Plan Review Details - Permit 04101021
Plan Review Stops For Permit 04101021
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-04-27 Cont ID  
Sent By jwitmer Date 2005-04-27 Time 15:36 Rev Time 0.77
Received By jwitmer Date 2005-04-27 Time 15:36 Sent To  
Notes
2005-04-27 00:00:00REVISIONS OK JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-01-20 Cont ID  
Sent By jwitmer Date 2005-01-20 Time 07:16 Rev Time 0.55
Received By jwitmer Date 2005-01-20 Time 07:15 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-12-23 Cont ID  
Sent By jwitmer Date 2004-12-23 Time 15:49 Rev Time 0.55
Received By jwitmer Date 2004-12-23 Time 15:48 Sent To  
Notes
2004-12-23 00:00:00BUILDING PLAN REVIEW:
 PLANS ARE CODE COMPLIANT FOR BUILDING,
 BUT SEE ELECTRICAL COMMENTS FOR
 ENGINEERING LICENSING REQUIREMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-11-23 Cont ID  
Sent By jwitmer Date 2004-11-23 Time 12:48 Rev Time 2.22
Received By jwitmer Date 2004-11-23 Time 12:48 Sent To PC
Notes
2004-11-23 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04101021
 ADD: 250 S AUSTRALIAN AVE/ 103
 CONT: TURNER
 TEL: (561)966-9622
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
  
 1)PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) PLANS A-602 INDICATE THE USE OF WOOD
 BLOCKING IN WALLS, SEE 609.2.1 TYPE I
 OR
 TYPE II BUILDINGS NO COMBUSTIBLES IN
 WALLS.
  
  
 2)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 3)TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY.
  
  
 4)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PROVIDE ADDITONAL INFORMATION FOR ANY
 SOFFITS OR DROPPED CEILINGS. TYPE OF
 STRUCTURE, ATTACHMENT TO DECK ABOVE,
 SPACING OF FRAMING MEMBERS AND
 THICKNESS
 OF FINISH MATERIALS?
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2005-05-27 Cont ID  
Sent By btrobaug Date 2005-05-27 Time 14:57 Rev Time 0.33
Received By btrobaug Date 2005-05-27 Time 14:57 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2005-04-28 Cont ID  
Sent By dpalmer Date 2005-04-28 Time 09:40 Rev Time 0.30
Received By dpalmer Date 2005-04-28 Time 09:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2005-04-20 Cont ID  
Sent By dpalmer Date 2005-04-20 Time 17:23 Rev Time 0.30
Received By dpalmer Date 2005-04-20 Time 17:20 Sent To  
Notes
2005-04-20 00:00:00**** UNSAT ****
  
 1)NOTE: PLEASE HAVE PLANS SIGNED WITH
 SIGNATURE OF RECORD FOR ENGINEER.
 PER FS 471.025
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-01-14 Cont ID  
Sent By dpalmer Date 2005-01-14 Time 08:31 Rev Time 0.25
Received By dpalmer Date 2005-01-14 Time 08:31 Sent To  
Notes
2005-01-14 00:00:00CA # ADDED TO TITLE BLOCKS FOR M, E, FP
 PLANS.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-01-12 Cont ID  
Sent By dpalmer Date 2005-01-12 Time 15:10 Rev Time 0.25
Received By dpalmer Date 2005-01-12 Time 15:10 Sent To  
Notes
2005-01-12 00:00:00******* UNSAT *********
  
 1)NOTE: PLEASE SEE PLANS ARE NOW SIGNED
 BY ENGINEER WHICH IS FINE, HOWEVER AS
 PREVIOUS NOTES STATED.
 PLEASE SEE FAC 61G15-23.002, MISSING
 LICENSE INFORMATION FOR CA #.
 FS 471.023
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-12-23 Cont ID  
Sent By dpalmer Date 2004-12-23 Time 13:58 Rev Time 0.25
Received By dpalmer Date 2004-12-23 Time 13:58 Sent To  
Notes
2004-12-23 00:00:00************** UNSAT *************
  
 1)NOTE: PLEASE SEE NOTES 1 AND 3 FROM
 PREVIOUS REVIEW.
 FS 471.023,471.025, FAC 61G15-23.002
  
 PLEASE HAVE ENGINEER OF RECORD SIGN
 PLANS WITH LEGAL SIGNATURE.
 PLEASE ALSO INCLUDE ALL LICENSE
 INFORMATION ON TITLE BLOCK AS REQUIRED
 PER ABOVE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-11-01 Cont ID  
Sent By dpalmer Date 2004-11-01 Time 08:41 Rev Time 0.33
Received By dpalmer Date 2004-11-01 Time 08:07 Sent To  
Notes
2004-11-01 00:00:00************** UNSAT **************
  
 1)NOTE: PLEASE SEE PLANS NEED TO BE
 SIGNED WITH LEGAL SIGNATURE BY THE
 ENGINEER OF RECORD.
 FS 471.025, FAC 61G15-23.002
  
 2)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125% AND LOADING FOR TRACK LTS PER
 220.12.
  
 3)NOTE: PLEASE SEE MISSING LICENSE # AS
 REQUIRED UNDER FS 471.023 ON TITLE BLOCK
 PER 61G15-23.002
  
 PLEASE SEE ANY POSSIBLE NOTES FROM OTHER
 REVIEWERS WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2005-04-27 Cont ID  
Sent By mwennerg Date 2005-04-27 Time 15:43 Rev Time 0.00
Received By mwennerg Date 2005-04-27 Time 15:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2005-04-27 Cont ID  
Sent By mwennerg Date 2005-04-27 Time 13:06 Rev Time 0.00
Received By mwennerg Date 2005-04-27 Time 13:06 Sent To  
Notes
2005-04-27 00:00:001) PLEASE REFER TO THE NOTES GENERATED
 BY ELECTRICAL PLANS REVIEW.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910 OR 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-12-27 Cont ID  
Sent By nmccray Date 2004-12-27 Time 12:37 Rev Time 0.00
Received By jwitmer Date 2005-01-20 Time 07:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-11-12 Cont ID  
Sent By jwitmer Date 2005-01-20 Time 07:14 Rev Time 0.00
Received By jwitmer Date 2004-11-12 Time 12:41 Sent To  
Notes
2004-11-12 00:00:001) STOVE IN KITCHEN CANNOT BE
 USED FOR ANY PURPOSE. IT CAN BE
 USED FOR ILLUSTRATION PURPOSES
 ONLY. NO COOKING THAT PRODUCES
 SMOKE OR GREASE LADEN VAPORS WILL
 BE ALLOWED WITHOUT AN APPROVED
 HOOD, DUCT, AND SUPPRESSION SYSTEM.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-05-24 Cont ID  
Sent By adarroug Date 2005-05-24 Time 17:38 Rev Time 0.00
Received By adarroug Date 2005-05-24 Time 17:38 Sent To E
Notes
2005-05-26 00:00:00TO JAKE'S DESK, FIELD ISSUE./WRT.
2005-05-24 00:00:00TO "BTROBAUG" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-05-11 Cont ID  
Sent By ptjomsto Date 2005-05-11 Time 13:51 Rev Time 0.00
Received By ptjomsto Date 2005-05-11 Time 13:51 Sent To  
Notes
2005-05-11 00:00:00SUB GIVEN TO PATTY KRAUSS

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-04-18 Cont ID  
Sent By adarroug Date 2005-04-18 Time 08:42 Rev Time 0.00
Received By adarroug Date 2005-04-18 Time 08:42 Sent To  
Notes
2005-04-18 00:00:00TO "COMM" BD#28

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-04-13 Cont ID  
Sent By adarroug Date 2005-04-13 Time 10:09 Rev Time 0.00
Received By adarroug Date 2005-04-13 Time 10:09 Sent To B
Notes
2005-04-13 00:00:00TO "JWITMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-01-06 Cont ID  
Sent By mjacobs Date 2005-01-06 Time 15:39 Rev Time 0.00
Received By mjacobs Date 2005-01-06 Time 15:39 Sent To  
Notes
2005-01-06 00:00:00TO "COMM BD#4/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-12-07 Cont ID  
Sent By mjacobs Date 2004-12-07 Time 14:38 Rev Time 0.00
Received By mjacobs Date 2004-12-07 Time 14:38 Sent To E
Notes
2004-12-07 00:00:00SENT TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-11-23 Cont ID  
Sent By jwitmer Date 2004-11-23 Time 12:48 Rev Time 0.00
Received By jwitmer Date 2004-10-26 Time 10:27 Sent To PC
Notes
2004-10-26 00:00:00TO COMM BD#14

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-05-15 Cont ID  
Sent By pkrauss Date 2005-05-15 Time 19:50 Rev Time 0.30
Received By pkrauss Date 2005-05-15 Time 19:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-01-14 Cont ID  
Sent By pkrauss Date 2005-01-14 Time 13:00 Rev Time 0.35
Received By pkrauss Date 2005-01-14 Time 13:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-01-04 Cont ID  
Sent By pkrauss Date 2005-01-04 Time 12:25 Rev Time 0.35
Received By pkrauss Date 2005-01-04 Time 12:01 Sent To  
Notes
2005-01-04 00:00:00DENIED:
 LEGAL SIGNATURE OF THE ENGINEER (NOT
 INITIALS) PER FS471.025 &
 FAC61G15-23.002.SEE ALSO COMMENT #1
 BY DEWEY PALMER, ELECTRICAL PLAN REVIEW.
  
  
 PLEASE NOTE, FIRE DAMPER SHALL BE
 INSTALLED PER MANUFACTURERS
 SPECIFICATIONS.FIRE DAMPER SHOULD BE
 PERPENDICULAR TO THE RATED WALL.
  
 PLANS ARE OTHERWISE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-11-17 Cont ID  
Sent By pkrauss Date 2004-11-17 Time 07:03 Rev Time 0.45
Received By pkrauss Date 2004-11-17 Time 06:56 Sent To  
Notes
2004-11-17 00:00:00DENIED:
 1.PLAN SHEET M-1 INDICATES EXISTING
 DUCT PENETRATING TENANT SEPARATION WALL
 WHICH REQUIRES A FIRE DAMPER.PLEASE
 INDICATE ON PLAN ANY NEW OR EXISTING
 FIRE DAMPERS PER 2001 FBC(M) 607.6.
  
 2.PROVIDE REVISED OUTSIDE AIR
 CALUCALTIONS IN ACCORDANCE WITH 2001
 FBC(M)403.3.
  
 3.NO COMBUSTIBLES ALLOWED ABOVE THE
 CEILING IN THE RETURN AIR PLENUM PER
 2001 FBC(M)602.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS @ (561)805-6719.
  
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-04-29 Cont ID  
Sent By kstevens Date 2005-04-29 Time 16:39 Rev Time 0.50
Received By kstevens Date 2005-04-29 Time 16:39 Sent To  
Notes
2005-04-29 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
  
 1) INDICATE ON THE FLOOR PLAN THE
 LOCATION OF THE REFRIGERATOR AND SHOW
 THE POINT OF CONNECTION LOCATION.
 SECTION 104.2.1.
  
 2) NO PLUMBING CONTRACTOR HAS APPLIED
 FOR A PERMIT FOR THIS WORK. PLEASE HAVE
 PLUMBING CONTRACTOR SUBMIT NEW "P"
 SHEETS AT TIME OF APPLICATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy