Plan Review Details - Permit 04101257
Plan Review Stops For Permit 04101257
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2007-03-29 Cont ID  
Sent By lmartine Date 2007-03-29 Time 10:44 Rev Time 0.00
Received By lmartine Date 2007-03-29 Time 10:44 Sent To  
Notes
2007-03-29 11:04:31SHUTTER SUBMITTAL

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2007-01-25 Cont ID  
Sent By lmartine Date 2007-01-25 Time 17:38 Rev Time 0.00
Received By lmartine Date 2007-01-25 Time 17:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-04-04 Cont ID  
Sent By alange Date 2006-04-04 Time 13:23 Rev Time 0.50
Received By alange Date 2006-04-04 Time 13:23 Sent To  
Notes
2006-04-04 00:00:00STRUCTURAL REV OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-10-18 Cont ID  
Sent By alange Date 2005-10-18 Time 08:23 Rev Time 1.00
Received By alange Date 2005-10-18 Time 07:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-10-03 Cont ID  
Sent By alange Date 2005-10-03 Time 15:09 Rev Time 0.50
Received By alange Date 2005-10-03 Time 14:03 Sent To  
Notes
2005-10-03 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 4.POZZI FIXED WINDOW MISSING SECOND
 COPY OF NOTICE OF ACCEPTANCE PRODUCT
 APPROVAL AND ALSO MISSING TWO COPIES OF
 THE FOLLOWING STATE PRODUCT APPROVAL.
 NEW NOTES:I MADE TWO COMPLETE SETS OF
 POZZI FIXED WINDOW MIAMI-DADE NOA'S.
 THE STATE PRODUCT APPROVAL SUBMITTED WAS
 NOT VALID FOR THIS PRODUCT.SUBMIT A
 COMPLETED APPICATION FOR LOCAL PRODUCT
 APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-09-19 Cont ID  
Sent By alange Date 2005-09-19 Time 09:38 Rev Time 1.00
Received By alange Date 2005-09-19 Time 08:54 Sent To M
Notes
2005-09-19 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 4.POZZI FIXED WINDOW MISSING SECOND
 COPY OF NOTICE OF ACCEPTANCE PRODUCT
 APPROVAL AND ALSO MISSING TWO COPIES OF
 THE FOLLOWING STATE PRODUCT APPROVAL.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5.PLEASE SIGN OWNER/AGENT ON ENERGY
 CALCS.SIGN BOTH COPIES.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-05-26 Cont ID  
Sent By alange Date 2005-05-26 Time 09:26 Rev Time 2.00
Received By alange Date 2005-05-26 Time 07:26 Sent To  
Notes
2005-05-26 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 3.BASED ON SBCCI BUILDING VALUATION
 DATA, THE PROJECT VALUE HAS BEEN
 INCREASED TO $220,413.ADDITIONAL
 PERMIT FEES ARE DUE.
  
 4.PRODUCT APPROVALS REQUIRED FOR ALL
 EXTERIOR DOORS AND WINDOWS
 ALL PRODUCT APPROVALS REQUIRE THE
 FOLLOWING.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 NOTE: A. ENGINEERS IMPACT PROTECTION
 REPORT IS OK.
  
 B.AN APPLICATION WAS SUBMITTED FOR
 SITE SPECIFIC PRODUCT APPROVAL.THE
 APPLICATION WAS NOT COMPLETED.WHAT WAS
 IT FOR?
  
 5.PLEASE SIGN OWNER/AGENT ON ENERGY
 CALCS.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-12-07 Cont ID  
Sent By alange Date 2004-12-07 Time 08:52 Rev Time 2.50
Received By alange Date 2004-12-06 Time 16:48 Sent To Z
Notes
2004-12-07 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.BASED ON SBCCI BUILDING VALUATION
 DATA, THE PROJECT VALUE HAS BEEN
 INCREASED TO $220,413.ADDITIONAL
 PERMIT FEES ARE DUE.
  
 4.PRODUCT APPROVALS REQUIRED FOR ALL
 EXTERIOR DOORS, WINDOWS, IMPACT
 PROTECTION, ROOFING AND STRAPS AND
 TIE-DOWNS.
 ALL PRODUCT APPROVALS REQUIRE THE
 FOLLOWING.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5.PLEASE SIGN OWNER/AGENT ON ENERGY
 CALCS.
  
