| Plan Review Stops For Permit 04101196 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2005-01-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2005-01-28 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2005-01-28 |
Time |
13:39 |
Sent To |
|
|
| Notes |
| 2005-01-28 00:00:00 | PROVISO | | | | | | SUBMIT TWO COPIES OF AN INSTALLATION | | | SCHEDULE FOR THE STORM PANELS SPECIFYING | | | THE MOUNT TYPE, ANCHOR TYPE AND ANCHOR | | | SPACING BEFORE INSTALLATION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2005-01-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2005-01-10 |
Time |
14:55 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2005-01-10 |
Time |
14:55 |
Sent To |
|
|
| Notes |
| 2005-01-10 00:00:00 | DENIED | | | | | | 1) SUBMIT THE STATE PRODUCT APPROVAL FOR | | | THE 16'X 8' (4) PANEL SLIDING GLASS | | | DOOR. THE ONE SUBMITTED IS FOR A THREE | | | PANEL DOOR. | | | | | | 2) THE PRODUCT APPROVALS SUBMITTED FOR | | | THE WINDOW MULLIONS ARE LIMITED IN SIZE | | | AND WILL NOT WORK IN THE TWO LARGE | | | OPENINGS AT THE LIVING ROOM AND MASTER | | | BEDROOM. SUBMIT THE APPROPRIATE PROD. | | | APPROVALS. | | | | | | 3) THE PRODUCT APPROVAL DRAWINGS FOR THE | | | 9' AND 16' WIDE GARAGE DOORS HAVE DESIGN | | | PRESSURES LOWER THAN THE REQUIRED | | | PRESSURES LISTED ON THE PLANS. | | | | | | 4) SUBMIT TWO COPIES OF THE PRODUCT | | | APPROVAL, KEY PLAN AND INSTALLATION | | | SCHEDULE FOR THE STORM PANELS. THE | | | FLORIDA PRODUCT APPROVAL THAT WAS | | | SUBMITTED IS FOR WEATHER GUARD, INC. AND | | | THE ATTACHED INFORMATION IS FOR | | | WEATHERGUARD. THESE ARE TWO DIFFERENT | | | COMPANIES. | | | | | | 5) THE GLAZING PRODUCTS SUBMITTED WITH | | | AAMA CERTIFICATION HAVE NOT BEEN TESTED | | | FOR LARGE MISSLE IMPACT AND ARE REQUIRED | | | TO BE PROTECTED WITH STORM PANELS. | | | | | | 6) THE ID MARK (F-) IN THE FOOTING | | | SCHEDULE SHOULD BE (F-10). PLEASE | | | CORRECT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-12-02 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2004-12-02 |
Time |
09:54 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2004-12-02 |
Time |
07:15 |
Sent To |
|
|
| Notes |
| 2004-12-02 00:00:00 | DENIED | | | | | | 1)IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | | COPY OF RECEIPT SUBMITTED TO CITY OF | | | WEST PALM BEACH BUILDING DEPARTMENT, | | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | | | 2) SPECIFY THE BOTTOM CORD LIVE LOAD ON | | | THE PLANS. SEE FBC TABLE 1604.1 FOR | | | REQUIREMENTS. | | | | | | 3) THE FOOTING SCHEDULE ON A1 IS MISSING | | | THE F-10 MARK. | | | | | | 4) ON SHEET A2 SPECIFY SAFETY GLAZING | | | FOR THE WINDOWS AT THE BATH TUB IN THE | | | LADIES SUITE AND BESIDE THE SHOWER IN | | | HIS BATH. | | | | | | 5) A DETAIL 5/A5 IS SPECIFIED ON THE | | | PLANS ON A5 AND A6, BUT THE DETAIL IS | | | NOT GIVEN. | | | | | | 6) SEVERAL OF THE DETAILS CALLED OUT IN | | | THE ROOF PLAN ON A6 DO NOT CORRESPOND | | | WITH THE DETAILS SPECIFIED ON A5. SEE | | | MARKS ON THE PLANS. | | | | | | 7) PLEASE CLARIFY THE CONNECTION FOR THE | | | THREE GIRDERS THAT MEET AT THE STEEL | | | COLUMN SHOWN IN DETAIL 9 ON A5. THE | | | BOTTOM OF TWO GIRDERS ARE AT 14' AND THE | | | BOTTOM OF THE THIRD IS 10'. | | | | | | 8) THE ENERGY CALCULATION FORM IS | | | REQUIRED TO BE SIGNED AND DATED BY THE | | | OWNER/AGENT PER FBC CHAPTER 13. | | | | | | 9)PRODUCT APPROVALS SUBMITTED | | | WITH PERMIT APPLICATION AFTER OCTOBER 1, | | | 2003 ARE REQUIRED TO COMPLY WITH THE | | | FLORIDA PRODUCT APPROVAL SYSTEM. FOR | | | INFORMATION PLEASE SEE THE STATE WEBSITE | | | AT WWW.FLORIDABUILDING.ORG. PRODUCTS | | | WITH STATEWIDE APPROVAL ARE REQUIRED TO | | | BE SUBMITTED WITH A COVER SHEET THAT | | | LISTS THE PRODUCT IDENTITY NUMBER FROM | | | THE STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 10) ALL PRODUCT APPROVAL INFORMATION | | | SUBMITTED MUST BE CLEAR AND LEGIBLE. | | | WHEN MULTIPLE PRODUCTS OR MODELS ARE | | | LISTED IN A SINGLE PRODUCT APPROVAL THE | | | ONES THAT ARE BEING USED MUST BE | | | SPECIFIED AND THE INSTALLATION DRAWINGS | | | AND DESIGN PRESSURES FOR THOSE ITEMS | | | MUST BE SUBMITTED. | | | | | | 11) SUBMIT STATE/LOCAL PRODUCT APPROVALS | | | FOR THE ARCHED TOP FIXED GLASS WINDOWS | | | AND THE STRUCTURAL MULLIONS. | | | | | | 12) SUBMIT AN ACCURATE KEY PLAN AND | | | INSTALLATION SCHEDULE FOR THE STORM | | | PANELS, LISTING ONLY THE OPENINGS THAT | | | WILL BE SHUTTERED. THE PRODUCT APPROVALS | | | THAT WERE SUBMITTED ARE FOR IMPACT | | | WINDOWS, WHICH INDICATES THAT ONLY THE | | | GLAZED DOORS WOULD BE SHUTTERED. | | | | | | IF YOU HAVE QUESTIONS PLEASE CALL; | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2006-03-28 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-03-28 |
Time |
17:48 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2006-03-28 |
Time |
17:48 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2006-03-20 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-03-20 |
Time |
08:52 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2006-03-20 |
Time |
08:42 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2006-03-14 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-03-14 |
Time |
13:41 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2006-03-14 |
Time |
13:36 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2006-01-31 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-01-31 |
Time |
13:19 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2006-01-31 |
Time |
12:46 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2004-12-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-12-28 |
Time |
13:21 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2004-12-28 |
Time |
13:21 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-11-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-11-12 |
Time |
12:58 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-11-12 |
Time |
12:58 |
Sent To |
M |
|
| Notes |
| 2004-11-12 00:00:00 | ********** UNSAT *************** | | | | | | | | | 1 )NOTE: PLEASE LIST THE REQ'D ARC | | | FAULT PROTECTED CURCUIT(S) ON PANEL | | | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" | | | IN BEDROOMS ARE TO BE PROTECTED , | | | INCLUDING, LTS, RECEPTS, SD'S ETC. | | | 2002 NEC 210.12 | | | PLANS ONLY REFLECT RECEPTS. | | | | | | 2)NOTE: PLEASE SEE MISSING SD'S INSIDE | | | AND OUTSIDE LIB/BEDRM. THIS RM WHICH | | | CONTAINS A CLOSET IS CONSIDEREDTO BE | | | AN ADAPTABLE BEDRM. | | | PLEASE ALSO SEE LOCATION OF SD IN | | | MASTER | | | BEDRM SUITE, PLANS SHOWS TWO SD'S IN | | | BEDRM? NONE OUTSIDE. | | | NFPA-72 8-1.4.1.6.2 | | | PLEASE SEE 8-1.4.2 FOR SD LOCATIONS, | | | 3' MIN AWAY FROM BATHS. | | | | | | 3)NOTE: PLEASE SEE 210.52 FOR RECEPT | | | SPACING, 2' OF WALL SPACING. | | | | | | 4)NOTE: PLEASE SEE MISSING GFI RECEPT IN | | | MECH RM. 210.63 | | | PLEASE ALSO SEEGFI FOR COND UNIT. | | | | | | 5)NOTE: PLEASE SEE MISSING EGRESS LT | | | REQUIRED FROM CABANA BATH TO OUTSIDE. | | | 210.70 | | | | | | | | | PLEASE SEE ONE SET OF PLANS HAS SOME OF | | | THE ABOVE ITEMS REDLINED ON PLANS. | | | | | | PLEASE REMOVE ALLOLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2006-03-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-03-28 |
