| Plan Review Stops For Permit 04101013 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
P |
Date |
2006-10-17 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-10-17 |
Time |
11:21 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2006-10-17 |
Time |
11:21 |
Sent To |
|
|
| Notes |
| 2006-10-17 11:22:14 | COLUMN DELETION OK AND REVISED FLOOR PLAN OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2005-11-22 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-11-22 |
Time |
11:03 |
Rev Time |
0.33 |
| Received By |
alange |
Date |
2005-11-22 |
Time |
10:55 |
Sent To |
|
|
| Notes |
| 2005-11-22 00:00:00 | LEDGER REVISION OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2005-06-20 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-06-20 |
Time |
16:10 |
Rev Time |
0.50 |
| Received By |
alange |
Date |
2005-06-20 |
Time |
16:10 |
Sent To |
|
|
| Notes |
| 2005-06-20 00:00:00 | FRAMING REVISION LETTER RECIEVED OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2005-05-20 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-05-20 |
Time |
08:30 |
Rev Time |
0.50 |
| Received By |
alange |
Date |
2005-05-20 |
Time |
08:30 |
Sent To |
|
|
| Notes |
| 2005-05-20 00:00:00 | FOUNDATION STEM WALL REVISION OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2005-05-09 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-05-09 |
Time |
14:19 |
Rev Time |
2.00 |
| Received By |
mjacobs |
Date |
2005-05-09 |
Time |
10:40 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2005-03-08 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-03-08 |
Time |
10:22 |
Rev Time |
1.25 |
| Received By |
alange |
Date |
2005-03-08 |
Time |
09:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-12-02 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2004-12-02 |
Time |
09:47 |
Rev Time |
1.66 |
| Received By |
alange |
Date |
2004-12-02 |
Time |
08:48 |
Sent To |
|
|
| Notes |
| 2004-12-02 00:00:00 | DENIED | | | | | | 1.PLEASE COMPLETE ENERGY CALCS WITH | | | PREPARERS SIGNATURE AND OWNER/AGENT | | | SIGNATURE. | | | | | | 2.SUBMIT 2 COPIES OF PRODUCT | | | APPROVALS | | | FOR OVER HEAD DOOR, STRAPS AND TIE | | | DOWNS, ROOF TILE AND BITUMEN ROOF. | | | ALL PRODUCT APPROVALS WITH QUALITY | | | ASSURANCE ARE REQUIRED TO HAVE THE | | | FOLLOWING SUBMITTED WITH THEM. | | | | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, | | | 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR | | | INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | PRODUCT APPROVAL FOR EXTERIOR DOOR IS | | | NOT IMPACT RESITANT AS PER PLANS | | | SPECIFICATIONS. | | | | | | 3.SEC D-2 / A-7FBC 2111.1.9 WEST | | | PALM BEACH AMMENDMENT TO THE FBC. | | | WATER STOP TO BE 1/1/2" INCHES. | | | | | | 4. SHOW ROOF AND WALL SHEATHING NAILING | | | SCHEDULE ON PLANS. | | | | | | 5.DETAIL D-11 / A-9 SHOW STRAPS AND | | | TIE-DOWNS USED ON THIS DETAIL. | | | | | | 6.SHOW METHOD OF CRAWL SPACE | | | VENTILATION. | | | | | | 7.FBC 1005.4.4EMERGENCY ESCAPE | | | RESCUE OPENING SIZES. BEDROOM 2 WINDOWS | | | SH-101 DOES NOT MEET REQUIRED OPENING | | | OF | | | 5.7 SQ/FT IT IS ONLY 3.7 SQ/FT | | | | | | 8.FBC 3401.7.1.2.1 SHOW HOW EXISTING | | | | | | BUILDING WILL COMPLY WIH THIS SECTION | | | FOR SMOKE DETECTORS AND GFCI | | | RECEPTICALS. | | | | | | | | | 9.BEFORE A PERMIT TO CONSTRUCT, MAY | | | BE ISSUED, IMPACT FEES MUST BE PAID TO | | | PALM BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
8 |
Status |
N |
Date |
2006-10-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-10-17 |
Time |
07:18 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-10-17 |
Time |
07:11 |
Sent To |
B |
|
| Notes |
| 2006-10-17 07:19:47 | REV SENT BACK TO ELECWHICH WAS PASSED ON 10/1 AND | | | STAMPED, SENT TO ART LANGE AND PLACED ON HIS TABLE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
P |
Date |
2006-10-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-10-01 |
Time |
14:10 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-10-01 |
Time |
13:58 |
Sent To |
M |
|
| Notes |
| 2006-10-01 00:00:00 | PLANS OK, | | | | | | | | | **REDLINED RISER TO VERIFY THE EXISTING | | | GROUNDING ELECTRODE SHOWN. BASED ON THE | | | 4/0'S SHOWN FOR SEC'S, PLEASE SEE 250.66 | | | AS THE MIN SIZE FOR GEC IS #2. (#3 ) IS | | | BEING SHOWN WHICH IS TOO SMALL. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
F |
Date |
2006-03-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-03-22 |
Time |
07:51 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-03-22 |
Time |
07:06 |
Sent To |
M |
|
| Notes |
| 2006-03-22 00:00:00 | ********* UNSAT ********** | | | | | | *** PLEASE SEE CHANGES IN PLANS FROM | | | PREVIOUS WHICH HAD CREATE SOME COMMENTS. | | | | | | 1)NOTE: PLEASE SEE MISSING COUNTER SPACE | | | GFI AS REQUIRED PER 210.52C1, THIS WAS | | | ON PREVIOUS PLANS.' | | | | | | 2) NOTE: PLEASE SEE MISSING ISLAND | | | RECEPT PER 210.52C2 | | | ( ON PRE-PLANS) | | | | | | 3)NOTE: PLEASE SEE PREVIOUS PLANS SHOWED | | | "J-BOXES" FOR UC LIGHTING, HOWEVER THESE | | | BOXES HAVE NOW BEEN REMOVED , YET THE | | | CIRCUTIING FOR THESE ARE STILL BEING | | | SHOWN. | | | | | | 4)NOTE: PLEASE DEFINE DINING AREA ON | | | PLANS, PLEASE SEE NEW RECEPTS NOW ADDED | | | WHICH ARE ON LIGHTING CIRCUIT. PLEASE | | | SEE 210.52B1 WHICH REQUIRES RECEPTS IN | | | DINING RMS, BREALFAST AREAS AND THE LIKE | | | TO BE ON ONE OR MORE OF THE SMALL | | | APPLIANCE BRANCH CIRCUITS. | | | PLEASE SEE TWO AREAS WHICH ARE LABLED | | | "DEN", PLEASE SEE AREA ADJACENT TO THE | | | KITCHEN WILL BE CONSIDERED THE DINING | | | AREA. | | | SHALL BE #12, 20 | | | | | | 5)NOTE: PLEASE CLARIFY RISER AS, PLANS | | | ONLY ONE ONE METER/PANEL IN THE SAME | | | LOCATION, HOWEVER PLEASE SEE RISER SHOWS | | | THE METER/MAIN AND A SEPARATE PANEL WITH | | | A MCB?? ARE THESE TWO PANEL? | | | PLEASE ALSO SEE MIN CLEARENCE IS NOTED, | | | HOWEVER IF CLEARENCE IS MET FOR | | | METER/MAIN AND PANEL, THEN DISCONNECTING | | | MEANS FOR CU IS NOT MET. PLEASE REVISE | | | PLANS AND SHOW THE LAYOUT TO SCALE. | | | PLEASE SEE NOTING THE TECHNICAL | | | REQUIRMENT IS NOT ACCEPTABLE AS THERE | | | SEEMS TO BE AN ISSUE WITH CLEARENCE IN | | | THE FIELD. | | | FBC 104.2.1, NEC 110.26 | | | | | | 6) NOTE: PLEASE SEE AN AHU WITH A | | | DISCONNECT AND OCP IS NOW ADDED TO | | | CLOSET WHICH IS NOT PERMITTED PER | | | 110.26,240.24 | | | PLEASE ALSO CORRELATE AS THIS DISC IS | | | SHOWN AS 50A AND PANEL SEEMS TO INDICATE | | | THE OCP AS 60A. PLEASE SEE 424.3VB WHICH | | | REQUIRES A MIN OF 125% OCP.(THIS WOULD | | | BE 60A MIN FOR 10KW). | | | | | | 7) NOTE: PLEASE SEE PANEL SCHEDULE | | | MENTIONS NEW PACKAGE UNIT A/C , HOWEVER | | | PLEASE SEE ELECTRICAL PLANS DO NOT SHOW | | | THIS? | | | PLEASE SHOW AND SHOW DISC'S AS REQUIRED | | | PER 440.11 | | | | | | 8)NOTE: PLEASE SEE MISSING RECEPT FOR 2' | | | OR MORE OF WALL SPACE PER 210.52 IN | | | BEDRM. | | | THIS IS REDLINED ON PLANS. | | | | | | 9) NOTE: PLEASE VERIFY NUMEROUS CIRCUITS | | | ON PLANS WHICH SHOWS #12,HOWEVER | | | INDICATES 15A OPC>? | | | THIS IS ONLY A NOTE AS THIS DOES NOT | | | VIOLATE CODE. PLEASE VERIFY,IF THIS IS | | | SHOWN ON PLANS THIS WAY, THEN THIS IS | | | WHAT IS REQUIRED TO BE INSTALLED. | | | | | | ** PLEASE VERIFY THE #3 AS EXISTING GEC, | | | AS 250.66 REQUIRES A MIN OF #2. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
N |
Date |
2005-05-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-05-02 |
Time |
12:44 |
Rev Time |
0.10 |
| Received By |
dpalmer |
Date |
2005-05-02 |
Time |
12:44 |
Sent To |
M |
|
| Notes |
| 2005-05-02 00:00:00 | NO ELECTRICAL REVISION SUBMITTED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2005-04-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-04-07 |
Time |
09:26 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2005-04-07 |
Time |
09:26 |
Sent To |
P |
|
| Notes |
| 2005-04-07 00:00:00 | 4X FEE REMOVED BY BLDG OFFICAL. | | | | | | STILL NEEDS NEW RECORDED NOC, | | | ORIG NOC EXPIRED PER FS 713 | | | 90 DAYS W/OUT WORK COMMENCING. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2005-03-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-03-28 |
Time |
13:13 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2005-03-28 |
Time |