 6.PLEASE SHOW HOW SMOKE DETECTORS AND
 GFCI OUTLETS WILL COMPLY WITH FBC
 3401.7.1.2.1 FOR THE EXISTING BUILDING.
  
 7.SAFTEY GLAZING REQUIRED FOR WINDOW
 #18FBC 2405.2.1
  
  
 8.1015.2 HEIGHT. GUARDRAILS SHALL
 FORM A VERTICAL PROTECTIVE BARRIER NOT
 LESS THAN 42" HIGH.
 1015.3 OPENINGS. OPEN GUARDRAILS
 SHALL HAVE INTERMEDIATE RAILS OR ORNA-
 MENTAL PATTERNS SUCH AS A 4" DIAMETER
 SPHERE CAN NOT PASS THROUGH. A BOTTOM
 RAIL OR CURB SHALL BE PROVIDED THAT WILL
 REJECT THE PASSAGE OF 2" DIAMETER
 SPHERE.
  
 9. SHOW ATTIC ACCESS COMPLYING WITH
 FBC 2309.6
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-02-14 Cont ID  
Sent By dpalmer Date 2007-02-14 Time 10:49 Rev Time 0.00
Received By dpalmer Date 2007-02-13 Time 16:56 Sent To PC
Notes
2007-02-14 10:50:43ELECTRICAL ROOM SHOWN ON PLANS NOT TO BE USED FOR
 STORAGE AS STATED BY THE PLANS, OWNER AND CONTRACTOR.
 THIS IS AN DEDICATED ELECTRICAL ROOM.
 408.7, 240.24D, 110.26
2007-02-14 07:57:44CALLED MIKE RUSSELL, WAITING FOR NEW PLANS TO BE FAXED,

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-12-21 Cont ID  
Sent By dpalmer Date 2006-12-21 Time 20:08 Rev Time 0.00
Received By dpalmer Date 2006-12-21 Time 19:10 Sent To M
Notes
2006-12-21 20:09:59** UNSAT **
  
 1) NOTE: PLEASE COMPLETE LOAD CALCULATIONS PER
 220.31B.
 PLEASE ALSO SEE UNDER THE MAIN HOUSE CALCULATIONS,
 THERE ARE MANY ITEMS ON OTHER PANEL SCHEDULES FOR LOADS
 WHICH ARE NOT SHOWN PART OF THE MAIN ELECTRICAL LOAD
 CALCULATIONS?
 PLEASE SEE 220.31, A/C HEAT AT 100%, PLEASE SEE 215.5
 ETC.
  
 2) NOTE: PLEASE SEE MISSING EGRESS LIGHT AND CONTROL
 FOR REAR DOOR PER 210.70.
  
 3) NOTE: PLEASE SEE MISSING REAR OUTDOOR GFI RECEPT PER
 210.52E, 210.8
  
 4) NOTE: PLEASE SEE GENERATOR PERMIT HAS NOT BEEN
 ISSUED AT THIS TIME, AND PLANS MAY NOT INDICATE THIS
 UNIT AND EQUIPMENT UNTIL SUCH TIME AS ISSUED AND SHOULD
 BE STATED ON RISER UNDER A SEPARATE PERMIT.
 FBC 106.1.2.
  
 5) NOTE: PLEASE SHOW LOCATIONS OF ELECTRICAL PANELS IN
 ADDITION IF APPLICABLE. PLANS SEEM TO SHOW WHAT APPEARS
 TO BE PANEL LOCATED IN A CLOSET/PANTRY, HOWEVER NOT
 CLEAR. ARE PANELS LOCATED IN OTHER SECTION OF MAIN
 HOUSE? 110.26, 240.24, 408.7 ETC.
  
 6) NOTE: PLEASE SEE 220.3B4 FOR RECESSED LIGHTS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 IF THERE ARE ANY QUESTIONS, OR COMMENTS, PLEASE CALL,
  
 DEWEY PALMER
 561-805-6717

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-10-25 Cont ID  
Sent By dpalmer Date 2006-10-25 Time 20:08 Rev Time 0.00
Received By dpalmer Date 2006-10-25 Time 19:48 Sent To M
Notes
2006-10-25 20:08:31***** UNSAT *******
  
  
 1) NOTE: PLEASE SEE IN ORDER FOR THE SUB CONTRACTORS TO
 TAKE OVER AS DESIGNERS FOR MEP'S THE LETTER FROM THE
 ENGINEER MUST BE DATED WHEN SIGNED AND SEALED, MUST
 ALSO BE CORRECTLY NOTARIZED PER FS 117.05.
 PLEASE PROVIDE LETTER OF CLARIFICATION IF THE
 ARCHITECTURAL WILL REMAIN THE SAME AS ON RECORD SET.
  
