Plan Review Details - Permit 04101253
Plan Review Stops For Permit 04101253
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-12-06 Cont ID  
Sent By alange Date 2004-12-06 Time 15:59 Rev Time 1.50
Received By alange Date 2004-12-06 Time 07:37 Sent To  
Notes
2004-12-06 00:00:00DENIED
  
 1.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2.SUBMIT 2 COPIES OF A SURVEY OR SITE
 PLAN SHOW EXISITNG BUILDINGS AND NEW
 CONSTRUCTION.
  
 3.SUBMIT 2 COPIES OF MANUAL J ENERGY
 CALCS.
  
 4.SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR EXTERIOR DOORS, WINDOWS,
 IMPACT PROTECTION, ROOFING AND TRAPS AND
 TIE-DOWNS.
 ALL PRODUCT APPROVALS REQUIRE THE
 FOLLOWING.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5.FBC 2405.1 SAFTEY GLAZING REQUIRED
 OVER TUB AREA. SHOW ON PLANS.
  
 6.SHOW HOW SMOKE DETECTOR AND GFCI
 OUTLETS WILL COMPLY WITH FBC
 3401.7.1.2.1
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-11-12 Cont ID  
Sent By dpalmer Date 2004-11-12 Time 19:46 Rev Time 0.40
Received By dpalmer Date 2004-11-12 Time 19:46 Sent To P
Notes
2004-11-12 00:00:00*********** UNSAT **********
  
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2)NOTE:PLEASE VERIFY SIZE OF HEAT
 SHOWN,
 SHOWS 8KW. PLEASE SEE THIS MAY BE
 UNDER-SIZED FOR SQ FT OF DWELLING.
  
 3)NOTE: PLEASE SEE FBC CHAPTER 34
 3401.7.1.2.1/ 3401.7.2.6 FOR ADDITIONS
 AND REMODELS OF EXISTING DWELLINGS.
 PLEASE SHOW EXSITNG ELECTRICAL TO MEET
 2002 NEC .
 PLEASE SHOW EITHER ALL NEW OR EXSITNG
 SD'S WHICH ARE REQUIRED TO MEET NFPA-72
 8-1.4.1.6.2
  
  
 4)NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETED SETS FOR REVIEW AND STAMPING.
 ONE COPY OF OLD SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE ONLY.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-11-12 Cont ID  
Sent By csiegber Date 2004-11-12 Time 15:58 Rev Time 0.00
Received By csiegber Date 2004-11-12 Time 15:58 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-10-29 Cont ID  
Sent By csiegber Date 2004-10-29 Time 14:29 Rev Time 0.00
Received By csiegber Date 2004-10-29 Time 14:29 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-11-29 Cont ID  
Sent By pkrauss Date 2004-11-29 Time 15:52 Rev Time 0.35
Received By pkrauss Date 2004-11-29 Time 15:30 Sent To B
Notes
2004-11-29 00:00:00DENIED:
 1.PROVIDE ENERGY AND MANUAL J
 CALCULATIONS IN ACCORDANCE WITH 2001 FBC
 CHAPTER 13 SUB-CHAPTER 600.
  
 2.PROVIDE EQUIPMENT SCHEDULE.
 INDICATE IF THE EQUIPMENT IS NEW OR
 EXISTING.
  
 3.PROVIDE PLAN INDICATE ALL NEW DUCT
 AND GRILLE SIZE/LAYOUT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-11-23 Cont ID  
Sent By kstevens Date 2004-11-23 Time 05:12 Rev Time 0.25
Received By kstevens Date 2004-11-23 Time 05:12 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By csiegber Date 2004-10-29 Time 14:29 Rev Time 0.00
Received By mmclean Date 2004-11-12 Time 12:14 Sent To I
Notes
2004-11-12 00:00:00NOTE: DENIED, NEED TO PROVIDE TWO COPY
 OF SURVEY SHOWING THE ADDITION WITH
 SETBACKS.CALLED CONTR.