13:10 |
Sent To |
P |
|
| Notes |
| 2005-03-28 00:00:00 | ******* UNSAT 3RD REVIEW ************ | | | | | | PLEASE SEE NOTES FROM TWO PREVIOUS | | | REVIEWS. | | | | | | 1)NOTE: NOTE #1 OK | | | | | | 2)NOTE: NOTE #2 NO, PLEASE SEE SECOND | | | PART OF PF PREVIOUSE NOTE: 210.8,210.52E | | | | | | 3)NOTE: NOTE #3, NO, PLEASE SEE PREVIOUS | | | NOTES. 210.8A6 | | | | | | 4)NOTE: NOET #4, OK, NOTE ADDED TO | | | PLANS. | | | | | | 5)NOTE: NOTE #5, NO, PLEASE SEE FAC | | | 61G15-23.002 FOR REQUIRED CA# TO BE ON | | | TITLE BLOCK. FS 471.023 | | | PLEASE SEE THIS IS REQUIRED FOR ALL | | | SHEETS AND FOR ALL TRADES WHEATHER OR | | | NOT COMMENT IS MADE BY OTHER | | | REVIEWER(S). | | | PLEASE ALSO SEE MECH/PLUMB SHEETS. | | | | | | 6)NOTE: NOTE #6 OK. | | | | | | 1)NOTE: NOTE #1, PLEASE SEE PLANS STILL | | | MENTIONS "NEW PANEL A" IN TWO PLACES, | | | HOWEVER RISER INDICATES EXISTING?? | | | | | | 2)NOTE: NOTE #2, PLEASE SEE A NOTICE WAS | | | GIVEN ON PREVIOUS REVIEW WITH RESPECT TO | | | DESIGN PROFESSIONAL AND REPEAT COMMENTS | | | THREE OR MORE TIMES. | | | PLEASE SEE A 4X FEE FOR PLAN REVIEW HAS | | | NOW BEEN ACCESSED AND MUST BE PAID | | | BEFORE PLANS ARE RE-SUBMITTED. | | | FS 553.80(2)(B). | | | PLEASE SEE ONE SET OF PLANS ARE BEING | | | RETAINED FOR FILE FOR POSSIBLE REVIEW BY | | | FBPE'S. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO TWO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2005-02-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-02-28 |
Time |
06:47 |
Rev Time |
0.30 |
| Received By |
dpalmer |
Date |
2005-02-28 |
Time |
06:39 |
Sent To |
P |
|
| Notes |
| 2005-02-28 00:00:00 | ************* UNSAT ************ | | | | | | PLEASE SEE SOME NOTES FROM PREVIOUS | | | REVIEW STILL NEED TO BE ADDRESSED. | | | PLEASE SEE NOTES BELOW TAKEN DIRECTLY | | | INSERTED FROM PREVIOUS REVIEW. | | | | | | 1)NOTE: OK. | | | | | | | | | 2)NOTE: PLEASE SEE FBC CHAPTER 34 FOR | | | ADDITIONS AND REMODEL OF EXISTING | | | DWELLINGS. | | | PLEASE SHOW LAYOUT FOR ALL REQUIRED | | | SD'S | | | PER NFPA-72 8-1.4.1.6.2 | | | SMOKE DETECTORS ARE REQUIRED INSIDE AND | | | OUTSIDE ALL SLEEPING ROOMS. ON EACH | | | LEVEL OF A MULTI-LEVEL DWELLING UNIT. | | | IN CLOSE PROXIMITY OF STAIRWAYS LEADING | | | TO FLOORS ABOVE AND IN THE VICINITY OF | | | BEDROOMS. | | | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE | | | A MIN OF 3' FROM BATHROOM DOORS AND | | | KITCHENS. | | | ABOVE PER:FBC 905.2, NFPA-72 8-1.4.2 | | | ** | | | PLEASE ALSO SHOW LAYOUT FOR ALL RECEPTS, | | | NEW OR EXISTING WHICH ARE REQUIRED TO BE | | | GFI PROTECTED. 210.8 | | | PLEASE SEE FBC 3401.7.1.2.1 FOR | | | ADDITIONS, AND 3401.7.2.6 FOR OVER 50%. | | | | | | 3) NOTE: PLEASE SHOW ALL RECEPTS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED PER 210.8A-6 | | | | | | 4)NOTE: OK.PLEASE SEE CLEARENCE FOR | | | 110.26 FOR ELECTRICAL EQUIPMENT. | | | | | | | | | 5)NOTE: PLEASE HAVE ALL INFORMATION ON | | | TITLE BLOCK BE CLEAR AND VISABLE. | | | PLEASE SEE BELOEW FOR REQUIRED CA #. | | | PLEASE SEE FAC 61G15-23.002, FS 471.023 | | | PLEASE ALSO SEE FS 471.025 WHICH | | | REQUIRES LEGAL SIGNATURE FOR SIGNED AND | | | SEALED PLANS. PLANS SEEM TO BE INITIALED | | | WHICH ARE NOT ACCEPTABLE. IF PLANS ARE | | | INDEED SIGNED WITH LEGAL SIGNATURE, | | | PLEASE PROVIDE AND SIGNED,SEALED, | | | NOTORIZED LETTER FOR LEGAL SIGNATURE. | | | THIS WILL BE PLACED IN SIGNATURE FILE | | | AND CAN BE USED FOR FUTURE REFERENCE. | | | | | | 6)NOTE: PLEASE SHOW NEW FOOTER STEEL TO | | | BE PART OF GROUNDING ELECTRODE SYSTEM. | | | 250.50 | | | | | | *** NEW NOTES *** | | | | | | 1)NOTE: PLEASE SEE PLANS MENTIONS NEW | | | PANEL "A" AND EXISTING PANEL.?? PLEASE | | | CLARIFY. | | | | | | 2)NOTE: PLEASE SEE ATTACHED FS | | | 553.80(2)(B) WITH RESPECT TO DESIGN | | | PROFESSIONALS, PLEASE SEE NOTICE ONLY | | | GIVEN AT THIS TIME. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | | | | PLEASE SEE COMMENTS FROM OTHER REVIEWERS | | | WHICH MAY HAVE AN AFFECT ON ELECTRICAL | | | PLANS. (ZONING ETC). | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-11-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-11-12 |