 2) NOTE: PLEASE SEE PLANS MAY NOT BE SUBMITTED IN
 PEN/PENCIL OR COLORED PEN. PLANS MUST BE AND SHALL BE
 SUBMITTED AS "DRAFTMANS" QUALITY AND SHALL BE DONE IN A
 MINIMUM OF 1/8" SCALE. PLEASE SEE THE QUALITY OF PLANS
 SHALL BE CLEAR AS THIS IS REQUIRED FOR ALL TRADES FOR
 ALL REVIEWER(S). PLEASE SEE IN NO CASE CAN PLANS BE
 DONE WITH "WHITE-OUT"
 FBC 106.1.3,106.3.5.4,FBC ADMIN SECT.
  
 3) NOTE: PLEASE SEE THE SITE PLAN SUBMITTED IS SHOWING
 A NEW GEN WHICH HAS NOT BEEN PERMITTED OR APPLIED FOR
 UNDER THIS ADDRESS.PLEAS KNOW AT THIS TIME NO GEN IS
 PERMITTED AND WILL BE VERIFIED BY INSPECTOR.
 SUBMIT COMPLETE PACKAGE, PERMIT APPLICATION ETC FOR THE
 GEN.
 106.1.2.
  
 4) NOTE: PLEASE SEE MISSING FOOTER STEEL AS PART OF THE
 GROUNDING ELECTRODE SYSTEM AS REDLINED ON PREVIOUS
 PLANS AND REQUIRED FOR NEW FOOTER STEEL PER 250.50
  
 5) NOTE: PLEASE SEE THAT ALL PLANS CONTAINS THE PRINTED
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR SIAD
 PLANS/ DESIGN.
  
 6) NOTE: PLEASE SEE ALL OF 210.8A
  
 7) NOTE: PLEASE SEE MISSIGN RECEPTS PER 210.52C1
  
  
 ** PLEASE SUBMIT ABOVE AND COMPLETE PLANS AS STATED.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 [email protected]
 561-805-6717
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-09-08 Cont ID  
Sent By dpalmer Date 2005-09-08 Time 07:28 Rev Time 0.33
Received By dpalmer Date 2005-09-07 Time 20:03 Sent To P
Notes
2005-09-08 00:00:00REDLINED 250.50 FOR NEW FOOTER STEEL AND
 COLD WATER PIPE.
 REDLINED, NO EQUIPMENTGROUNDING
 CONDUCTORFROM MAIN GUTTER TO FIRST
 MEANS OF DISCONNECTS.
2005-09-07 00:00:00IN ELEC FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-05-10 Cont ID  
Sent By dpalmer Date 2005-05-10 Time 07:07 Rev Time 0.75
Received By dpalmer Date 2005-05-10 Time   Sent To P
Notes
2005-05-10 00:00:00************* UNSAT 2ND REVIEW ********
  
 PLEASE SEE SOME COMMENTS FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
  
 THESE COMMENTS ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW.
  
 1)NOTE: NOTE #1, NO, PLEASE SEE ALL
 TITLE BLOCKS FOR ARCHITECTUAL FIRM ARE
 STILL MISSING THE REQUIRED LICENSE
 INFORMAITON AS REQUIRED UNDER FAC
 61G1-16.004 AND FS 481.219.
 ONLY THE ARCH'S AR # WAS ADDED.
 PLEASE SEE THIS IS REQUIRED FOR ALL
 SHEETS AND FOR ALL TRADES WHEATHER OR
 NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 2)NOTE: NOTE #2 OK.
  
 3)NOTE: NOTE #3 OK.
  
 4)NOTE: NOTE #4 NO, PLEASE SEE EQUIPMENT
 GROUNDING CONDUCTORS ARE STILL SHOWN
 FROM GUTTER TO MAINS.??
 250.6,250.24
  
 5)NOTE: NOTE #5 NO, PLEASE SEE 220.4B
 FOR RECESSED LIGHTING FIXTURES.
 THESE ARE TO BE SHOWN ABOVE NORMAL
 LIGHTING LOADS.
  
 6)NOTE: NOTE #6 OK.
  
 7)NOTEL NOTE #7 OK.
  
 8)NOTE: NOTE #8 OK.
  
 9)NOTE: NOTE #9 OK, HOWEVER PLEASE SEE
 NEW NOTES FOR GROUNDING AT DEATCHED
 BLDGS NOW THAT SERVICE IS SHOWN.
  
 10)NOTE: NOTE #10 OK, FOUND INRESPONSE
 LETTER, HOWEVER RISER DIAGRAM NEEDS TO
 SHOW THIS AS LTR WILL NOT BE PART OF
 PLANS FOR INSPECTOR.
  
 11)NOTE: NOTE #11 NO, PLEASE SEE
 ADDTIONS TO EXISTING BLDGS AS SET-FORTH
 IN FBC CHAPTER 34 AS PREVIOUSLY NOTED.
 IF MAIN HOUSE IS HAS HISTORIC
 DESIGNATION, THEN MAIN HOUSE WOULD BE
 EXEMPT.
  
 12)NOTE: NOTE #12, NO, PLEASE SEE LOWER
 HALF OF SEAL ON SOME SHEETS IS STILL NOT
 COMING THROUGH COMPLETELY.
  
 13)NOTE: NOTE #13, NO RESPONSE NEEDED,
 BLDG VALUATION ADJUSTED.
  
 14)NOTE: NOTE #14, OK. PLEASE SEE THE
 SAME COMMENT WILL BE IN EFFECT THIS
 REVIEW ALSO AS SHEETS WILL BE REQUIRED
 TO BE CHANGED OUT.
  
 15)NOTE: NOTE #15 NO RESPONSE NEEDED,
 HOWEVER, PLEASE SEE ZONING COMMENTS.
  
 NEW NOTES:
  
 1)NOTE: PLEASE SEE SINCE SERVICE
 LOCATIONS ARE NOW SHOWN, PLEASE SEE
 GROUNDING ELECTRODE SYSTEM AT DEATCHED
 BLDG NEEDS TO BE SHOWN PER 250.32,
 250.50. PLEASE SHOW/INCLUDE NEW FOOTER
 STEELAND COLD WATER (IF METAL) AT
 DETACHED NEW ADDTION/HOUSE.
  
 2)NOTE: PLEASE SEE NEW GUTTER IS NOW
 SHOWN AS 14"X14'X4', PLEASE SEE THE
 MAINS ARE SHOWN ABOVE THIS EQUIPMENT.
 PLEASE SEE 110.26, GUTTER SHALL NOT
 EXTEND MORE THAN 6" FROM MAINS SHOWN.
 PLEASE SEE THIS IS A NOTE GIVEN PER
 DESIGN SHOWN.
  
 3)NOTE: PLEASE SEE KITCHEN ISLAND
 RECEPTS. GFI SERVING COUNTERSPACE MAY
 NOT EXTEND MORE THAN 6" OUT AND 6" DOWN
 TO GFI TO SERVE THAT COUNTERSPACE.
 PLEASE SEE COUNTER SHOWN.
 PLEASE ALSO SEE OTHER COUNTERSPACE WHICH
 APPEARS TO BE A PENINSULAR COUNTERSPCE
 W/OUT ANY GFI.
 PLEASE SEE 2210.52C1-5
  
 4)NOTE: PLEASE CLARIFY WHICH CIRCUITS
 ARE FEEDING OLD/ORIG HOUSE.??
 215.5
  
 5)NOTE: PLEASE SEE ATTACHED COPY OF FS
 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONALS AND PLANS WITH REPEAT
 COMMENTS.
 THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASEDO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-11-18 Cont ID  
Sent By dpalmer Date 2004-11-18 Time 06:25 Rev Time 0.75
Received By dpalmer Date 2004-11-18 Time 06:15 Sent To P
Notes
2004-11-18 00:00:00************ UNSAT **************
  
 1)NOTE: PLEASE INCLUDE ALL INFORMATION
 ON TITLE BLOCKS FOR ARCH FIRM AS
 REQUIRED UNDER FAC 61G1-16.004 AND FS
 481.219. THIS IS REQUIRED ON ALL SHEETS
 AND FOR ALL TRADES WHEATHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 2)NOTE: PLEASE SEE NOE SEC'S ARE SHOWN
 ON RISER FROM METER TO GUTTER?
 310.16, 240.4, 215.5 ETC
  
 3)NOTE: PLEASE INDICATE SIZE OF METER
 CAN. 215.5
  
 4)NOTE: PLEASE SEE 250.6,250.24.
 EQUIPMENT GROUNDING CONDUCTORS ARE ONLY
 INSTALLED AFTER THE FIRST MEANS OF
 DISCONNECT.
  
 5)NOTE: PLEASE SUBMIT COMPLETED LOAD
 CALCUALTIONS PER 220.31B
 PLEASE SHOW LT LOAD ETC.
 PLEASE SEE 220.4B4 FOR ANY RECESSED
 LTS.
  
 6)NOTE: PLEASE SEE PANEL SCHEDULE "A"
 AND AWG FOR ALL ON RIGHT-HAND SIDE.??
 MISPRINT?
  
 7)NOTE: PLEASE SEE 2002 NEC 210.12 FOR
 REQUIREMENTS OF ARC FAULT PROTECTION.
 PANEL SCHEDULE AND CIRCUITING ONLY
 INDICATES FOR RECEPTS.
 SEE 2002 NEC, WHICH REQUIRES ALL
 "OUTLETS".
  
  
 8) NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 9)NOTE: PLEASE VERIFY ENTIRE SERVICE AND
 LOCATION??? PLANS SHOW SERVICE ON
 "DETACHED" GARAGE.
 PLEASE SEE PANELS IN HOUSE WOULD REQUIRE
 MAINS ETC. 225.31
 PLEASE SHOW GROUNDING PER 250.32.
  
 10)NOTE: PLEASE CLARIFY WHICH PANEL FEED
 GARAGE?
 215.5
  
 11)NOTE:PLEASE SEE FBC CHAPTER 34 FOR
 ADDITIONS TO EXISTING DWELLINGS.
 3401.7.1.2.1
 PLEASE PROVIDE COMPLETE LAYOUT OF
 EXISTING. PLEASE SHOW EITHER ALL
 EXISTING LOCATIONS FOR GFI'S AND SD'S OR
 SHOW ALL LOCATIONS TO BE "INSTALLED
 NEW". ALL SD'S ARE REQUIRED TO BE TIED
 INTO NEW SD'S IN NEW ADDITION.
 PLEASE SEE NFPA-72 8-1.4.1.6.2,8-1.4.2
 FOR LOCATIONS.
  
 12)NOTE: PLEASE BE SURE "RAISED SEAL" IS
 CLEAR AND VISABLE WITH ALL INFORMATION
 REQUIRED ON SEAL.
 FS 471.025
  
 13)NOTE: PLEASE SEE POSSIBLE BUILDING
 COMMENTS FOR VALUE.FBC 104.6.5
  
 14) NOTE: PLEASE REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 ONE SET OF OLD SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE ONLY.
  
 15)NOTE: PLEASE SEE COMMENTS FROM OTHER
 REVIEWERS WHICH MAY HAVE AFFECT ON
 ELECTRICAL PLANS.
 PLEASE SEE ZONING COMMENTS FOR REMOVAL
 OF ANY KITCHEN IN EXSITING DWELLING.
 THIS MAY BE INCLUDED ON THIS PERMIT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS ,
 PLEASE DO NOT HESITATE IN CONTACTING
 ME.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2005-05-21 Cont ID  
Sent By pschmitz Date 2005-05-21 Time 12:07 Rev Time 0.00
Received By pschmitz Date 2005-05-21 Time 12:07 Sent To P
Notes
2005-05-21 00:00:00CHANGES ON GAS, AS PER ARCHITECT OF
 RECORD MR CHILDS.

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2007-03-21 Cont ID  
Sent By adarroug Date 2007-03-21 Time 16:58 Rev Time 0.00
Received By adarroug Date 2007-03-21 Time 16:58 Sent To M
Notes
2007-03-21 16:58:27TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2007-03-15 Cont ID  
Sent By adarroug Date 2007-03-15 Time 11:18 Rev Time 0.00
Received By adarroug Date 2007-03-15 Time 11:18 Sent To B
Notes
2007-03-15 11:19:15TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2007-02-27 Cont ID  
Sent By adarroug Date 2007-02-27 Time 15:53 Rev Time 0.00
Received By adarroug Date 2007-02-27 Time 15:53 Sent To M
Notes
2007-02-27 15:53:50TO "M"BOX

