| Plan Review Stops For Permit 04100990 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2005-03-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-03-21 |
Time |
08:31 |
Rev Time |
1.00 |
| Received By |
shill |
Date |
2005-03-21 |
Time |
08:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2005-01-28 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-01-28 |
Time |
10:24 |
Rev Time |
1.50 |
| Received By |
shill |
Date |
2005-01-28 |
Time |
10:24 |
Sent To |
|
|
| Notes |
| 2005-01-28 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)SEE PREVIOUS LIST, ITEM #1.SOME | | | SHEETS ON THE CALCS REFER TO IBC RATHER | | | THAN FBC, GOVERNING CODE.THE SEAL | | | (CALCS) IS TO BE DATED, | | | FAC61G1-16.003,004. | | | | | | 2.)SHOW FBC CHAPTER 500 COMPLIANCE, | | | EITHER TABLE 500 OR FBC503.2.3.2. (NEW | | | COMMENT). | | | | | | 3.)PLEASE NOTE THAT THERE IS A FAILED | | | ZONING REVIEW.APPLICANT INFORMED AT | | | TIME OF RESUBMITTAL THAT A MINOR SITE | | | PLAN AMENDMENT WAS PENDING AND THAT A | | | ZONING REVIEW WAS NOT BEING REQUESTED | | | AT | | | THIS TIME.A PERMIT CANNOT BE ISSUED | | | UNTIL THE ZONING REVIEW HAS A PASS | | | STATUS. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-11-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2004-11-30 |
Time |
07:05 |
Rev Time |
3.00 |
| Received By |
shill |
Date |
2004-11-29 |
Time |
13:24 |
Sent To |
Z |
|
| Notes |
| 2004-11-29 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 | | | | | | 1.)SOME SHEETS ON THE CALCS REFER TO | | | IBC RATHER THAN FBC. | | | | | | 2.)DECLARE A BUILDING TYPE, OCCUPANCY | | | OF NEW SPACE, OCCUPANCY OF SPACE | | | ADJACENT AND BELOW. | | | | | | 3.)CLEARLY INDICATE FIRE SEPARATION | | | BETWEEN OCCUPANCIES.THE RATING FOR | | | THE | | | FLOOR/CEILING ASSEMBLY IS NOT GIVEN. | | | PROVIDE ASSEMBLY NUMBER | | | OR CALCULATED FIRE RESISTANCE IF | | | REQUIRED. | | | | | | 4.)THE DETAILS DO NOT CORRELATE WITH | | | THE FLOOR PLAN.THE DETAIL FOR U419 | | | DOES NOT PROVIDE WHICH RATING YOU ARE | | | USING; DOES NOT CORRELATE WITH THE | | | FLOOR | | | PLAN.FLOOR PLAN INDICATES A 2 HR WALL | | | BUT DOES NOT REFER TO U419 OR DETAIL. | | | | | | 5.)SHEET E2 APPEARS TO HAVE CONDUIT | | | PENETRATING A STAIRWAY ASSEMBLY WHICH | | | IS | | | NOT ALLOWED FBC1006.1.3.1. | | | | | | 6.)IS THE MEZZANINE AREA TO BE | | | SPRINKLED?NO SPRINKLER HEADS ARE SHOWN | | | IN THIS AREA. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2005-01-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-01-20 |
Time |
15:51 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2005-01-20 |
Time |
15:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-11-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-11-02 |
Time |
11:53 |
Rev Time |
0.75 |
| Received By |
dpalmer |
Date |
2004-11-02 |
Time |
11:40 |
Sent To |
|
|
| Notes |
| 2004-11-02 00:00:00 | *********** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SEE PLANS ARE REQUIRED TO | | | BE SIGNED,DATED AND SEALED AN ENGINEER | | | PER FS 471.003H(3) | | | | | | 2)NOTE:PLEASE INCLUDE AN MEANS OF | | | DISCONNECT FROM EM/PWR RECEPT INTO BLDG. | | | PER 225.31,DISC GROUPED PER 230.72, DISC | | | PER 230.76,230.79 | | | | | | 3)NOTE: PLEASE SEE POSSIBLE FIRE/BLDG | | | REVIEWCOMMENTS. PLANS APPEAR TO SHOW | | | CONDUITS BEING ROUTED IN STAIRWAY? | | | | | | 4)NOTE: PLEASE SEE FS 481.221/471.025 | | | ALL SEALS ARE TO BE CLEAR AND VISABLE | | | WITH ALL REQUIRED INFORMATION. | | | SEAL(S) IS NOT CLEAR ON ALL SHEETS. | | | PLEASE BE SURE NEW SEAL FOR ENGINEER IS | | | ALSO VISABLE. | | | | | | 5)NOTE: PLEASE VERIFY ADDRESS SHOWN ON | | | TITLE BLOCK. NAMES OKEE SQUARE, WHICH IS | | | ON OKEECHOBEE BLVD? YET, JOB APPL/PLANS | | | SHOWS A BANYAN BLVD ADDRESS?? APPEARS TO | | | BE CHANNEL 5 SITE?? | | | | | | | | | 6)NOTE: PLAN NOTES MENTIONS, LOAD STUDY | | | TO BE DONE OVER A 30 DAYS. LOAD ON | | | EXISTING SERVICE SHOULD BE AVAILABLE DUE | | | TO BLDG BEING COMPLETED IN THE LAST | | | COUPLE OF YEARS. THIS IS REQUIRED AT | | | THIS TIME. IF LOAD STUDY CAN BE DONE AT | | | THIS TIME BEFORE PERMIT IS ISSUED. THIS | | | IS ACCEPTABLE ALSO. | | | | | | PLEASE SEE POSSIBLE COMMENTS FROM OTHER | | | REVIEWER(S) WHICH MAY HAVE NA AFFECT ON | | | ELECTRICAL PLANS. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2005-02-03 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2005-02-03 |
Time |
08:37 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2005-02-03 |
Time |
08:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2004-11-10 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-11-10 |
Time |
12:56 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-11-10 |
Time |
12:55 |
Sent To |
|
|
| Notes |
| 2004-11-10 00:00:00 | 1) ZONING DATA INDICATES JURISDICTION | | | IS PALM BEACH COUNTY. THE PROJECT | | | IS LOCATED WEST PALM BEACH. | | | | | | 2) PLEASE DESCRIBE ANY FIRE | | | PROTECTION PROPOSED IN THE | | | NEXTEL EQUIPMENT ROOM. | | | | | | 3) FIRE SPRINKLER INFORMATION | | | ON PAGE A-5. | | | | | | 4) OKEE-SQUARE IS MENTIONED ON | | | PLANS. THIS IS INCORRECT | | | INFORMATION. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-03-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-03-16 |
Time |
14:48 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-03-16 |
Time |
14:47 |
Sent To |
|
|
| Notes |
| 2005-03-16 00:00:00 | TO "COMM" BD#64 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-01-13 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-01-13 |
Time |
14:39 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2005-01-13 |
Time |
14:39 |
Sent To |
|
|
| Notes |
| 2005-01-13 00:00:00 | TO "COMM BD#13" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
|
Date |
2004-12-03 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2004-12-03 |
Time |
12:03 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2004-10-25 |
Time |
14:44 |
Sent To |
|
|
| Notes |
| 2004-10-25 00:00:00 | TO COMM BD#19 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2005-01-21 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-01-21 |
Time |
14:27 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2005-01-21 |
Time |
13:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2004-11-16 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-11-16 |
Time |
17:39 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2004-11-16 |
Time |
17:30 |
Sent To |
|
|
| Notes |
| 2004-11-16 00:00:00 | DENIED: | | | PLAN SHEET M-3 DETAIL 1 INDICATES | | | CONDENSING UNIT MOUNTING OFF THE | | | EXTERIOR WALL.PLEASE CLARIFY THE | | | ELEVATION OF THE CONDESING UNITS AND HOW | | | THEY WILL BE ACCESSED.PLEASE NOTE | | | THERE SHALL BE ENOUGH CLEARANCE FOR | | | SERVICING AND MAINTENANCE IN ACCORDANCE | | | WITH 2001 FBC(M) 306.1 AND THE | | | MANUFACTURER'S INSTALLATION | | | INSTRUCITONS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS @ (561)805-6719. | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2005-03-21 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-03-21 |
Time |
10:15 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-03-21 |
Time |
10:15 |
Sent To |
|
|
| Notes |
| 2005-03-21 00:00:00 | APPROVED BY EDNASHA BOWERS, PLANNER | | | 822-1444, SEE ATTACHED MINOR AMENDMENT | | | LETTER. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2004-12-03 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2004-12-03 |
Time |
11:29 |
Rev Time |
2.00 |
| Received By |
mmclean |
Date |
2004-12-03 |
Time |
11:29 |
Sent To |
|
|
| Notes |
| 2004-12-03 00:00:00 | DENIED, NEED TO PROVIDE CORRECT | | | SITEPLAN | | | THAT WAS FIRST APPROVED.RANDALL | | | GRANBERRY, PLANNER 822-1454. RETURN | | | PLANS TO COMM BOARD #19 MM |
|
|