| Plan Review Stops For Permit 04101017 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2004-11-10 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2004-11-10 |
Time |
14:19 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2004-11-10 |
Time |
14:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-11-09 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2004-11-09 |
Time |
14:42 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2004-11-09 |
Time |
12:38 |
Sent To |
|
|
| Notes |
| 2004-11-09 00:00:00 | | | | PLEASE CORRECT THE FOLLOWING FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} MAIN BLDG TEMP #2 IS LISTED AS 3#3AL | | | WITH A 400 AMP OCP, SEE 310.16 (TABLE) | | | THE RISER SHOWS 4-3/0 AL. PLEASE | | | CORRELATE RISER AND PANELSCHEDULE | | | CONDUCTOR, OCP, AND CONDUIT SIZES. | | | | | | 2} PLEASE NOTE THE CERTIFICATE OF | | | AUTHORIZATION NUMBER IS REQUIRED ON THE | | | TITLE BLOCK PER 61G15-23.002 FAC. | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|
|