Plan Review Details - Permit 04101196
Plan Review Stops For Permit 04101196
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-01-28 Cont ID  
Sent By rmcdouga Date 2005-01-28 Time 13:39 Rev Time 0.00
Received By rmcdouga Date 2005-01-28 Time 13:39 Sent To  
Notes
2005-01-28 00:00:00PROVISO
  
 SUBMIT TWO COPIES OF AN INSTALLATION
 SCHEDULE FOR THE STORM PANELS SPECIFYING
 THE MOUNT TYPE, ANCHOR TYPE AND ANCHOR
 SPACING BEFORE INSTALLATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-01-10 Cont ID  
Sent By rmcdouga Date 2005-01-10 Time 14:55 Rev Time 0.00
Received By rmcdouga Date 2005-01-10 Time 14:55 Sent To  
Notes
2005-01-10 00:00:00DENIED
  
 1) SUBMIT THE STATE PRODUCT APPROVAL FOR
 THE 16'X 8' (4) PANEL SLIDING GLASS
 DOOR. THE ONE SUBMITTED IS FOR A THREE
 PANEL DOOR.
  
 2) THE PRODUCT APPROVALS SUBMITTED FOR
 THE WINDOW MULLIONS ARE LIMITED IN SIZE
 AND WILL NOT WORK IN THE TWO LARGE
 OPENINGS AT THE LIVING ROOM AND MASTER
 BEDROOM. SUBMIT THE APPROPRIATE PROD.
 APPROVALS.
  
 3) THE PRODUCT APPROVAL DRAWINGS FOR THE
 9' AND 16' WIDE GARAGE DOORS HAVE DESIGN
 PRESSURES LOWER THAN THE REQUIRED
 PRESSURES LISTED ON THE PLANS.
  
 4) SUBMIT TWO COPIES OF THE PRODUCT
 APPROVAL, KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. THE
 FLORIDA PRODUCT APPROVAL THAT WAS
 SUBMITTED IS FOR WEATHER GUARD, INC. AND
 THE ATTACHED INFORMATION IS FOR
 WEATHERGUARD. THESE ARE TWO DIFFERENT
 COMPANIES.
  
 5) THE GLAZING PRODUCTS SUBMITTED WITH
 AAMA CERTIFICATION HAVE NOT BEEN TESTED
 FOR LARGE MISSLE IMPACT AND ARE REQUIRED
 TO BE PROTECTED WITH STORM PANELS.
  
 6) THE ID MARK (F-) IN THE FOOTING
 SCHEDULE SHOULD BE (F-10). PLEASE
 CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-12-02 Cont ID  
Sent By rmcdouga Date 2004-12-02 Time 09:54 Rev Time 0.00
Received By rmcdouga Date 2004-12-02 Time 07:15 Sent To  
Notes
2004-12-02 00:00:00DENIED
  
 1)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) SPECIFY THE BOTTOM CORD LIVE LOAD ON
 THE PLANS. SEE FBC TABLE 1604.1 FOR
 REQUIREMENTS.
  
 3) THE FOOTING SCHEDULE ON A1 IS MISSING
 THE F-10 MARK.
  
 4) ON SHEET A2 SPECIFY SAFETY GLAZING
 FOR THE WINDOWS AT THE BATH TUB IN THE
 LADIES SUITE AND BESIDE THE SHOWER IN
 HIS BATH.
  
 5) A DETAIL 5/A5 IS SPECIFIED ON THE
 PLANS ON A5 AND A6, BUT THE DETAIL IS
 NOT GIVEN.
  
 6) SEVERAL OF THE DETAILS CALLED OUT IN
 THE ROOF PLAN ON A6 DO NOT CORRESPOND
 WITH THE DETAILS SPECIFIED ON A5. SEE
 MARKS ON THE PLANS.
  
 7) PLEASE CLARIFY THE CONNECTION FOR THE
 THREE GIRDERS THAT MEET AT THE STEEL
 COLUMN SHOWN IN DETAIL 9 ON A5. THE
 BOTTOM OF TWO GIRDERS ARE AT 14' AND THE
 BOTTOM OF THE THIRD IS 10'.
  
 8) THE ENERGY CALCULATION FORM IS
 REQUIRED TO BE SIGNED AND DATED BY THE
 OWNER/AGENT PER FBC CHAPTER 13.
  
 9)PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 10) ALL PRODUCT APPROVAL INFORMATION
 SUBMITTED MUST BE CLEAR AND LEGIBLE.
 WHEN MULTIPLE PRODUCTS OR MODELS ARE
 LISTED IN A SINGLE PRODUCT APPROVAL THE
 ONES THAT ARE BEING USED MUST BE
 SPECIFIED AND THE INSTALLATION DRAWINGS
 AND DESIGN PRESSURES FOR THOSE ITEMS
 MUST BE SUBMITTED.
  
 11) SUBMIT STATE/LOCAL PRODUCT APPROVALS
 FOR THE ARCHED TOP FIXED GLASS WINDOWS
 AND THE STRUCTURAL MULLIONS.
  
 12) SUBMIT AN ACCURATE KEY PLAN AND
 INSTALLATION SCHEDULE FOR THE STORM
 PANELS, LISTING ONLY THE OPENINGS THAT
 WILL BE SHUTTERED. THE PRODUCT APPROVALS
 THAT WERE SUBMITTED ARE FOR IMPACT
 WINDOWS, WHICH INDICATES THAT ONLY THE
 GLAZED DOORS WOULD BE SHUTTERED.
  
 IF YOU HAVE QUESTIONS PLEASE CALL;
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-03-28 Cont ID  
Sent By btrobaug Date 2006-03-28 Time 17:48 Rev Time 0.50
Received By btrobaug Date 2006-03-28 Time 17:48 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-03-20 Cont ID  
Sent By btrobaug Date 2006-03-20 Time 08:52 Rev Time 0.50
Received By btrobaug Date 2006-03-20 Time 08:42 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-03-14 Cont ID  
Sent By btrobaug Date 2006-03-14 Time 13:41 Rev Time 0.50
Received By btrobaug Date 2006-03-14 Time 13:36 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-01-31 Cont ID  
Sent By btrobaug Date 2006-01-31 Time 13:19 Rev Time 0.50
Received By btrobaug Date 2006-01-31 Time 12:46 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-12-28 Cont ID  
Sent By dpalmer Date 2004-12-28 Time 13:21 Rev Time 0.25
Received By dpalmer Date 2004-12-28 Time 13:21 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-11-12 Cont ID  
Sent By dpalmer Date 2004-11-12 Time 12:58 Rev Time 0.33
Received By dpalmer Date 2004-11-12 Time 12:58 Sent To M
Notes
2004-11-12 00:00:00********** UNSAT ***************
  
  
 1 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 2002 NEC 210.12
 PLANS ONLY REFLECT RECEPTS.
  
 2)NOTE: PLEASE SEE MISSING SD'S INSIDE
 AND OUTSIDE LIB/BEDRM. THIS RM WHICH
 CONTAINS A CLOSET IS CONSIDEREDTO BE
 AN ADAPTABLE BEDRM.
 PLEASE ALSO SEE LOCATION OF SD IN
 MASTER
 BEDRM SUITE, PLANS SHOWS TWO SD'S IN
 BEDRM? NONE OUTSIDE.
 NFPA-72 8-1.4.1.6.2
 PLEASE SEE 8-1.4.2 FOR SD LOCATIONS,
 3' MIN AWAY FROM BATHS.
  
 3)NOTE: PLEASE SEE 210.52 FOR RECEPT
 SPACING, 2' OF WALL SPACING.
  
 4)NOTE: PLEASE SEE MISSING GFI RECEPT IN
 MECH RM. 210.63
 PLEASE ALSO SEEGFI FOR COND UNIT.
  