Time |
12:31 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-03-28 |
Time |
12:31 |
Sent To |
E |
|
| Notes |
| 2006-03-28 00:00:00 | TO "BTROBAUG" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2006-01-31 |
|
|
Cont ID |
|
| Sent By |
ptjomsto |
Date |
2006-01-31 |
Time |
08:41 |
Rev Time |
0.00 |
| Received By |
ptjomsto |
Date |
2006-01-31 |
Time |
08:41 |
Sent To |
|
|
| Notes |
| 2006-01-31 00:00:00 | REV/ELEC GIVEN TO BILL TROBAUGH |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-01-18 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-01-18 |
Time |
11:05 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2005-01-18 |
Time |
11:05 |
Sent To |
B |
|
| Notes |
| 2005-01-18 00:00:00 | TO "ROB MCD" DESK/RESUB. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2004-12-27 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2004-12-27 |
Time |
15:09 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2004-12-27 |
Time |
15:07 |
Sent To |
E |
|
| Notes |
| 2004-12-27 00:00:00 | TO "DP" DESK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-12-20 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2004-12-20 |
Time |
14:56 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2004-12-20 |
Time |
16:38 |
Sent To |
Z |
|
| Notes |
| 2004-12-20 00:00:00 | SENT TO "Z" BOX. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-12-02 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2004-12-02 |
Time |
09:54 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2004-10-28 |
Time |
14:21 |
Sent To |
|
|
| Notes |
| 2004-11-08 00:00:00 | TO SFD RACK/E | | 2004-10-28 00:00:00 | TO Z |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2005-01-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-01-10 |
Time |
06:41 |
Rev Time |
0.25 |
| Received By |
pkrauss |
Date |
2005-01-10 |
Time |
06:40 |
Sent To |
B |
|
| Notes |
| 2005-01-10 00:00:00 | NO CHANGES ON THE RESUBMITTAL |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2004-11-18 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2004-11-18 |
Time |
07:58 |
Rev Time |
0.45 |
| Received By |
drunnels |
Date |
2004-11-18 |
Time |
07:57 |
Sent To |
P |
|
| Notes |
| 2004-11-18 00:00:00 | PAT RAFTER |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2005-01-01 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-01-01 |
Time |
07:30 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2005-01-01 |
Time |
07:30 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2004-11-22 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-11-22 |
Time |
05:30 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2004-11-22 |
Time |
05:30 |
Sent To |
B1 |
|
| Notes |
| 2004-11-22 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SHT A-4 SANITARY RISER DIAGRAM DOES | | | NOT REFLECT THE FLOOR PLAN. THE RISER | | | DIAGRAM SHOWS TWO SHOWERS IN BATH #2, | | | BUT THE FLOOR PLAN SHOWS ONLY ONE. THE | | | TUB IN BATH #3 IS ON THE RIGHT SIDE OF | | | THE W/C ON THE FLOOR PLAN, BUT IS SHOWN | | | NEAR THE LAV ON THE RISER DIAGRAM. SHOW | | | ALL PIPE SIZES ON THE RISER DIAGRAM, | | | MANY SECTIONS IN THE MASTER BATH DO NOT | | | HAVE PIPE SIZES. SECTION 104.2.1. | | | | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2004-12-27 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2004-11-06 |
Time |
13:16 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2004-11-06 |
Time |
13:16 |
Sent To |
I |
|
| Notes |
| 2004-11-06 00:00:00 | NOTE: MUST PULL SEPERATE PERMIT FOR | | | POOL/DECK |
|
|