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2007-02-13 Cont ID  
Sent By adarroug Date 2007-02-13 Time 10:24 Rev Time 0.00
Received By adarroug Date 2007-02-13 Time 10:24 Sent To E
Notes
2007-02-13 10:24:47TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2007-02-09 Cont ID  
Sent By adarroug Date 2007-02-09 Time 16:25 Rev Time 0.00
Received By adarroug Date 2007-02-09 Time 16:25 Sent To M
Notes
2007-02-09 16:26:35TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2006-12-17 Cont ID  
Sent By adarroug Date 2006-12-17 Time 16:00 Rev Time 0.00
Received By adarroug Date 2006-12-17 Time 15:59 Sent To E
Notes
2006-12-17 16:00:19TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2006-10-23 Cont ID  
Sent By adarroug Date 2006-10-23 Time 11:36 Rev Time 0.00
Received By adarroug Date 2006-10-23 Time 11:35 Sent To E
Notes
2006-10-23 11:36:32TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-10-13 Cont ID  
Sent By adarroug Date 2006-10-13 Time 11:54 Rev Time 0.00
Received By adarroug Date 2006-10-13 Time 11:54 Sent To Z
Notes
2006-10-13 11:54:51TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-03-24 Cont ID  
Sent By spalmer Date 2006-03-24 Time 17:30 Rev Time 0.00
Received By spalmer Date 2006-03-24 Time 17:30 Sent To B
Notes
2006-03-24 00:00:00TO ALANGE

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-10-05 Cont ID  
Sent By adarroug Date 2005-10-05 Time 18:04 Rev Time 0.00
Received By adarroug Date 2005-10-05 Time 18:04 Sent To B
Notes
2005-10-05 00:00:00TO "ALANGE" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-09-26 Cont ID  
Sent By adarroug Date 2005-09-26 Time 09:25 Rev Time 0.00
Received By adarroug Date 2005-09-26 Time 09:25 Sent To M
Notes
2005-09-26 00:00:00TO "TGORDON" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-09-06 Cont ID  
Sent By adarroug Date 2005-09-06 Time 09:30 Rev Time 0.00
Received By adarroug Date 2005-09-06 Time 09:30 Sent To E
Notes
2005-09-06 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-08-29 Cont ID  
Sent By adarroug Date 2005-08-29 Time 14:32 Rev Time 0.00
Received By adarroug Date 2005-08-29 Time 14:32 Sent To  
Notes
2005-08-29 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-05-09 Cont ID  
Sent By adarroug Date 2005-05-09 Time 10:27 Rev Time 0.00
Received By adarroug Date 2005-05-09 Time 10:27 Sent To E
Notes
2005-05-09 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-04-29 Cont ID  
Sent By adarroug Date 2005-04-29 Time 11:08 Rev Time 0.00
Received By adarroug Date 2005-04-29 Time 11:08 Sent To Z
Notes
2005-04-29 00:00:00TO "Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-11-17 Cont ID  
Sent By mjacobs Date 2004-11-17 Time 10:39 Rev Time 0.00
Received By mjacobs Date 2004-11-17 Time 10:39 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2004-10-29 Time   Rev Time 0.00
Received By csiegber Date 2004-10-29 Time 14:23 Sent To  
Notes
2004-10-29 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 10 Status P Date 2007-03-27 Cont ID  
Sent By tgordon Date 2007-03-27 Time 10:12 Rev Time 0.20
Received By tgordon Date 2007-03-27 Time 10:12 Sent To  
Notes
2007-03-27 10:12:47REVISION TO MECHANICAL PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 9 Status F Date 2007-03-27 Cont ID  
Sent By tgordon Date 2007-03-27 Time 09:03 Rev Time 0.30
Received By tgordon Date 2007-03-27 Time 09:02 Sent To  
Notes
2007-03-27 09:06:08** MECHANICAL REVISION **
 *** DENIED ***
 1) NEED TO PROVIDE FOR RETURN AIR TO DEN AND DINING
 ROOM, SEE 2004 FBC/R M1602.4.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2007-02-28 Cont ID  
Sent By tgordon Date 2007-02-28 Time 09:40 Rev Time 0.25
Received By tgordon Date 2007-02-28 Time 09:40 Sent To  
Notes
2007-02-28 09:40:40REVISION TO MECHANICAL PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 7 Status F Date 2007-02-12 Cont ID  
Sent By tgordon Date 2007-02-12 Time 13:57 Rev Time 0.45
Received By tgordon Date 2007-02-12 Time 13:57 Sent To  
Notes
2007-02-12 14:02:02MECHANICAL REVISION
 *** DENIED ***
 1) SEE ON REVISED MECHANICAL PLANS YELLOW HIGH LIGHTED
 SUPPLY AIR DUCTS AND GRILLS THAT NEED TO BE SIZED,
 PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2006-12-22 Cont ID  
Sent By tgordon Date 2006-12-22 Time 15:16 Rev Time 0.30
Received By tgordon Date 2006-12-22 Time 15:16 Sent To P
Notes
2006-12-22 15:19:40*** DENIED ***
 1) MECHANICAL PLANS ARE FADED AND DIFFICULT TO SEE,
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY.
 PER 2004 FBC 106.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
 .

