Plan Review Details - Permit 04100990
Plan Review Stops For Permit 04100990
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-03-21 Cont ID  
Sent By shill Date 2005-03-21 Time 08:31 Rev Time 1.00
Received By shill Date 2005-03-21 Time 08:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-01-28 Cont ID  
Sent By shill Date 2005-01-28 Time 10:24 Rev Time 1.50
Received By shill Date 2005-01-28 Time 10:24 Sent To  
Notes
2005-01-28 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE PREVIOUS LIST, ITEM #1.SOME
 SHEETS ON THE CALCS REFER TO IBC RATHER
 THAN FBC, GOVERNING CODE.THE SEAL
 (CALCS) IS TO BE DATED,
 FAC61G1-16.003,004.
  
 2.)SHOW FBC CHAPTER 500 COMPLIANCE,
 EITHER TABLE 500 OR FBC503.2.3.2. (NEW
 COMMENT).
  
 3.)PLEASE NOTE THAT THERE IS A FAILED
 ZONING REVIEW.APPLICANT INFORMED AT
 TIME OF RESUBMITTAL THAT A MINOR SITE
 PLAN AMENDMENT WAS PENDING AND THAT A
 ZONING REVIEW WAS NOT BEING REQUESTED
 AT
 THIS TIME.A PERMIT CANNOT BE ISSUED
 UNTIL THE ZONING REVIEW HAS A PASS
 STATUS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-11-30 Cont ID  
Sent By shill Date 2004-11-30 Time 07:05 Rev Time 3.00
Received By shill Date 2004-11-29 Time 13:24 Sent To Z
Notes
2004-11-29 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)SOME SHEETS ON THE CALCS REFER TO
 IBC RATHER THAN FBC.
  
 2.)DECLARE A BUILDING TYPE, OCCUPANCY
 OF NEW SPACE, OCCUPANCY OF SPACE
 ADJACENT AND BELOW.
  
 3.)CLEARLY INDICATE FIRE SEPARATION
 BETWEEN OCCUPANCIES.THE RATING FOR
 THE
 FLOOR/CEILING ASSEMBLY IS NOT GIVEN.
 PROVIDE ASSEMBLY NUMBER
 OR CALCULATED FIRE RESISTANCE IF
 REQUIRED.
  
 4.)THE DETAILS DO NOT CORRELATE WITH
 THE FLOOR PLAN.THE DETAIL FOR U419
 DOES NOT PROVIDE WHICH RATING YOU ARE
 USING; DOES NOT CORRELATE WITH THE
 FLOOR
 PLAN.FLOOR PLAN INDICATES A 2 HR WALL
 BUT DOES NOT REFER TO U419 OR DETAIL.
  
 5.)SHEET E2 APPEARS TO HAVE CONDUIT
 PENETRATING A STAIRWAY ASSEMBLY WHICH
 IS
 NOT ALLOWED FBC1006.1.3.1.
  
 6.)IS THE MEZZANINE AREA TO BE
 SPRINKLED?NO SPRINKLER HEADS ARE SHOWN
 IN THIS AREA.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-01-20 Cont ID  
Sent By dpalmer Date 2005-01-20 Time 15:51 Rev Time 0.50
Received By dpalmer Date 2005-01-20 Time 15:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-11-02 Cont ID  
Sent By dpalmer Date 2004-11-02 Time 11:53 Rev Time 0.75
Received By dpalmer Date 2004-11-02 Time 11:40 Sent To  
Notes
2004-11-02 00:00:00*********** UNSAT *****************
  
 1)NOTE: PLEASE SEE PLANS ARE REQUIRED TO
 BE SIGNED,DATED AND SEALED AN ENGINEER
 PER FS 471.003H(3)
  
 2)NOTE:PLEASE INCLUDE AN MEANS OF
 DISCONNECT FROM EM/PWR RECEPT INTO BLDG.
 PER 225.31,DISC GROUPED PER 230.72, DISC
 PER 230.76,230.79
  
 3)NOTE: PLEASE SEE POSSIBLE FIRE/BLDG
 REVIEWCOMMENTS. PLANS APPEAR TO SHOW
 CONDUITS BEING ROUTED IN STAIRWAY?
  
 4)NOTE: PLEASE SEE FS 481.221/471.025
 ALL SEALS ARE TO BE CLEAR AND VISABLE
 WITH ALL REQUIRED INFORMATION.
 SEAL(S) IS NOT CLEAR ON ALL SHEETS.
 PLEASE BE SURE NEW SEAL FOR ENGINEER IS
 ALSO VISABLE.
  
 5)NOTE: PLEASE VERIFY ADDRESS SHOWN ON
 TITLE BLOCK. NAMES OKEE SQUARE, WHICH IS
 ON OKEECHOBEE BLVD? YET, JOB APPL/PLANS
 SHOWS A BANYAN BLVD ADDRESS?? APPEARS TO
 BE CHANNEL 5 SITE??
  
  
 6)NOTE: PLAN NOTES MENTIONS, LOAD STUDY
 TO BE DONE OVER A 30 DAYS. LOAD ON
 EXISTING SERVICE SHOULD BE AVAILABLE DUE
 TO BLDG BEING COMPLETED IN THE LAST
 COUPLE OF YEARS. THIS IS REQUIRED AT
 THIS TIME. IF LOAD STUDY CAN BE DONE AT
 THIS TIME BEFORE PERMIT IS ISSUED. THIS
 IS ACCEPTABLE ALSO.
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY HAVE NA AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-02-03 Cont ID  
Sent By mcarsill Date 2005-02-03 Time 08:37 Rev Time 0.00
Received By mcarsill Date 2005-02-03 Time 08:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-11-10 Cont ID  
Sent By mcarsill Date 2004-11-10 Time 12:56 Rev Time 0.00
Received By mcarsill Date 2004-11-10 Time 12:55 Sent To  
Notes
2004-11-10 00:00:001) ZONING DATA INDICATES JURISDICTION
 IS PALM BEACH COUNTY. THE PROJECT
 IS LOCATED WEST PALM BEACH.
  
 2) PLEASE DESCRIBE ANY FIRE
 PROTECTION PROPOSED IN THE
 NEXTEL EQUIPMENT ROOM.
  
 3) FIRE SPRINKLER INFORMATION
 ON PAGE A-5.
  
 4) OKEE-SQUARE IS MENTIONED ON
 PLANS. THIS IS INCORRECT
 INFORMATION.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-03-16 Cont ID  
Sent By adarroug Date 2005-03-16 Time 14:48 Rev Time 0.00
Received By adarroug Date 2005-03-16 Time 14:47 Sent To  
Notes
2005-03-16 00:00:00TO "COMM" BD#64

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-13 Cont ID  
Sent By mjacobs Date 2005-01-13 Time 14:39 Rev Time 0.00
Received By mjacobs Date 2005-01-13 Time 14:39 Sent To  
Notes
2005-01-13 00:00:00TO "COMM BD#13"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date 2004-12-03 Cont ID  
Sent By mjacobs Date 2004-12-03 Time 12:03 Rev Time 0.00
Received By mjacobs Date 2004-10-25 Time 14:44 Sent To  
Notes
2004-10-25 00:00:00TO COMM BD#19

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-01-21 Cont ID  
Sent By pkrauss Date 2005-01-21 Time 14:27 Rev Time 0.40
Received By pkrauss Date 2005-01-21 Time 13:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-11-16 Cont ID  
Sent By pkrauss Date 2004-11-16 Time 17:39 Rev Time 0.40
Received By pkrauss Date 2004-11-16 Time 17:30 Sent To  
Notes
2004-11-16 00:00:00DENIED:
 PLAN SHEET M-3 DETAIL 1 INDICATES
 CONDENSING UNIT MOUNTING OFF THE
 EXTERIOR WALL.PLEASE CLARIFY THE
 ELEVATION OF THE CONDESING UNITS AND HOW
 THEY WILL BE ACCESSED.PLEASE NOTE
 THERE SHALL BE ENOUGH CLEARANCE FOR
 SERVICING AND MAINTENANCE IN ACCORDANCE
 WITH 2001 FBC(M) 306.1 AND THE
 MANUFACTURER'S INSTALLATION
 INSTRUCITONS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS @ (561)805-6719.
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2005-03-21 Cont ID  
Sent By mmclean Date 2005-03-21 Time 10:15 Rev Time 0.00
Received By mmclean Date 2005-03-21 Time 10:15 Sent To  
Notes
2005-03-21 00:00:00APPROVED BY EDNASHA BOWERS, PLANNER
 822-1444, SEE ATTACHED MINOR AMENDMENT
 LETTER.

Review Stop Z ZONING
Rev No 1 Status F Date 2004-12-03 Cont ID  
Sent By mmclean Date 2004-12-03 Time 11:29 Rev Time 2.00
Received By mmclean Date 2004-12-03 Time 11:29 Sent To  
Notes
2004-12-03 00:00:00DENIED, NEED TO PROVIDE CORRECT
 SITEPLAN
 THAT WAS FIRST APPROVED.RANDALL
 GRANBERRY, PLANNER 822-1454. RETURN
 PLANS TO COMM BOARD #19 MM