Plan Review Details - Permit 04101063
Plan Review Stops For Permit 04101063
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-08-09 Cont ID  
Sent By alange Date 2005-08-09 Time 07:56 Rev Time 1.25
Received By alange Date 2005-08-09 Time 07:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-06-15 Cont ID  
Sent By alange Date 2005-06-15 Time 10:28 Rev Time 1.00
Received By alange Date 2005-06-15 Time 07:25 Sent To  
Notes
2005-06-15 00:00:00DENIED
 NOTES FROM FIRST REVIEW NOT ADDRESSED:
  
  
 3.
 ***ALL PRODUCT APPROVALS REQUIRE THE
 FOLLOWING. ***
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-04-01 Cont ID  
Sent By alange Date 2005-04-01 Time 09:08 Rev Time 1.00
Received By alange Date 2005-04-01 Time 09:08 Sent To  
Notes
2005-04-01 00:00:00DENIED
 NOTES FROM FIRST REVIEW NOT ADDRESSED:
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.SUBMIT 2 COPIES OF PRODUCT APPROVALS
 WITH QUALITY ASSURANCE FOR MASONITE
 DOOR.INFORMATION SUBMITTED WAS ONLY A
 SPEC SHEET.
  
 ***ALL PRODUCT APPROVALS REQUIRE THE
 FOLLOWING. ***
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 NEW COMMENTS:
 A.OUTDOOR COOKING CENTER NOT TO BE
 INSTALL UNDER COMBUSTIBLE CONSTRUCTION
 PER MANUFACTURERS SPECS.
  
 B.SHEET A-2 NOT SIGNED AND SEALED.
  
 C.PLEASE SIGN OWNER/AGENT ON ENERGY
 CALCS.
  
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-12-03 Cont ID  
Sent By alange Date 2004-12-03 Time 12:30 Rev Time 1.00
Received By alange Date 2004-12-03 Time 11:55 Sent To  
Notes
2004-12-03 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.SUBMIT 2 COPIES OF PRODUCT APPROVALS
 WITH QUALITY ASSURANCE FOR WINDOWS,
 EXTERIOR DOORS, SHUTTERS, ROOFING AND
 IMPACT PROTECTION.
 NOTE: I ALREADY INSERTED PRODUCT
 APPROVAL INFO FOR STRAPS AND TIE DOWNS.
  
 ALL PRODUCT APPROVALS REQUIRE THE
 FOLLOWING.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4.SAFTEY GLAZING IS REQUIRED AT
 SHAOWER AREA.PLEASE NOTE ON PLANS.
  
 5. SHOW SIZE AND LOCATION OF ATTIC
 ACCESS.FBC 2309.6
  
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-08-08 Cont ID  
Sent By dpalmer Date 2006-08-08 Time 21:15 Rev Time 0.00
Received By dpalmer Date 2006-08-08 Time 21:15 Sent To PC
Notes
2006-08-08 00:00:00REVISED RECEPTS AND LTS.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-08-23 Cont ID  
Sent By dpalmer Date 2005-08-23 Time 13:02 Rev Time 1.00
Received By dpalmer Date 2005-08-23 Time 13:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-07-29 Cont ID  
Sent By dpalmer Date 2005-07-29 Time 18:30 Rev Time 1.00
Received By dpalmer Date 2005-07-29 Time 18:20 Sent To M
Notes
2005-07-29 00:00:00*********** UNSAT 4TH REVIEW ***********
  
 ***************************************
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW AND SOME NEW NOTES ONCE AGAIN DUE
 TO CHANGES IN PLANS.
 ***************************************
  
 1)NOTE: PLEASE SEE PLANS HAVE NOW COME
 BACK IN WITH A COMPLETELY NEW RISER.
 PLEASE SEE NEW NEW MLO METER/MAIN SHOWN.
 PLEASE CLARIFY 400A?? THIS IS ONLY A
 NOTE:
 PLEASE SEE A MCB WILL BE REQUIRED AS
 THERE MAY NOT BE ANY MORE THAN 6 SPACES
 IN A SINGLE ENCLOSURE.230.71
 PLEASE SEE NEW COMMENT FOR GROUNDING
 ELECTRODE SYSTEM DUE TO INCREASE IN
 SERVICE.
  
 2)NOTE: AS REQUESTED ON PREVIOUS REVIEW,
 ALL AIC RATINGS FOR NEW MAIN/ PANELS ETC
 SHALL BE SUBMITTED. 110.9, 215.5
 PLEASE SEE ABOVE, ALL MAINS, BRKRS
 PANELS ARE TO BE RATED FOR THE AVAILABLE
 FAULT CURRENT.
  
 3)NOTE: PLEASE SEE NOTE #3 FROM ALL
 PREVIOUS REVIEWS. PLEASE SEE 220.31B FOR
 LOAD CALCULATIONS.
 THIS WAS GONE OVER IN MEETING WITH
 ARCHITECT AND ELECTRICIAN,HOWEVER ONLY
 PART OF THE CALCULATIONS ARE NOW
 CORRECTED?
 PLEASE SEE THIS HAS BEEN THE SAME
 COMMENT NOW FOR FOUR(4) REVIEWS.?????
  
 4)NOTE: PLEASE SEE 210.52D,210.11C3 THE
 REQUIRED DEDICATED BATH CIRCUIT(S) ARE
 TO BE LISTED ON PANEL SCHEDULE AS
 PREVIOUSLY NOTED.??
  
 5)NOTE: PLEASE SEE ARC FAULT PROTECTION
 IS STILL LISTED FOR PROTECTION OF
 "RECEPT'S". PLEASE SEE THIS WAS REDLINED
 ON PLANS AND MEETING WITH ARCHITECT AND
 ELECTRICAN TO CORRECT TO THE 2002 NEC
 210.12. PLEASE SEE THE 2002 NEC
 REQUIREMENT FOR THIS WAS ADOPTED BY THE
 STATE ON JULY 1ST, 2003.
 PLEASE SEE ARC FAULT PROTECTION IS
 REQUIRED FOR ALL "OUTLETS", THIS
 INCLUDES LTS, RECEPTS, FANS, SD'S ETC.
  
 6)NOTE: PLEASE SEE DUE TO CHANGE AND
 INCREASE IN SERVICE TO 400A'S? , PLEASE
 SEE GROUNDINGELECTRODE CONDUCTOR SHALL
 BE SIZED PER TABLE 250.66 IN THE NEC,
 BASED ON MIN SEC'S FROM 310.15B6
 PLEASE SEE IF SERVICE STAYS AT 400A'S, A
 MIN. OF A 1/0 SHALL BE USED.
 PLEASE CORRECT.
  
 7)NOTE: PLEASE SEE AS NOTED ON (3)THREE
 PREVIOUS REVIEWS, A 4X FEE SHALL BE
 ACCESSED PER FS 553.80(2)(B)TO ALL
 REPEAT COMMENTS. PLEASE SEE THIS IS
 REQUIRED UNDER STATE STATUE AND IS NOT A
 LOCAL RULE OR FEE. THIS IS PER
 FS553.80(2)(B) WITH RESPECT TO THE
 DESIGN PROFESSIONL. PLEASE SEE A COPY
 TAKEN DIRECTLY FROM THE FS WAS ATTACHED
 FOR THE LAST TWO REVIEWS.
 PLEASE SEE LOAD CALCULATIONS AND
 POSSIBEL "MISPRINT".
 IT IS STRONGLY SUGGESTED A MEETING BE
 SCHEDULED TO GO OVER COMMENTS.
 PLANS MAY BE TURNED OVER TO THE STATE
 BOARD OF ARCHITECTS FOR REVIEW.
 ONE COPY OF ELECTRICAL PLANS IS NOW
 RETAINED FOR FILE.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT ONE SET OF ANY VOIDED/OLD
 COPIES FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-06-13 Cont ID  
Sent By dpalmer Date 2005-06-13 Time 13:09 Rev Time 0.50
Received By dpalmer Date 2005-06-13 Time 13:07 Sent To B
Notes
2005-06-13 00:00:00************ UNSAT 3RD REVIEW *********
  
 PLEASE SEE NOTES FROM PREVISOUS REVIEWS
 AND NOTES CONTAINED IN THIS THIRD
 REVIEW.
  
 1)NOTE: NO,
 PLEASE SEE NOW A COMPLETE NEW RISER
 DIAGRAM IS NOW SUBMITTED SHOWING ALL
 PANELS/SERVICE AS NEW??
 PLEASE SEE BOTH SUB PANELS ARE SHOWN AS
 T.L.O'S ?? IS THIS SUPPOSE TO BE MLO?
 PLEASE SEE THESE PANELS ARE NOW MISSING
 EQUIPMENT GROUNDING CONDUCTORS FROM
 MCB/PANEL "A" PER 250.122,250.110,250.24
 ETC.
  
 2)NOTE: PLEASE SEE SINCE ALL THESE
 PANELS ARE NOW SHOWN AS NEW , PLEASE
 SUBMIT AIC RATINGS FOR AL0 EQUIPMENT,
 MAINS/PANELS/ BRKRS ARE ALL TO BE RATED
 FOR THE AVAILABLE FAULT CURRENT PER
 110.9/215.5
  
 3)NOTE: PLEASE SEE NOTE # 3 FROM TWO
 PREVIOUS REVIEWS. PLEASE SEE 220.31B FOR
 LOAD CALCULATIONS OF EXISTING LOADS AND
 NEW LOADS/HEATING ETC ADDED.
  
 4)NOTE: PLEASE SEE A SUB PANEL IS NOW
 SHOWN IN THE CLOTHES CLOSET, PLEASE SEE
 240.24D, 408.7, PANELS ARE SHALL NOT BE
 INSTALLED IN CLOTHES CLOSET.
  
 5)NOTE: PLEASE SEE PREVIOUS REVIEW
 MENTIONED FS 553.80(2)(B) WITH RESPECT
 TO THE DESIGN PROFESSIONAL AND REPEAT
 COMMENTS. A NOTICE WAS GIVEN IF PLANS
 CAME BACK WITH ANY OF THE COMMENTS
 REPEATED FROM TWO PREVIOUS REVIEW NOT
 ADDRESSED, A 4X FEE FOR THE PLAN REVIEW
 PORTION OF THE PERMIT FEE WOULD BE
 ACCESSED. PLEASE SEE A FEE IS NOW
 ACCESSED AS REQUIRED UNDER FS
 553.80(2)(B) IN THE AMOUNT OF $1320.00.
 PLEASE SEE FS WHICH REQUIRES THIS TO BE
 PAID BEFORE PLANS MAY BE RESUBMITTED.
 THIS FEE IS ACCESSED TO THE DESIGN
 PROFESSIONAL AND NOT THE HOME OWNER OR
 CONTRACTOR OF RECORD.
 PLEASE NOTE: AS OF THIS REVIEW, NO ONE
 HAS CALLED TO GO OVER ANY QUESTIONS ON
 THIS PROJECT.
  
 6)NOTE: PLEASE LIST THE REQUIRED BATH
 CIRCUIT AS #12, 20A 210.52D ,210.11C3
  
 7)NOTE: PLEASE SEE NOT ALL SHEETSARE
 SIGNED THE SAME WAY BY THE ARCH, PLEASE
 ALSO SEE SOME SHEETS NOT SIGNED AND
 SEALED .
 FS 481.221
  
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SEE ONE SET OF OLD SHEETS ARE TO
 BE SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-03-15 Cont ID  
Sent By dpalmer Date 2005-03-15 Time 08:43 Rev Time 0.50
Received By dpalmer Date 2005-03-15 Time 08:43 Sent To M
Notes
2005-03-15 00:00:00********* UNSAT 2ND REVIEW ************
  