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2006-10-26 Cont ID  
Sent By tgordon Date 2006-10-26 Time 08:38 Rev Time 0.45
Received By tgordon Date 2006-10-26 Time 08:38 Sent To P
Notes
2006-10-26 08:50:58MECHANICAL REVISION
 *** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTES #1AND 2, PLEASE
 CORRECT.
  
 2) ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN. PER FBC 104.2.1 .
  
 3) PLEASE SHOW THE EQUIPMENT LISTING ON THE REVISED
 MECH. PLANS.
  
 4) PLEASE SHOW THE SIZE OF THE RETURN AIR DUCTS (FLEX)
 TO THE TWO 14X14 RETURN GRILLS IN THE MASTER BEDROOM
 AND THE HALLWAY.
  
 5) PLEASE PROVIDE RETURN AIR TO THE DINING ROOM AND
 DEN, PER 2001 FBC/M 601.4. (SEE NOTE #6).
  
 6) BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-09-26 Cont ID  
Sent By tgordon Date 2005-09-26 Time 11:20 Rev Time 0.20
Received By tgordon Date 2005-09-26 Time 11:20 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2005-09-19 Cont ID  
Sent By tgordon Date 2005-09-19 Time 14:07 Rev Time 0.30
Received By tgordon Date 2005-09-19 Time 14:07 Sent To  
Notes
2005-09-19 00:00:00*** DENIED ***
 1) NEED COMBUSTION AIR CALCULATIONS FOR
 DRYER.
 2) MAKE UP AIR CAN NOT COME FROM ROOF
 TOPS. PER 2001 FBC/M CH.13 609.1.ABC.1
 (2).
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-05-24 Cont ID  
Sent By pkrauss Date 2005-05-24 Time 06:47 Rev Time 0.30
Received By pkrauss Date 2005-05-24 Time 06:47 Sent To B
Notes
2005-05-24 00:00:00DENIED:2ND REQUEST
 1.TITLE BLOCK IS TO REFLECT LICESNE
 NUMBER AN PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT IN ACCORDANCE WITH
 FAC 61G1-16.004 (2)&(6), FS 481.219.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-11-29 Cont ID  
Sent By pkrauss Date 2004-11-29 Time 17:42 Rev Time 0.45
Received By pkrauss Date 2004-11-29 Time 17:23 Sent To B
Notes
2004-11-29 00:00:00DENIED:
 1.PROVIDE MANUFACTURER SUBMITTAL DATA
 FOR THE FIREPLACE.
  
 2.PROVIDE INFORMATION ON THE GAS
 DRYER, I.E. COMBUSTION AIR & MAKE-UP AIR
 PER 2001 FBC(M) CHAPTER 7.
  
 3.SEE ALSO COMMENT #1 BY DEWEY PALMER,
 ELECTRICAL PLAN REVIEW.
  
 PLANS ARE OTHERWISE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop P PLUMBING
Rev No 6 Status P Date 2007-01-09 Cont ID  
Sent By jleech Date 2007-01-09 Time 09:44 Rev Time 0.00
Received By jleech Date 2007-01-09 Time 09:44 Sent To  
Notes
2007-01-09 09:45:04PLUMBING AS-BUILDS OK

Review Stop P PLUMBING
Rev No 5 Status F Date 2007-01-06 Cont ID  
Sent By jleech Date 2007-01-06 Time 12:57 Rev Time 0.00
Received By jleech Date 2007-01-06 Time 12:57 Sent To B
Notes
2007-01-06 13:06:50DENIED;
 1. AS BUILTS DONOT MATCH FLOOR PLANS.
 2.AUTOMATIC CLOTHES WASHER CAN NOT DISCHARGE THRU THE
 BATHROOM GROUPSEC 909.1
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 4 Status F Date 2006-11-02 Cont ID  
Sent By jleech Date 2006-11-02 Time 15:21 Rev Time 0.00
Received By jleech Date 2006-11-02 Time 15:02 Sent To B
Notes
2006-11-02 15:15:13DENIED;
 1. PERSON RESPONSABLEFOR DRAWING TO SIGN, PRINT AND
 DATE PLANS. NO PEN OR PENCIAL TO BE USED ON PLANS.
 2. FLOOR PLAN HAS CHANGED, A NEW FLOOR PLAN SHOULD BE
 SUBMITED WITH AS BUILTS.
 3.GAS RISER DIAGRAM WAS APPROVED UNDER ARCHITECTAL PLAN
 NOT SHOWN ON AS BUILT.
 4.PLUMBING AS BUILT SANITARY NOT TO CODE. AUTOMATIC
 CLOTHES WASHER MUST DISCHARGE DOWN STREAM OF THE
 BATHROOM GROUP. SEE SECTION
 909.1 WET VENT.
 5.SIZE ALL PIPES WATER AND SANITARY THAT ARE ON THE
 DRAWINGS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-09-09 Cont ID  
Sent By jleech Date 2005-09-09 Time 12:49 Rev Time 0.50
Received By jleech Date 2005-09-09 Time 12:49 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-05-21 Cont ID  
Sent By pschmitz Date 2005-05-21 Time 12:10 Rev Time 0.00
Received By pschmitz Date 2005-05-21 Time 12:10 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-11-23 Cont ID  
Sent By kstevens Date 2004-11-23 Time 06:46 Rev Time 0.75
Received By kstevens Date 2004-11-23 Time 06:46 Sent To M
Notes
2004-11-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 E. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 G. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 H. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 2) ALL GAS APPLIANCES SHALL BE APPROVED
 FOR RESIDENTIAL USE ONLY. MANUFACTURE
 INSTALLATION INFORMATION WILL WILL BE
 REQUIRED AT TIME OF FINAL AND FINAL
 APPROVAL WILL BE BY THE FIELD
 INSPECTOR.
 NO COMMERCIAL GAS APPLIANCES APPROVED.
 3) SHT P.3 PLUMBING NOTES #13 AIR
 CHAMBERS ARE NOT APPROVED. DELETE
 REFERENCE. SECTION 104.2.1
 4) MINIMUM INFORMATION ON THE TITLE
 BLOCK FOR THE ARCHITECT REQUIRES THE
 FIRM LICENSE NUMBER. 61G1-16.004(2) AND
 FS 481.219
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status F Date 2006-10-19 Cont ID  
Sent By mmclean Date 2006-10-19 Time 14:40 Rev Time 0.00
Received By mmclean Date 2006-10-19 Time 14:40 Sent To I
Notes
2006-10-19 14:42:22DENIED,
 1. THE SITEPLAN SHOWS A GENERATOR, NEED CLARIFICATION
 IF THE REVISION IF FOR SUCH PERMIT.
 2. NEED TO PULL A SEPARATE PERMIT FOR GENERATOR.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 3 Status P Date 2005-09-02 Cont ID  
Sent By mmclean Date 2005-09-02 Time 15:37 Rev Time 0.00
Received By mmclean Date 2005-09-02 Time 15:37 Sent To I
Notes
2005-09-02 00:00:00NOTE: MAX. HEIGHT ALLOWED WITH CHIMNEY
 IS 33FT. SEE PLANS REFLECTING THIS
 HEIGHT.

Review Stop Z ZONING
Rev No 2 Status F Date 2005-05-06 Cont ID  
Sent By mmclean Date 2005-05-06 Time 18:10 Rev Time 0.00
Received By mmclean Date 2005-05-06 Time 18:10 Sent To I
Notes
2005-05-06 00:00:00DENIED,
 1. OVER THE HEIGHT ALLOWED OF 33FT.
 2. SOUTH ELEVATION SHOWS 34+FT AND NORTH
 ELEVATION SHOWS 35+FT.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2004-11-16 Cont ID  
Sent By mmclean Date 2004-11-16 Time 11:48 Rev Time 0.00
Received By mmclean Date 2004-11-16 Time 11:48 Sent To I
Notes
2004-11-16 00:00:00NOTE: DENIED, CHIMNEY OVER HEIGHT
 ALOWED. MUST REDUCE BY 2FT TO 33FT.
  
 ***NO KITCHEN ALLOWED IN EXISTING
 HOUSE***