Time |
18:18 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-11-12 |
Time |
18:18 |
Sent To |
P |
|
| Notes |
| 2004-11-12 00:00:00 | ************* UNSAT ************ | | | | | | 1)NOTE: PLEASE SEE ZONING COMMENTS, | | | PLEASE CORRELATE PLANS WITH WORK | | | PROPOSED. | | | APPLICATION MENTIONS TO BUILD NEW 3-CAR | | | GARAGE? | | | | | | 2)NOTE: PLEASE SEE FBC CHAPTER 34 FOR | | | ADDITIONS AND REMODEL OF EXISTING | | | DWELLINGS. | | | PLEASE SHOW LAYOUT FOR ALL REQUIRED | | | SD'S | | | PER NFPA-72 8-1.4.1.6.2 | | | SMOKE DETECTORS ARE REQUIRED INSIDE AND | | | OUTSIDE ALL SLEEPING ROOMS. ON EACH | | | LEVEL OF A MULTI-LEVEL DWELLING UNIT. | | | IN CLOSE PROXIMITY OF STAIRWAYS LEADING | | | TO FLOORS ABOVE AND IN THE VICINITY OF | | | BEDROOMS. | | | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE | | | A MIN OF 3' FROM BATHROOM DOORS AND | | | KITCHENS. | | | ABOVE PER:FBC 905.2, NFPA-72 8-1.4.2 | | | ** | | | PLEASE ALSO SHOW LAYOUT FOR ALL RECEPTS, | | | NEW OR EXISTING WHICH ARE REQUIRED TO BE | | | GFI PROTECTED. 210.8 | | | PLEASE SEE FBC 3401.7.1.2.1 FOR | | | ADDITIONS, AND 3401.7.2.6 FOR OVER 50%. | | | | | | 3) NOTE: PLEASE SHOW ALL RECEPTS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED PER 210.8A-6 | | | | | | 4)NOTE: PLEASE CLARIFY NUMBER OF A/C | | | UNITS, PANEL SCHEDULE(S) SHOW 3-SYSTEMS | | | 1-EXISTING, TWO NEW , YET ONLY ONE COND | | | UNIT FOR ONE OF THE NEW SYSTEMS?? | | | | | | 5)NOTE: PLEASE HAVE ALL INFORMATION ON | | | TITLE BLOCK BE CLEAR AND VISABLE, | | | PLEASE SEE CA# CAN NOT BE MADE OUT. | | | FAC 61G15-23.002, FS 471.023 | | | PLEASE ALSO SEE FS 471.025 WHICH | | | REQUIRES LEGAL SIGNATURE FOR SIGNED AND | | | SEALED PLANS. PLANS SEEM TO BE INITIALED | | | WHICH ARE NOT ACCEPTABLE. IF PLANS ARE | | | INDEED SIGNED WITH LEGAL SIGNATURE, | | | PLEASE PROVIDE AND SIGNED,SEALED, | | | NOTORIZED LETTER FOR LEGAL SIGNATURE. | | | THIS WILL BE PLACED IN SIGNATURE FILE | | | AND CAN BE USED FOR FUTURE REFERENCE. | | | | | | 6)NOTE: PLEASE SHOW NEW FOOTER STEEL TO | | | BE PART OF GROUNDING ELECTRODE SYSTEM. | | | 250.50 | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | | | | PLEASE SEE COMMENTS FROM OTHER REVIEWERS | | | WHICH MAY HAVE AN AFFECT ON ELECTRICAL | | | PLANS. (ZONING ETC). | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
N |
Date |
2005-02-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-02-24 |
Time |
13:03 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-02-24 |
Time |
13:03 |
Sent To |
E |
|
| Notes |
| 2005-02-24 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
13 |
Status |
N |
Date |
2006-09-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-25 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-25 |
Time |
14:43 |
Sent To |
E |
|
| Notes |
| 2006-09-25 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
12 |
Status |
N |
Date |
2006-03-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-03-21 |
Time |
15:54 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-03-21 |
Time |
15:51 |
Sent To |
I |
|
| Notes |
| 2006-03-21 00:00:00 | TO DP'S DESK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
11 |
Status |
N |
Date |
2006-03-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-03-17 |
Time |
16:27 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-03-17 |
Time |
16:27 |
Sent To |
P |
|
| Notes |
| 2006-03-17 00:00:00 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2006-03-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-03-02 |
Time |
09:24 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-03-02 |
Time |
09:24 |
Sent To |
Z |
|
| Notes |
| 2006-03-02 00:00:00 | TO "Z" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2005-11-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-11-16 |
Time |
16:57 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-11-16 |
Time |
16:57 |
Sent To |
B |
|
| Notes |
| 2005-11-16 00:00:00 | TO "ALANGE" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2005-06-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-06-08 |
Time |
08:31 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-06-08 |
Time |
08:31 |
Sent To |
B |
|
| Notes |
| 2005-06-08 00:00:00 | TO AL DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2005-05-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-05-18 |
Time |
11:13 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-05-18 |
Time |
11:13 |
Sent To |
B |
|
| Notes |
| 2005-05-18 00:00:00 | TO "ALANGE" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2005-04-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-04-25 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-04-25 |
Time |
13:39 |
Sent To |
E |
|
| Notes |
| 2005-04-25 00:00:00 | TO "DPALMER" DESK/REVISION | | | NEW SHEETS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2005-04-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-04-06 |
Time |
12:49 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-04-06 |
Time |
12:49 |
Sent To |
E |
|
| Notes |
| 2005-04-06 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-03-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-03-24 |
Time |
14:04 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-03-24 |
Time |
14:04 |
Sent To |
E |
|
| Notes |
| 2005-03-24 00:00:00 | TO "DPALMER'DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-02-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-02-17 |
Time |
10:23 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-02-17 |
Time |
10:23 |
Sent To |
Z |
|
| Notes |
| 2005-02-17 00:00:00 | TO "Z" BOX/RESUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-11-10 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-11-10 |
Time |
13:54 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-11-10 |
Time |
13:54 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-10-25 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-10-25 |
Time |
16:12 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-10-25 |
Time |
16:12 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
N |
Date |
2005-04-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-04-12 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2005-03-03 |
Time |
13:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
P |
Date |
2006-10-02 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-10-02 |
Time |
09:35 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-10-02 |
Time |
09:35 |
Sent To |
P |
|
| Notes |
| 2006-10-02 00:00:00 | *** PROVISO *** | | | 1) INSTANT HOT GAS WATER HEATER VENT | | | TERMINATION MUST BE A MIN. OF 4 FT. FROM | | | A/C CONDENSER UNIT, PER 2004 FBC/M 501.2 | | | . | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
F |
Date |
2006-03-22 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-03-22 |
Time |
09:20 |
Rev Time |
1.15 |
| Received By |
tgordon |
Date |
2006-03-22 |
Time |
09:20 |
Sent To |
P |
|
| Notes |
| 2006-03-22 00:00:00 | *** DENIED *** | | | 1) MECHANICAL PLANS ARE SEALED BY AN | | | ENGINEER AND REQUIRES THE ENGINEER'S | | | INFORMATION PRINTED IN THE TITLE BLOCK, | | | PER FAC 61G15.23.002 . | | | | | | 2) PLEASE PROVIDE AN A/C EQUIPMENT LIST | | | ON THE MECHANICAL PLAN SHOW ALL | | | EQUIPMENT NEW AND EXISTING. | | | | | | 3) PLEASE SHOW LOCATION OF CONDENSER | | | UNITS ON MECHANICAL PLAN. | | | | | | 4) PLEASE PROVIDE COMBUSTION AIR AND | | | CALCULATIONS FOR GAS CLOTHES DRYER AND | | | GAS INSTA-HOT WATER HEATER ON MECH. | | | PLANS. | | | | | | 5) REVISED MECHANICAL AND ELECTRICAL | | | PLANS SUBMITTED, SECOND FLOOR PLAN DO | | | NOT MATCH PLEASE CORRECT. | | | | | | 6) ELECTRICAL PLANS ARE SHOWING 3 A/C | | | SYSTEMS, MECH. PLANS ONLY TWO PLEASE | | | CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2005-05-03 |
|
|
Cont ID |
|
| Sent By |
prafter |
Date |
2005-05-03 |
Time |
10:32 |
Rev Time |
0.50 |
| Received By |
prafter |
Date |
2005-05-03 |
Time |
10:32 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2005-03-03 |
|
|
Cont ID |
|
| Sent By |
prafter |
Date |
2005-03-03 |
Time |
13:52 |
Rev Time |
0.50 |
| Received By |
prafter |
Date |
2005-03-03 |
Time |
13:52 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2005-03-03 |
|
|
Cont ID |
|
| Sent By |
prafter |
Date |
2005-03-03 |
Time |
12:36 |
Rev Time |
1.50 |
| Received By |
prafter |
Date |
2005-03-03 |
Time |
12:36 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2004-11-30 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-11-30 |
Time |
06:42 |
Rev Time |
0.55 |
| Received By |
pkrauss |
Date |
2004-11-29 |
Time |
17:51 |
Sent To |
B |
|
| Notes |
| 2004-11-30 00:00:00 | DENIED: | | | 1.PLAN SHEET M-1 INDICATES THE AHU IN | | | THE LAUNDRY ROOM WITH THE GAS DRYER. | | | PLEASE CLARIFY RETURN AIR DUCT | | | LOCATION. | | | PER 2001 FBC(M) 303.2, APPLIANCES SHALL | | | NOT BE LOCATED IN HAZARDOUS AREAS | | | UNLESS | | | LISTED AND APPROVED FOR THE SPECIFIC | | | INSTALLATION.PLEASE PROVIDE DETAIL OF | | | THE DUCT SYSTEM FOR AHU #2.GAS | | | CONTAMINANT SHALL NOT BE RE-CIRCULATED. | | | SHOW COMPLIANCE WITH 2001 FBC(M) 303.3. | | | | | | 2.PROVIDE MANUFACTURERS | | | SUBMITTAL/INSTALLATION INSTURCTIONS FOR | | | THE GAS DRYER. | | | | | | 3.PER 2001 FBC(M)601.4 RETURN AIR IS | | | TO BE EQUAL TO THE SUPPLY. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
P |
Date |
2006-10-14 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-10-14 |
Time |
12:42 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-10-14 |
Time |
12:42 |
Sent To |
E |
|
| Notes |
| 2006-10-14 12:43:37 | AS BUILTS PLUMBING ONLY |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
F |
Date |
2006-03-24 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2006-03-24 |
Time |
10:53 |
Rev Time |
1.25 |
| Received By |
mperson |
Date |
2006-03-24 |
Time |
10:53 |
Sent To |
PC |
|
| Notes |
| 2006-03-24 00:00:00 | ****DENIED**** | | | REFERENCE: FBC-2004 PLUMBING | | | | | | PLEASE ADJUST YOUR DRAWINGS TO REFLECT | | | THE FOLLOWING CHANGES REQUIRED FOR PLAN | | | REVIEW: | | | | | | 1. SHEET P-1 INDICATES A TANKLESS WATER | | | INSTANT HOT HEATER, MODEL TKJM 140,000 | | | BTU. THE P&T FOR TANKLESS HEATER SHOWN | | | IN WRONG LOCATION FOR NEW HEATER | | | LOCATION. PLEASE ADJUST DRAWING. | | | 2. SUBMIT SHEET P-2 WITH NEW TANKLESS | | | WATER HEATER ON WATER ISOMETRIC AND | | | REMOVE EXISTING 60 GALLON GAS FIRED | | | HEATER FROM ISOMETRIC. | | | 3. REMOVE GAS PIPE FROM SHEETS P-1 AND | | | P-2, PLUMBING CONTRACTOR TO SUBMIT | | | SEPERATE AS BUILTS UNDER GAS PERMIT. | | | 4. ADDED NEW CW SHOWER ON SHEET P-1 | | | NEEDS TO BE ADDED TO P-2 WATER | | | ISOMETRICS, ALSO INDICATE WHAT THE ITEM | | | IS NEXT TO SHOWER AND INDICATE THIS ITEM | | | ON WATER ISOMETRIC. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2005-04-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-04-12 |
Time |
10:33 |
Rev Time |
1.50 |
| Received By |
kstevens |
Date |
2005-04-12 |
Time |
10:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2005-04-02 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-04-02 |
Time |
10:32 |
Rev Time |
0.60 |
| Received By |
kstevens |
Date |
2005-04-02 |
Time |
10:32 |
Sent To |
|
|
| Notes |
| 2005-04-02 00:00:00 | DENIED | | | REFERENCE: FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | FROM PREVIOUS REVIEWS: | | | | | | ENGINEERS SHALL LEGIBLY INDICATE THEIR | | | NAME, ADDRESS AND LICENSE NUMBER ON EACH | | | SHEET. IF PRACTICING THROUGH A DULY | | | AUTHORIZED ENGINEERING BUSINESS, ENGIN- | | | EERS, ENGINEERS SHALL LEGIBLY INDICATE | | | THEIR NAME AND LICENSE NUMBER, AS WELL | | | AS, THE NAME, ADDRESS AND CERTIFICATE OF | | | AUTHORIZATION NUMBER OF THE ENGINEERING | | | BUSINESS ON EACH SHEET. A TITLE BLOCK | | | WILL SATISFY THIS REQUIREMENT. FAC | | | 61G15-23.002(2) - FS 471.025 | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2005-03-02 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-03-02 |
Time |
07:40 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2005-03-02 |
Time |
07:40 |
Sent To |
M |
|
| Notes |
| 2005-03-02 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | A) FROM PREVIOUS REVIEW: | | | | | | 2) SHT P-2 SANITARY RISER DIAGRAM, AT | | | THE WASH MACHINE, THE CLEANOUT SHALL BE | | | LOCATED 4 FEET ABOVE THE FLOOR FOR | | | ACCESS OR SHALL LOOK OUT TO THE | | | EXTERIOR OF THE WALL. SECTION 708.10 | | | 4) SHT P-2 GAS ISOMETRIC SHOWS NEW | | | LOCATION OF GAS METER, BUT UPSTREAM OF | | | THE METER IS THE GAS GRILL (30K BTU). | | | THIS APPLIANCE SHALL BE SHOWN | | | DOWNSTREAM OF THE METER/REGULATOR. | | | 5) THE FOLLOWING INFORMATION IS | | | REQUIRED FOR GAS PERMIT: | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2001 | | | FUEL GAS CODE. - ALL CUT SECTION LENGTHS | | | ARE NOT SHOWN ON ISOMETRIC. | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | C. TYPE OF GAS, (LP OR NATURAL) | | | D. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2001 FUEL GAS CODE SECS. 401.8 | | | THRU 402.5.2 AND TABLES 402(1) THRU | | | 402(34). - INDICATE TABLE/TABLES USED. - | | | TOTAL BTU LOAD IS NOT SHOWN AND THE | | | TABLES USED ARE NOT SHOWN. | | | E. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM | | | PER FBC-2001 FUEL GAS CODE APPENDIX A - | | | USE OF CAPACITY TABLES (A)(3). | | | F. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER FBC-2001 FUEL | | | GAS CODE SECTION 304. - FOR DRYER ROOM | | | G. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2001 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | H. CLEARLY SHOW THE LOCATION AND CAP- | | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | | OR ASME), THE DISTANCE OF THE TANK FROM | | | THE BUILDING AND ADJACENT PROPERTY | | | LINES THE DISTANCE OF THE TANK FROM ALL | | | SOURCES OF IGNITION, OTHER CONTAINERS, | | | BUILDINGS, AND THE LOCATION OF ANY | | | BUILDING OPENINGS BELOW THE RELIEF VALVE | | | OF THE TANK PER NFPA 58, TABLE 3-2.2.2. | | | I. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK | | | AND APPURTENANCES PER NFPA 58. IF THE | | | TANK IS BELOW GROUND THE CONTAINER SHALL | | | BE SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). | | | 6) ENGINEERS SHALL LEGIBLY INDICATE THE | | | NAME, ADDRESS, AND LICENSE NUMBER ON | | | EACH SHEET. IF PRACTICING THROUGH A | | | DULY AUTHORIZED ENGINEERING BUSINESS THE | | | ENGINEER SHALL AS WELL AS INDICATE THE | | | NAME, ADDRESS, AND CERTIFICATE OF | | | AUTHROIZATION NUMBER OF THE ENGINEERING | | | BUSINESS ON EACH SHEET. FAC | | | 61G15-23.002(2) & FS 471.025 | | | 7) A PROFESSIONAL ENGINEER SHALL SIGN | | | HIS NAME PER FAC 61G15-23.002(1) & FS | | | 471.025. PER FBPE INITIALS ARE NOT | | | ACCEPTABLE. IF THIS IS YOUR LEGAL | | | SIGNATURE, A SIGNED/SEALED/DATED | | | NOTORIZED LETTER INDICATING YOUR LEGAL | | | SIGNATURE IS REQUIRED FOR OUR FILES. | | | 8) PER ZONING NOTE THE GARAGE WILL NOT | | | BE BUILT. PLEASE INDICATE WHERE THE | | | WATER HEATER WILL BE LOCATED. INDICATE | | | IF THE WATER HEATER WILL BE RATED FOR | | | OUTSIDE USE OR IF IT WILL BE LOCATED | | | INSIDE. SECTION 104.2.1 | | | *************NEW COMMENT*********** | | | 1B) ONLY THE FIXTURES WITHIN THE | | | BATHROOM GROUP SHALL CONNECT THE THE | | | WET-VENTED HORIZONTAL BRANCH DRAIN. ANY | | | ADDITIONAL FIXTURES SHALL DISCHARGE | | | DOWNSTREAM OF THE WET VENT. THE W/M | | | SHALL CONNECT DOWNSTREAM OF THE TOILET | | | AND LAV OF THE POWDER ROOM . | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2004-11-23 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-11-23 |
Time |
06:02 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2004-11-23 |
Time |
06:02 |
Sent To |
M |
|
| Notes |
| 2004-11-23 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1) SHT P-2 SANITARY RISER DIAGRAM, AT | | | THE WASH MACHINE, DOUBLE SANITARY TEE | | | PATTERNS SHALL NOT RECEIVE THE | | | DISCHARGE | | | OF APPLIANCES WITH PUMPING ACTION | | | DISCHARGE. SECTION 706.3. THE WASH | | | MACHINE SHALL CONNECT BELOW THE LAUNDRY | | | SINK. | | | 2) SHT P-2 SANITARY RISER DIAGRAM, AT | | | THE WASH MACHINE, THE CLEANOUT SHALL BE | | | LOCATED 4 FEET ABOVE THE FLOOR FOR | | | ACCESS OR SHALL LOOK OUT TO THE | | | EXTERIOR | | | OF THE WALL. SECTION 708.10 | | | 3) SHT P-2 WATER RISER DIAGRAM, AT THE | | | WASH MACHINE, WATER HAMMER ARRESTORS | | | ARE | | | REQUIRED PER SECTION 604.9 AND SHALL BE | | | LOCATED NEAR THE FIXTURE IN AN | | | "EFFECTIVE RANGE" NOT IN THE CEILING. | | | PDI-WH 201 AND MANUF. INSTALLATION | | | INSTRUCTIONS. | | | 4) SHT P-2 GAS ISOMETRIC SHOWS NEW | | | LOCATION OF GAS METER, BUT UPSTREAM OF | | | THE METER IS THE GAS GRILL (30K BTU). | | | THIS APPLIANCE SHALL BE SHOWN | | | DOWNSTREAM | | | OF THE METER/REGULATOR. | | | 5) THE FOLLOWING INFORMATION IS | | | REQUIRED | | | FOR GAS PERMIT. | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2001 | | | FUEL GAS CODE. | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED. | | | C. TYPE OF GAS, (LP OR NATURAL) | | | D. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2001 FUEL GAS CODE SECS. 401.8 | | | THRU 402.5.2 AND TABLES 402(1) THRU | | | 402(34). - INDICATE TABLE/TABLES USED | | | E. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM | | | PER | | | FBC-2001 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES (A)(3). | | | F. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER FBC-2001 FUEL | | | GAS CODE SECTION 304. - FOR DRYER ROOM | | | G. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2001 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | H. CLEARLY SHOW THE LOCATION AND CAP- | | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | | OR ASME), THE DISTANCE OF THE TANK FROM | | | THE BUILDING AND ADJACENT PROPERTY | | | LINES | | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | | CES OF IGNITION, OTHER CONTAINERS, | | | BUILD | | | INGS, AND THE LOCATION OF ANY BUILDING | | | OPENINGS BELOW THE RELIEF VALVE OF THE | | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | I. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK | | | AND | | | APPURTENANCES PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). | | | 6) ENGINEERS SHALL LEGIBLY INDICATE THE | | | NAME, ADDRESS, AND LICENSE NUMBER ON | | | EACH SHEET. IF PRACTICING THROUGH A | | | DULY | | | AUTHORIZED ENGINEERING BUSINESS THE | | | ENGINEER SHALL AS WELL AS INDICATE THE | | | NAME, ADDRESS, AND CERTIFICATE OF | | | AUTHROIZATION NUMBER OF THE ENGINEERING | | | BUSINESS ON EACH SHEET. FAC | | | 61G15-23.002(2) & FS 471.025 | | | 7) A PROFESSIONAL ENGINEER SHALL SIGN | | | HIS NAME PER FAC 61G15-23.002(1) & FS | | | 471.025. PER FBPE INITIALS ARE NOT | | | ACCEPTABLE. IF THIS IS YOUR LEGAL | | | SIGNATURE, A SIGNED/SEALED/DATED | | | NOTORIZED LETTER INDICATING YOUR LEGAL | | | SIGNATURE IS REQUIRED FOR OUR FILES. | | | 8) PER ZONING NOTE THE GARAGE WILL NOT | | | BE BUILT. PLEASE INDICATE WHERE THE | | | WATER HEATER WILL BE LOCATED. INDICATE | | | IF THE WATER HEATER WILL BE RATED FOR | | | OUTSIDE USE OR IF IT WILL BE LOCATED | | | INSIDE. SECTION 104.2.1 | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2006-03-17 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-03-17 |
Time |
07:36 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-03-17 |
Time |
07:36 |
Sent To |
I |
|
| Notes |
| 2006-03-17 00:00:00 | DENIED, | | | 1. NEED TO SHOW (INDICATE) THE CHANGE IN | | | REVISION ON PLANS THAT AFFECTS THE | | | ZONING REVIEW. | | | 2. PLEASE SHOW CHANGES ON SURVEY (2 | | | COPIES) AND FLOOR PLAN. | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2005-02-23 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-02-23 |
Time |
12:22 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-02-23 |
Time |
12:22 |
Sent To |
I |
|
| Notes |
| 2005-02-23 00:00:00 | NOTE:1. MUST PULL A SEPARATE PERMIT FOR | | | FOR NEW CIRCULAR DRIVEWAY. MUST PROVIDE | | | TWO NEW SURVEY WITH DIMENSION OF | | | CIRCULAR DRIVEWAY. | | | 2. MUST PULL SEPARATE PERMIT FOR GATE | | | WITH CITY OF WPB UTILITY DEPT EASEMENT | | | APPROVAL. | | | CALLED BOBBY REGARDING THE NOTES. | | | | | | MICHELLE MCLEAN | | | ZONING TECHNINCIAN | | | CONSTRUCTION SERVICES | | | 805-6720 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2004-11-09 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-11-09 |
Time |
16:12 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2004-11-09 |
Time |
17:22 |
Sent To |
I |
|
| Notes |
| 2004-11-09 00:00:00 | NOTE: OWNER DECIDED NOT TO DO THE 2 | | | CAR | | | GARAGE AND CIRCULAR DRIVEWAY. | | | CONTRACTOR WILL PROVIDE 2 NEW COPY OF | | | SIGN SEAL SITEPLAN. |
|
|