 5)NOTE: PLEASE SEE MISSING EGRESS LT
 REQUIRED FROM CABANA BATH TO OUTSIDE.
 210.70
  
  
 PLEASE SEE ONE SET OF PLANS HAS SOME OF
 THE ABOVE ITEMS REDLINED ON PLANS.
  
 PLEASE REMOVE ALLOLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-03-28 Cont ID  
Sent By adarroug Date 2006-03-28 Time 12:31 Rev Time 0.00
Received By adarroug Date 2006-03-28 Time 12:31 Sent To E
Notes
2006-03-28 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-01-31 Cont ID  
Sent By ptjomsto Date 2006-01-31 Time 08:41 Rev Time 0.00
Received By ptjomsto Date 2006-01-31 Time 08:41 Sent To  
Notes
2006-01-31 00:00:00REV/ELEC GIVEN TO BILL TROBAUGH

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-01-18 Cont ID  
Sent By mjacobs Date 2005-01-18 Time 11:05 Rev Time 0.00
Received By mjacobs Date 2005-01-18 Time 11:05 Sent To B
Notes
2005-01-18 00:00:00TO "ROB MCD" DESK/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-12-27 Cont ID  
Sent By mjacobs Date 2004-12-27 Time 15:09 Rev Time 0.00
Received By mjacobs Date 2004-12-27 Time 15:07 Sent To E
Notes
2004-12-27 00:00:00TO "DP" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-12-20 Cont ID  
Sent By mmclean Date 2004-12-20 Time 14:56 Rev Time 0.00
Received By mjacobs Date 2004-12-20 Time 16:38 Sent To Z
Notes
2004-12-20 00:00:00SENT TO "Z" BOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-02 Cont ID  
Sent By rmcdouga Date 2004-12-02 Time 09:54 Rev Time 0.00
Received By rmcdouga Date 2004-10-28 Time 14:21 Sent To  
Notes
2004-11-08 00:00:00TO SFD RACK/E
2004-10-28 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-01-10 Cont ID  
Sent By pkrauss Date 2005-01-10 Time 06:41 Rev Time 0.25
Received By pkrauss Date 2005-01-10 Time 06:40 Sent To B
Notes
2005-01-10 00:00:00NO CHANGES ON THE RESUBMITTAL

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-11-18 Cont ID  
Sent By drunnels Date 2004-11-18 Time 07:58 Rev Time 0.45
Received By drunnels Date 2004-11-18 Time 07:57 Sent To P
Notes
2004-11-18 00:00:00PAT RAFTER

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-01-01 Cont ID  
Sent By jleech Date 2005-01-01 Time 07:30 Rev Time 0.50
Received By jleech Date 2005-01-01 Time 07:30 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-11-22 Cont ID  
Sent By kstevens Date 2004-11-22 Time 05:30 Rev Time 0.33
Received By kstevens Date 2004-11-22 Time 05:30 Sent To B1
Notes
2004-11-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT A-4 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN. THE RISER
 DIAGRAM SHOWS TWO SHOWERS IN BATH #2,
 BUT THE FLOOR PLAN SHOWS ONLY ONE. THE
 TUB IN BATH #3 IS ON THE RIGHT SIDE OF
 THE W/C ON THE FLOOR PLAN, BUT IS SHOWN
 NEAR THE LAV ON THE RISER DIAGRAM. SHOW
 ALL PIPE SIZES ON THE RISER DIAGRAM,
 MANY SECTIONS IN THE MASTER BATH DO NOT
 HAVE PIPE SIZES. SECTION 104.2.1.
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-12-27 Cont ID  
Sent By mmclean Date 2004-11-06 Time 13:16 Rev Time 0.00
Received By mmclean Date 2004-11-06 Time 13:16 Sent To I
Notes
2004-11-06 00:00:00NOTE: MUST PULL SEPERATE PERMIT FOR
 POOL/DECK