Plan Review Details - Permit 04101050
Plan Review Stops For Permit 04101050
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-04-27 Cont ID  
Sent By jwitmer Date 2005-04-27 Time 13:00 Rev Time 0.55
Received By jwitmer Date 2005-04-27 Time 13:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-03-01 Cont ID  
Sent By jwitmer Date 2005-03-01 Time 08:10 Rev Time 0.77
Received By jwitmer Date 2005-03-01 Time 08:10 Sent To  
Notes
2005-03-01 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04101050
 ADD: 2100 45TH ST # 143
 CONT:W P& S CONSTRUCTION
 TEL: (954)444-6714
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1)PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)COMMENT #3 FROM THE PREVIOUS REVIEW,
 PLANS ARE TO INDICATE A HANDICAPPED
 ACCESSIBLE COUNTER: 11-5.2 COUNTERS AND
 BARS, WHERE FOOD OR DRINK IS SERVED @
 COUNTERS EXCEEDING 34" IN HEIGHT FOR
 CONSUMPTION BY CUSTOMERS SEATED ON
 STOOLS OR STAND- ING AT THE COUNTER, A
 PORTION OF THE MAIN COUNTER WHICH IS 60"
 IN LENGTH MIN- IMUM SHALL BE PROVIDED IN
 COMPLIANCE WITH 11-4.32 OR SERVICE SHALL
 BE AVAIL- ABLE AT ACCESSIBLE TABLES
 WITHIN THE SAME AREA.
  
 3) COMMENT # 4 FROM THE PREVIOUS REVIEW,
 THE DOOR TO THE RESTROOM DOESN'T MEET
 THE MANEUVERING CLEARENCES, SEE:
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 4) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-11-24 Cont ID  
Sent By jwitmer Date 2004-11-24 Time 15:56 Rev Time 1.11
Received By jwitmer Date 2004-11-24 Time 15:55 Sent To  
Notes
2004-11-24 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04101050
 ADD:2100 45TH ST# B-14
 CONT: WP&S CONTRACTORS
 TEL: (954)444-6714
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1)PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) 704.2.1.4 CORRIDOR PARTITIONS,
 SMOKE STOP PARTITIONS, HORIZONTAL EXIT
 PART- ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 3) 11-5.2 COUNTERS AND BARS
 WHERE FOOD OR DRINK IS SERVED @ COUNTERS
 EXCEEDING 34" IN HEIGHT FOR CONSUMPTION
 BY CUSTOMERS SEATED ON STOOLS OR STAND-
 ING AT THE COUNTER, A PORTION OF THE
 MAIN COUNTER WHICH IS 60" IN LENGTH MIN-
 IMUM SHALL BE PROVIDED IN COMPLIANCE
 WITH 11-4.32 OR SERVICE SHALL BE AVAIL-
 ABLE AT ACCESSIBLE TABLES WITHIN THE
 SAME AREA.
  
 4) 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 5)TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-04-25 Cont ID  
Sent By dpalmer Date 2005-04-25 Time 18:54 Rev Time 0.30
Received By dpalmer Date 2005-04-25 Time 18:48 Sent To  
Notes
2005-04-25 00:00:00REDLINED
  
 ALL RECEPTS IN KITCHEN AREA TO BE
 GFI/GFI PROTECTED. 210.8B3
 2002 NEC
  
 PLEASE SEE NOC SUBMITTED HAS EXPIRED.
 PER FS 713.13(2), IF WORKHAS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING
 NOC, NOC EXPIRES.
 A NEW RECORDED NOC WILL BE REQUIRED
 BEFORE PICKING UP PERMIT.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-03-01 Cont ID  
Sent By dpalmer Date 2005-03-01 Time 06:55 Rev Time 0.33
Received By dpalmer Date 2005-03-01 Time 06:53 Sent To  
Notes
2005-03-01 00:00:00********** UNSAT 2ND REVIEW ********
  
 PLEASE SEE NOTES FROM PREVIOUS WHICH
 STILL NEED TO BE ADDRESSED.
  
 1)NOTE: OK.
  
 2)NOTE: NOTE #2 NO.
  
 3)NOTE: NOTE #3 NO.
  
 4)NOTE: NOTE #4 NO.
  
 5)NOTE: NOTE #5 NO.
  
 1)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) ATTACHED WITH RESPECT TO
 DESIGN PROFESSIONAL.
 PLEASE SEE ONE COPY OF ELECTRICAL PLANS
 HAVE NOW BEEN RETAINED.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-11-02 Cont ID  
Sent By dpalmer Date 2004-11-02 Time 10:44 Rev Time 0.00
Received By dpalmer Date 2004-11-02 Time 10:53 Sent To  
Notes
2004-11-02 00:00:00************* UNSAT ******************
  
 1)NOTE: PLEASE CORRELATE
 PLANS/PANEL/RISER. PLANS SHOWS 100A
 PANEL, YET RISER ETC SHOWS 150A
  
 2)NOTE: PLEASE CLARIFY EQUIPMENT
 GROUNDING FROM MAIN TO PANEL. 250.110,
 250.122
  
 3) NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 4)NOTE: PLEASE IDENTIFY ALL RECEPTS IN
 KITCHEN AREA AS GFI/GFI PROTECTED PER
 2002 NEC 210.8B3
  
 5)NOTE: PLEASE PROVIDE LOAD ON EXSITING
 1200A MAIN SHOWN. 215.5,220
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWERS WHICH MAY HAVE AN AFFECT ON
 ELECTRICAL SHEETS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
  
 INSERT NEW SHEETS ONLY INTO TWO
 COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
 NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-03-11 Cont ID  
Sent By mcarsill Date 2005-03-11 Time 15:16 Rev Time 0.00
Received By mcarsill Date 2005-03-11 Time 15:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-11-12 Cont ID  
Sent By dpalmer Date 2004-11-12 Time 09:23 Rev Time 0.00
Received By mcarsill Date 2004-11-12 Time 09:23 Sent To  
Notes
2004-11-12 00:00:001) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND
 CEILINGS.
  
 2) SEPARATE PLANS AND PERMITS
 FOR THE REQUIRED HOOD, DUCT, AND
 SUPPRESSION SYSTEM.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-01-27 Cont ID  
Sent By jleech Date 2006-01-27 Time 07:08 Rev Time 0.50
Received By jleech Date 2006-01-27 Time 07:08 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-01-23 Cont ID  
Sent By jleech Date 2006-01-23 Time 14:02 Rev Time 0.75
Received By jleech Date 2006-01-23 Time 14:01 Sent To  
Notes
2006-01-23 00:00:00DENIED;
 A 2# TO 12" W.C. REGULATOR MUST BE
 INSTALLED AFTER THE WATER HEATER BRANCH
 AND WITHIN 60' OF THE LAST GAS APPLIANCE
 TO MEET THE REQUIREMENTS OF THE FBC-2001
 FUEL GAS TABLE 402(2). THE REQULATOR FOR
 THE WATER HEATER MUST BE A 2# BY 12"
 W.C. WITH A SHUTOFF VALVE UP STREAM AND
 A UNION DOWN STREAM OF THE REGULATOR.
 SEE ONE PLAN MARKED IN RED.
 GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-01-22 Cont ID  
Sent By adarroug Date 2006-01-22 Time 12:31 Rev Time 0.00
Received By adarroug Date 2006-01-22 Time 12:31 Sent To P
Notes
2006-01-22 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-05-18 Cont ID  
Sent By adarroug Date 2005-05-18 Time 14:20 Rev Time 0.00
Received By adarroug Date 2005-05-18 Time 14:20 Sent To E
Notes
2005-05-18 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-04-20 Cont ID  
Sent By adarroug Date 2005-04-20 Time 14:40 Rev Time 0.00
Received By adarroug Date 2005-04-20 Time 14:40 Sent To  
Notes
2005-04-20 00:00:00TO "COMM" BD#33

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-02-22 Cont ID  
Sent By adarroug Date 2005-02-22 Time 15:51 Rev Time 0.00
Received By adarroug Date 2005-02-22 Time 15:51 Sent To  
Notes
2005-02-22 00:00:00TO "COMM" BD#1

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-11-27 Cont ID  
Sent By kstevens Date 2004-11-27 Time 17:45 Rev Time 0.00
Received By kstevens Date 2004-10-27 Time 10:43 Sent To  
Notes
2004-11-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 1) FIRST SHEET GENERAL NOTES #1 STATES
 "STANDARD BUILDING CODE", ADOPTED CODE
 IS THE FLORIDA BUILDING CODE-2001.
 PLEASE UPDATE REFERENCE.
 2) PLANS SHALL BE ROUTED TO DBPR, STATE
 OF FLORIDA DEPT. OF BUSINESS REGULATION,
 DIVISION OF HOTEL AND RESTURANT FOR
 REVIEW. SUBMIT 2 OR MORE SETS OF PLANS
 STAMPED BY DBPR REVIEW WITH "WORKSHEETS"
 ATTACHED FOR REVIEW. SECTION 101.4.7
 3) GREASE INTECEPTOR SHALL BE SIZED BY
 RODNEY COMPO, ENVIRONMENTAL COMPLIANCE.
 A DETERMINATION SHEET FROM R. COMPO
 SHALL BE ATTACHED TO PLANS WHEN
 RESUBMITTING FOR REVIEW. CONTACT MR.
 COMPO AT (561) 837-4074. WASTE ORD.
 #2938-95
 4) SEE ATTACHED SHEET FOR APPROVED
 GREASE INTERCEPTOR DETAIL.
 5) SHT M1 0F 3 PLUMBING NOTES #1
 INDICATES STANDARD PLUMBING CODE,
 APPROVED CODE IS FBC-2001 PLUMBING.
 UPDATE REFERENCE. SECTION 104.2.1
 6) SHT M1 OF 3 PLUMBING NOTES #8, 2-1/2"
 AND SMALLER PIPE SHALL SLOPE 1/4" PER
 FOOT. CORRECT PLUMBING REFERENCE. TABLE
 704.1
 7) SHT M1 OF 3 PLUMBING NOTES #12 AIR
 CHAMBERS ARE NOT APPROVED. DELETE FROM
 REFERENCE. NOTE INDICATES THAT SHOCK
 ARRESTORS ARE TO BE USED. IF SO SHOW ON
 WATER RISER DIAGRAM. SECTIONS 604.9 AND
 104.2.1
 8) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE. SECTION 608.13.2
 9) TWO WAY CLEANOUTS ARE REQUIRED ON THE
 INLET AND EXIT OF THE GREASE INTERCEPTOR
 AND THE LIDS SHALL BE STAMPED WITH THE
 WORDS "GREASE". (SEE ATTACHED SHEET).
 10) SHT M1 OF 3 STATES "NATIONAL FUEL
 GAS CODE 1999 EDITION", THE ADOPTED CODE
 FOR FUEL GAS IS FBC-2001 FUEL GAS.
 PLEASE CHANGE REFERENCE. SECTION
 104.2.1
 11 THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE GAS PERMIT REQUIRED .
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.-NOT ALL LENGTHS ARE
 SHOWN
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF USED.
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
2004-10-27 00:00:00TO COMM BD#20

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2005-05-17 Time   Rev Time 0.00
Received By hmoser Date 2005-05-17 Time 18:09 Sent To  
Notes
2005-05-17 00:00:00PASS PRIVISO
 NEED ADDITIONAL PERMITS FOR HOOD,HOOD
 SUPRESSION, AND WALK IN COOLERS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2005-03-12 Time   Rev Time 0.00
Received By hmoser Date 2005-03-12 Time 10:55 Sent To  
Notes
2005-03-12 00:00:00PLAN DENIED
 1) PROVIED OUT SIDE AIR CALCOLATIONS PER
 2001 FBC (M) 403.3
 2) ADDITIONAL PERMITS REQUIRED FOR THE
 HOOD,FIRE SUPPRESSION,GAS,WALK IN
 COOLERS.
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-11-16 Cont ID  
Sent By pkrauss Date 2004-11-16 Time 17:16 Rev Time 0.45
Received By pkrauss Date 2004-11-16 Time 17:16 Sent To  
Notes
2004-11-16 00:00:00DENIED:
 1.PROVIDE OUTSIDE AIR CALCULATIONS PER
 2001 FBC(M) 403.3.
  
 2.PLAN SHEET M1 OF 3 INDICATES GAS
 LOAD CALCULATIONS PER NATIONAL FUEL GAS
 CODE 1999 EDITION.THIS SHOULD READ
 2001 FBC, FUEL GAS.
  
 ADDITIONAL PERMITS REQUIRED FOR THE
 HOOD, FIRE SUPPRESSION, GAS, AND WALK-IN
 COOLERS.PROVIDE PLANS & MANUFACTURER
 SUBMITTAL DATA WITH PERMIT APPLICATION.
 PROVIDE SUBMITTAL FOR THE CONVECTION
 OVEN INDICATED ON M1 OF 3.
  
 3.PLANS ARE TO BE APPROVED BY DBPR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS @ (561)805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-05-16 Cont ID  
Sent By kstevens Date 2005-05-16 Time 12:58 Rev Time 1.25
Received By kstevens Date 2005-05-16 Time 12:58 Sent To  
Notes
2005-05-16 00:00:00PASSED/PROVISO
  
 WATER HAMMER ARRESTOR REQUIRED AT ICE
 MAKER.
  
 APPROVED 2LB. TO 1/2LB. GAS REGULATOR
 REQUIRED MAX. 50 FEET FROM MOST REMOTE
 OUTLET FROM METER.
  
 REVISION REQUIRED FOR GAS RISER SHOWING
 REGULATOR, AND MANUF. SPECIFICATION
 SHEET FOR REGULATOR REQUIRED AT TIME OF
 GAS ROUGH INSPECTION.

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-03-12 Cont ID  
Sent By jleech Date 2005-03-12 Time 07:37 Rev Time 2.00
Received By jleech Date 2005-03-12 Time 07:37 Sent To  
Notes
2005-03-12 00:00:00DENIED;
 GAS RISER DIAGRAM;
 SHOW ALL LENGHTS OF PIPE (SEE RED )
 IS GAS PIPE BLACK IRON OR GALV.,TREADED
 OR WELD?
 PRESSURE AT METER 1/2 LB OR 2 LB.
 SUBMIT MANUFACTURES SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPIANCE SEC. 402.2
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-11-27 Cont ID  
Sent By kstevens Date 2004-11-27 Time 17:45 Rev Time 2.00
Received By kstevens Date 2004-11-27 Time 17:45 Sent To  
Notes
2004-11-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHT A1 OF 3 GENERAL NOTES #1 STATES
 "STANDARD BUILDING CODE", ADOPTED CODE
 IS FBC-2001 BUILDING. PLEASE CHANGE
 REFERENCE. SECTION 104.2.1
 2) ROUTE THE PLANS TO DBPR DIVISION OF
 HOTELS AND RESTURANT FOOD LICENSE
 SERVICE FOR REVIEW. A MINIMUM OF 2
 STAMPED SETS SHALL BE RETURNED FOR
 REVIEW WITH THE WORKSHEETS ATTACHED.
 SECTION 101.4.7.
 3) GREASE INTERCEPTOR SHALL BE SIZED BY
 RODNEY COMPO, ENVIRONMENTAL COMPLIANCE.
 (561) 837-4074. ATTACH THE DETERMINE
 SHEET FROM MR. COMPO TO PLANS WHEN
 RESUBMITTING. WASTE ORD. #3928-95
 4) SHT M1 OF 3 PLUMBING NOTES:
 #1 STATES STANDARD BUILDING CODE -
 ADOPTED CODE IS FBC-2001 PLUMBING.
 CHANGE REFERENCE. SECTION 104.2.1
 #8 PIPE 2-1/2" AND SMALLER SHALL BE
 SLOPED AT 1/4" PER FT. TABLE 704.1
 #12 AIR CHAMBERS ARE NOT APPROVED.
 REMOVE FROM REFERENCE. SECTION 604.9 -
 ALSO NOTE INDICATES THAT SHOCK ARRESTORS
 WILL BE INSTALLED. SHOW THE SHOCK
 ARRESTORS ON THE WATER RISER, PER PDI-WH
 201 AND MANUF. INSTALLATION
 INSTRUCTIONS
 5) SHT M1 OF 3 GREASE TRAP DETAIL, TWO
 WAY CLEANOUTS ARE REQUIRED AT THE INLET
 AND THE OUTLET SIDES OF THE GREASE TRAP.
 THE LIDS SHALL BE STAMPED "GREASE". SEE
 ATTACHED UTILITY WPB GREASE TRAP
 DETAIL.
 6) THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE GAS PERMIT.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. - NOT ALL LENGHT OF PIPE
 ARE SHOWN.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 7) SUBMIT A DETAIL FOR THE ACCESSIBLE
 TOILET ROOM PER SECTIONS 11-4.16,
 11-4.19, & 11-4.22 AND ALL SUBSECTIONS.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy