Date 2005-01-11 Time 14:19 Sent To E
Notes
2005-01-11 00:00:00TO "DP" DESK/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-12-09 Cont ID  
Sent By mjacobs Date 2004-12-09 Time 13:39 Rev Time 0.00
Received By mjacobs Date 2004-12-09 Time 13:39 Sent To  
Notes
2004-12-09 00:00:00SENT TO COMM BD#30

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-01 Cont ID  
Sent By pkrauss Date 2004-12-01 Time 07:08 Rev Time 0.00
Received By pkrauss Date 2004-11-01 Time 12:15 Sent To  
Notes
2004-10-29 00:00:00TO COMM BD#4

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-05-02 Cont ID  
Sent By pkrauss Date 2005-05-02 Time 15:05 Rev Time 0.35
Received By pkrauss Date 2005-05-02 Time 15:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2005-04-25 Cont ID  
Sent By pkrauss Date 2005-04-25 Time 14:29 Rev Time 0.40
Received By pkrauss Date 2005-04-25 Time 12:50 Sent To  
Notes
2005-04-25 00:00:00DENIED:
 1.PLANS INDICATE REVISIONS 1, 2, 3 AND
 4 BUT ONLY REVISION #4 IS INDICATED ON
 PLAN SHEET AC-1 & AC-2.
  
 2.PLAN SHEET AC-2 INDICATES HEIGHT FOR
 THE CU STAND.DETAIL INDICATES "HEIGHT
 OF LEGS".THIS SHOULD READ "MINIMUM
 CLEARANCE ABOVE THE ROOF" WHICH MAY BE
 GREATER THAN 14" DEPENDING ON THE ROOF
 SYSTEM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-01-05 Cont ID  
Sent By pkrauss Date 2005-01-05 Time 07:31 Rev Time 0.35
Received By pkrauss Date 2005-01-05 Time 07:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-12-01 Cont ID  
Sent By pkrauss Date 2004-12-01 Time 06:52 Rev Time 0.45
Received By pkrauss Date 2004-12-01 Time 06:35 Sent To  
Notes
2004-12-01 00:00:00PROVISO:
 CONDENSING UNIT STAND INDICATED ON PLAN
 SHEET AC-2 INDICATES 18" FROM THE ROOF
 DECK.PLEASE REFERENCE 2001 FBC 1511.7
 FOR PROPER CLEARANCE BETWEEN THE ROOF
 SURFACE AND THE BOTTOM OF THE SUPPORT
 RAIL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-05-03 Cont ID  
Sent By kstevens Date 2005-05-03 Time 09:50 Rev Time 0.55
Received By kstevens Date 2005-05-03 Time 09:49 Sent To  
Notes
2005-05-03 00:00:00REVISION OK CHANGED KITCHEN FLOOR PLAN

Review Stop P PLUMBING
Rev No 3 Status F Date 2005-04-25 Cont ID  
Sent By kstevens Date 2005-04-25 Time 09:14 Rev Time 0.75
Received By kstevens Date 2005-04-25 Time 09:14 Sent To  
Notes
2005-04-25 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHT A-1 SHOW CLEAR FLOOR SPACE FOR
 THE WATER COOLER. SECTION 11-4.15.5
 2) SHT P-1 INDICATES REVISIONS 2, 3, & 4
 BUT ONLY REVISION NUMBER 4 WAS FOUND.
 INDICATE ALL REVISIONS WITH CLOUDS AND
 NUMBERED TRIANGLES TO EXPEDITE REVIEW.
 SECTION 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-01-10 Cont ID  
Sent By jleech Date 2005-01-10 Time 14:47 Rev Time 1.00
Received By jleech Date 2005-01-10 Time 14:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-11-27 Cont ID  
Sent By kstevens Date 2004-11-27 Time 19:31 Rev Time 0.50
Received By kstevens Date 2004-11-27 Time 19:16 Sent To  
Notes
2004-11-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) ARCHITECTURAL SHEETS: PRINTED NAME OF
 THE PERSON SEALING THE DOCUMENT IS
 REQUIRED PER FAC 61G1-16.004(6) AND FS
 481.2055.
 2) SHOW CLEAR FLOOR SPACE FOR LAVS,
 WATER CLOSETS, AND URINAL PER SECTIONS
 11-4.16.2, 11-4.18.3, 11-4.19.3, AND
 11-4.22.3.
 3) SUBMIT A DETAIL FOR THE PANTRY SINK
 SHOWING COMPLIANCE WITH SECTION 11-4.24
 AND ALL SUBSECTIONS.
 4) A DRINKING FOUNTAIN IS REQUIRED PER
 TABLE 403.1. ALSO SEE SECTION 410.1
 5) SHT P-1 SANITARY RISER DIAGRAM AND
 FLOOR PLAN FOR PIPING. THE SINK SHALL
 NOT DRAIN THROUGH THE HORIZONTEL WET
 VENT OF THE TOILET ROOMS. SECTION 909.1.
 THE SINK SHALL CONNECT DOWNSTREAM OF THE
 WET-VENTED FIXTURES. (SEE RED LINE
 EXAMPLE ON ONE SET OF PLANS.
 6) SHT P-1 WATER RISER DIAGRAM, AIR
 CHAMBERS ARE NOT APPROVED. SECTION
 604.9
 IF WATER HAMMER ARRESTORS ARE INSTALLED,
 THEY SHALL BE LOCATED NEAR THE FIXTURE
 IN AN "EFFECTIVE RANGE" NOT IN THE
 CEILING. PDI-WH 210 AND MANUF.
 INSTALLATION INSTRUCTIONS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]