 PLEASE SEE SOME COMMENTS FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
  
  
 1)NOTE: NOTE #1 NO, PLEASE SEE RISER
 DIAGRAM NOW SHOWS A NEW 150A MCB PANEL.
 WHERE IS THIS FED FROM? PLEASE SEE
 EXISTING 200A PANEL DOES NOT INDICATE
 ANY FEED TO NEW PANEL BY MEANS OF OCP,
 CONDUIT, CONDUCTOR SIZE ETC.
 PLEASE SEE MANY ITEMS SHOWN ON PANEL
 SCHEDULE WHICH NEED TO CORRELATE OCP,
 KW/LOAD, AND AWG.
 PLEASE SEE THESE ITEMS REDLINED.
 10KW ON 20A OCP, 5500 KW FOR 10KW LOAD,
 20A OCP ON #6ETC.
  
 2)NOTE: NOTE #2, OK.
  
 3)NOTE: NOTE #3 NO, PLEASE SEE 220.31B
 FOR LOAD CALCUALTIONS TO AN EXISTING
 SERVICE/DWELLING.
 PLEASE SUBMIT LOAD CALCS ON SERVICE
 ALONG WITH LOAD ON EACH PANEL.
  
 4)NOTE: NOTE #4 OK
  
 5)NOTE: NOTE #5 OK.
  
 6)NOTE: NOTE # NO. SEE PREVIOUS NOTES.
  
 7)NOTE #7 NO, PLEASE SEE 2002 NEC
 210.12, NOTE MENTIONS RECEPTS? THIS WAS
 OLD REQUIREMENT.
  
 NEW NOTE:
  
 1)NOTE: PLEASE SEE ATTACHED COPY OF
 FS553.80(2)(B) WITH RESPECT TO THE
 DESIGN PROFESSIONAL.
  
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-11-12 Cont ID  
Sent By dpalmer Date 2004-11-12 Time 19:14 Rev Time 0.33
Received By dpalmer Date 2004-11-12 Time 19:05 Sent To P
Notes
2004-11-12 00:00:00******* UNSAT **************
  
 1)NOTE: PLEASE CORRELATE PANEL SCHEDULE
 WITH RISER. RISER/PANEL INDICATES A
 "DOUBLE-TUB" (FEED-THRU) PANEL.
 YET PANEL SCHEDULE ONLY INDICATES 38
 CIRCUITS??
 PLEASE INDICATE NEW AND EXISTING
 CIRCUITS.
 215.5
  
 2)NOTE: PLEASE SHOW LOCATION OF COND
 UNIT ON PLANS FOR NEW A/C SYSTEM. PLEASE
 SHOW DISC PER 440.11.
 PLEASE SEE 210.63 FOR MISSING SERVICE
 RECEPT FOR COND UNIT AND AHU?
  
 3)NOTE: PLEASE SEE 220.31B FOR ADDITION
 OF HEAT LOADS TO EXSITING SERVICE.
 PLEASE RE-FIGURE LOAD CALCS.
  
 4)NOTE: PLEASE INCLUDE FOOTER STEEL AS
 PART OF THE GROUNDING ELECTRODE SYSTEM.
 250.50
  
 5)NOTE: PLEASE INCLUDE PRINTED LICENSE #
 ON TITLE BLOCK AS REQUIRED UNDER FAC
 61G1-16.004
  
 6)NOTE: PLEASE SEE FBC CHAPTER 34, FOR
 ADDITIONS TO EXISTING DWELLINGS.
 PLEASE SHOW LAYOUT FOR SD'S AND GFI
 PROTECTED RECEPTS REQUIRED UNDER CURRENT
 2002 NEC AND NFPA-72 8-1.4.1.6.2
 FBC 3401.7.1.2.1
  
 7)NOTE: ARC FAULT PROTECTION REQUIRED
 FOR NEW BEDRM ELECTRICAL DEVICES.
 2002 NEC 210.12
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETED SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-08-08 Cont ID  
Sent By adarroug Date 2006-08-08 Time 16:39 Rev Time 0.00
Received By adarroug Date 2006-08-08 Time 16:39 Sent To E
Notes
2006-08-08 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-08-22 Cont ID  
Sent By adarroug Date 2005-08-22 Time 08:35 Rev Time 0.00
Received By adarroug Date 2005-08-22 Time 08:35 Sent To E
Notes
2005-08-22 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-07-28 Cont ID  
Sent By adarroug Date 2005-07-28 Time 17:30 Rev Time 0.00
Received By adarroug Date 2005-07-28 Time 17:30 Sent To E
Notes
2005-07-28 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-05-25 Cont ID  
Sent By adarroug Date 2005-05-25 Time 10:18 Rev Time 0.00
Received By adarroug Date 2005-05-25 Time 10:18 Sent To E
Notes
2005-05-25 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-03-10 Cont ID  
Sent By adarroug Date 2005-03-10 Time 16:27 Rev Time 0.00
Received By adarroug Date 2005-03-10 Time 16:27 Sent To E
Notes
2005-03-10 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-11-10 Cont ID  
Sent By csiegber Date 2004-11-10 Time 13:53 Rev Time 0.00
Received By csiegber Date 2004-11-10 Time 13:53 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-10-27 Cont ID  
Sent By csiegber Date 2004-10-27 Time 09:49 Rev Time 0.00
Received By csiegber Date 2004-10-27 Time 09:49 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-08-02 Cont ID  
Sent By rregueir Date 2005-08-02 Time 19:06 Rev Time 0.00
Received By rregueir Date 2005-08-02 Time 19:02 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-03-31 Cont ID  
Sent By pkrauss Date 2005-03-31 Time 13:59 Rev Time 0.35
Received By pkrauss Date 2005-03-31 Time 11:19 Sent To B
Notes
2005-03-31 00:00:00PROVISO:
 A/C PLAN IS CODE COMPLIANT.
 THE GE MONOGRAM OUTDOOR COOKING CENTER
 IS NOT APPROVED.THE MANUFACTURER'S
 SPECIFICATION/INSTALLATION INDICATES:
 1.FOR OUTDOOR INSTALLATION ONLY.
 2.SHALL HAVE ADEQUATE VENTILIATION.
 3.SHALL NOT BE INSTALLED IN AN
 ENCLOSED AREA.
 ACCORDING TO THE MERRIAM-WEBSTER
 DICTIONARY OUTDOORS MEANS NOT ENCLOSED,
 HAVING NO ROOF.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-11-29 Cont ID  
Sent By pkrauss Date 2004-11-29 Time 17:09 Rev Time 0.35
Received By pkrauss Date 2004-11-29 Time 16:37 Sent To B
Notes
2004-11-29 00:00:00DENIED:
 1.PROVIDE A COMPLETED FORM 600C PER
 2001 FBC CHAPTER 13 SUB-CHAPTER 6 METHOD
 C.
  
 2.PROVIDE EQUIPMENT SCHEDULE.
 INDICATE IF THE A/C EQUIPMENT IS NEW OR
 EXISTING.
  
 3.PROVIDE DUCT/GRILLE SIZE AND
 LAYOUT.
  
 4.PROVIDE MANUFACTURER SUBMITTAL DATA
 FOR THE GRILLE INDICATED IN THE "NEW
 SUMMER KITCHEN".INDICATE IF THE GRILLE
 IS GAS OR ELECTRIC.PROVIDE VENTING
 INFORMATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2004-11-22 Cont ID  
Sent By kstevens Date 2004-11-22 Time 18:16 Rev Time 0.25
Received By kstevens Date 2004-11-22 Time 18:16 Sent To M
Notes
2004-11-22 00:00:00NO PLUMBING PLANS SUBMITTED - ALL WORK
 TO CITY CODES SUBJECT TO FIELD
 INSPECTORS APPROVAL

Review Stop Z ZONING
Rev No 1 Status P Date 2004-11-09 Cont ID  
Sent By csiegber Date 2004-11-09 Time 09:49 Rev Time 0.00
Received By mmclean Date 2004-11-09 Time 17:38 Sent To I
Notes
***NONE***