Plan Review Details - Permit 04100928
Plan Review Stops For Permit 04100928
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-01-27 Cont ID  
Sent By jwitmer Date 2005-01-27 Time 11:51 Rev Time 1.11
Received By jwitmer Date 2005-01-27 Time 11:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-12-23 Cont ID  
Sent By jwitmer Date 2004-12-23 Time 15:02 Rev Time 0.75
Received By jwitmer Date 2004-12-23 Time 15:02 Sent To  
Notes
2004-12-23 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04100928
 ADD: 1710 OKEECHOBEE RD
 CONT: PRESIDENTIAL CONSTRUCTION
 TEL: (561)723-3370
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
 CORRECT THE NOTICE OF COMMENCEMENT
 WRONG STREET NAME, CORRECT TO:
 OKEECHOBEE ROAD
 THE CITY MASTER STREET GUIDE HAS
 OKEECHOBEE ROAD AAS THE CORRECT NAME
 SINCE 1976.
  
 2) CORRECT THE ADDRESS ON THE PLANS TO
 1710 OKEECHOBEE ROAD.
  
 3) WIND EXPOSURE ON PLANS INDICATES A
 "C" ZONE WHEN LOCATED IN A "B" ZONE. IF
  
 DESIGNING TO THE "C" ZONE REQUIREMENTS
 PROVIDE THE MEAN ROOF HEIGHT AND
 PROVIDE
 THE HIGHER POSITIVE AND NEGITIVE
 PRESSURES FOR OPENINGS. SEE TABLE
 1606.2D. PRODUCT APPROVALS WILL REVIEWED
  
 WITH THE NEW PRESSURES.
  
 4) NOTE# 5 FROM PEVIOUS REVIEW, SHEET
 A-1 / A-3 BOTH INDICATE A 8"X8" STEEL
 COLUMN, NOTE 11 ON PAGE 1 INDICATES THE
  
 SIZE OF THE BOTTOM PLATE, BUT NO
 INFORMATION IS PROVIDED FOR THE
 PLACEMENT OF THE HOLES IN THE STEEL
 PLATE. EXAMPLE THE HOLES COULD BE 1/4"
 FROM THE EDGE?
  
 5)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-11-05 Cont ID  
Sent By jwitmer Date 2004-11-05 Time 15:22 Rev Time 4.44
Received By jwitmer Date 2004-11-05 Time 15:22 Sent To  
Notes
2004-11-05 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04100928
 ADD: 1710 OKEECHOBEE ROAD
 CONT:PRESIDENTIAL CONSTRUCTION
 CORP
 TEL: (561)723-3370
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
 1ST REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL
 LETTER
 LISTING THE ORIGINAL REVIEW COMMENT
 NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR
 SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1)PROVIDE NOC RECORDED WITH THE
 CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) FL. BLD CODE 1606.1.7 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 3) SHEET A-3 NOTE# 17 INDICATES THE USE
 OF WELD WIRE MESH IN THE SLAB:
 FL BLDG 1909.3 (EXEPTION# 2)
 CONCRETE SLABS ON GRADE CONTAINING 6X6/
 W1.4XW1.4 WELDED WIRE REINFORCEMENT
 FABRIC LOCATED IN THE MIDDLE TO THE
 UPPER 1/3RD OF THE SLAB SHALL BE SUP-
 PORTED BY APPROVED MATERIALS OR
 SUPPORTS
 AT SPACING NOT TO EXCEED 3 FT OR IN
 ACCORDANCE WITH MANUFACTURER'S SPEC.
  
 4)FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN
 QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE
 EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 5) SHEET A-3 HAS A NOT ABOUT 8"X8"
 STEEL
 COLUMNS,LOCATION OF HOLES FOR BOLTS
 NOR WELDS FOR POST TO BOTTOM PLATE?
  
 6) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 THERESEEMS TO BE A DISCREPANCY
 BETWEEN
 PAGES A-3 NOTE# 25 AND A-4 NOTE# 25,
 LOOKS LIKE A TYP-O ERROR SHOULD BE
 3000 PSI.
  
 7) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET A-4 NOTE# 51, THE MINIMUM LENGHT
 OF THE 1/2" EXSPANSION BOLTS NOT GIVEN?
  
 8) FABRIC AWNINGS OVER DOORWAYS REQUIRE
 A SEPERATE PERMIT.THE SITE IS LOCATED IN
 A FIRE DISTRICT.
 FBC* F102.2.8PERMANENT CANOPIES/
 AWNINGS AND THEIR SUPPORTS, ON BUILDINGS
 LOCATED IN THE FIRE DISTRICT, SHALL BE
 OF NON-COMBUSTIBLE MATERIAL, FIRE
 RETARDANT TREATED WOOD, WOOD OF TYPE III
 SIZES OR OF 1-HOUR RESISTANT
 CONSTRUCTION.ANNOTATE THE PLANS TO
 DEMONSTRATE COMPLIANCE.
  
 9) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EXTERIOR SWING DOORS
 B) OVERHEAD GARAGE DOORS
 C) ROOFING ASSEMBLIES, INSULATION AND
 ROOFING MATERIALS
  
 10) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-08-16 Cont ID  
Sent By dpalmer Date 2005-08-16 Time 06:42 Rev Time 0.30
Received By dpalmer Date 2005-08-16 Time 06:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-03-28 Cont ID  
Sent By dpalmer Date 2005-03-28 Time 14:46 Rev Time 0.25
Received By dpalmer Date 2005-03-28 Time 14:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-01-31 Cont ID  
Sent By dpalmer Date 2005-01-31 Time 10:09 Rev Time 0.30
Received By dpalmer Date 2005-01-31 Time 10:08 Sent To  
Notes
2005-01-31 00:00:00******** PROVISO/REVISE ***********
  
 ***** NOTES REDLINED *********
  
 PLEASE SEE RISER STILL INDICATES AN
 EQUIPMENT GROUNDING CONDUCTOR FROM
 METER
 TO MAIN DISC. PLEASE SEE TWO PREVIOUS
 REVIEWS.
 250.6,250.24
  
 PLEASE SUBMIT THE ABOVE BEFORE ROUGH
 ELECTRICAL INSPECTION.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-12-23 Cont ID  
Sent By dpalmer Date 2004-12-23 Time 14:13 Rev Time 0.33
Received By dpalmer Date 2004-12-23 Time 14:10 Sent To  
Notes
2004-12-23 00:00:00********** UNSAT *****************
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW HAVE STILL NOT BEEN ADDRESSED.
  
 1)NOTE: PLEASE SEE NOTE #'S 2,3, AND 5.
  
 PLEASE SEE 250.66 1/0 MIN
 PLEASE SEE 250.24,250.6 NO, EQUIPMENT
 GROUNDING UNTIL "AFTER" THE FIRST MEANS
 OF DISC.
 PLEASE SEE ADDRESS.
  
 PLANS ARE ALSO COMING BACK WITH COMMENTS
 FROM OTHER REVIEW(S), PLEASE VERIFY IF
 ANY COMMENTS WILL AFFECT ELECTRICAL
 PLANS.
  
  
 2)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) IS NOW ATTACHED WITH
 RESPECT TO DESIGN PROFESSIONAL.
 THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-10-26 Cont ID  
Sent By dpalmer Date 2004-10-26 Time 13:52 Rev Time 0.50
Received By dpalmer Date 2004-10-26 Time 13:52 Sent To  
Notes
2004-10-26 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE SEE PLANS SHOW A NEW BATH
 , YET NO CIRCUITING IS SHOWN FOR THIS??
  
 2)NOTE: PLEASE SEE 250.6,250.24.
 EQUIPMENT GROUNDING CONDUCTORS ARE NOT
 PERMITTED BEFORE THE FIRST MEANS OF
 DISCONNECT.
  
 3)NOTE: PLEASE SIZE GROUDING ELECTRODE
 CONDUCTOR PER 250.66. SHOWN AS #3??
 PLEASE SEE THAT SEC'S ARE PARALLEL 3/0'S
  
 4)NOTE: PLEASE SEE LS 101 5-8 FOR MIN
 LT REQUIRED IN SPACE.
  
 5)NOTE: PLEASE SEE ADDRESS SHOWN ON PLAN
 -S AND SPPLICATION IS SHOWN AS 1710 "OLD
 " OKEECHOBEE. THIS IS OKEECHOBEE RD. AND
 NOT OLD OKEE. PLEASE ALSO SEE BLDG
 REVIEW COMMENTS FOR THIS.
 '
 ********** NOTE **********
 THIS COMMENT FOR OTHER THAN ELECTRICAL
 SHEETS.
 PLEASE SEE ALL PLANS(LANSCAPE ETC) ARE
 REQUIRED TO BE SIGNED,DATED AND SEALED
 BY ALL ARCH'S ENGINEERS. SOME PLANS DO
 NOT CONTAIN ANY SEALS ETC.
 PLEASE ALSO SEE MISSING INFORMATION ON
 TITLE BLOCKS REQUIRED UNDER FAC 61G1-16-
 .004, FS 481.219
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWERS WHICH MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2005-10-14 Cont ID  
Sent By mamini Date 2005-10-14 Time 09:44 Rev Time 0.50
Received By mamini Date 2005-10-14 Time 09:44 Sent To  
Notes
2005-10-14 00:00:00PASSED:
  
 1. REVIEWED FOR DRAINAGE REVISION AS
 SUBMITTED.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2005-01-25 Cont ID  
Sent By mamini Date 2005-01-25 Time 14:16 Rev Time 1.00
Received By mamini Date 2005-01-25 Time 14:16 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2004-12-15 Cont ID  
Sent By mamini Date 2004-12-15 Time 08:55 Rev Time 0.50
Received By mamini Date 2004-12-15 Time 08:55 Sent To  
Notes
2004-12-15 00:00:00FAILED:
  
 1. PLEASE SEE 1ST REVIEW NOTES DATED
 10-28-04.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2004-10-28 Cont ID  
Sent By mamini Date 2004-10-28 Time 08:41 Rev Time 1.00
Received By mamini Date 2004-10-28 Time 08:41 Sent To  
Notes
2004-10-28 00:00:00FAILED:
 1. PLEASE SUBMIT CIVIL PLANS FOR OUR
 REVIEW AND APPROVAL, NOTE THAT DRAINAGE
 SYS. PER CITY OF WEST PALM BEACH'
 CRITERIA MUST BE INCLUDED, AND ALSO
 CALCULATION (SIGNED & SEALED) MUST BE
 SUBMITTED.
 2. PLEASE NOTE THAT CIVIL PLANS MUST BE
 REVIEWED FOR ALL THE CONNECION TO THE
 SERVICES BY THE PUBLIC UTILITITIES AND
 ENGINEERING, ATT;MANNY GONZALEZ 949-1085
 3. ALL PARKING STALLS MUST BE PAINTED
 WITH DOUBLE 4" WIDE STRIPES, AND THE
 ACCESSIBLE PARKING SPACES MUST COMPLY
 WITH FLORIDA AND ADA REQUIREMENTS.
 4. PLEASE STATE THAT, IF THERE IS
 EXSITING SIDE WALK ON OLD OKEECHOBEE RD.
 SOUTH SIDE OF THE PROPERTY, IF SO, SHOW
 THE RELATION TO THE PEDESTRIAN ACCESS
 PATH AS SHOWN.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-01-05 Cont ID  
Sent By mcarsill Date 2005-01-05 Time 17:09 Rev Time 0.00
Received By mcarsill Date 2005-01-05 Time 17:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-11-12 Cont ID  
Sent By mcarsill Date 2004-11-12 Time 12:26 Rev Time 0.00
Received By mcarsill Date 2005-01-05 Time 17:09 Sent To  
Notes
2004-11-12 00:00:001) BUILDING ADDRESS REQUIRED. A MINIMUM
 OF AT LEAST 6" HIGH NUMBERS ARE
 REQUIRED.
  
 2) ARE THERE ANY OTHER FIRE HYDRANTS
 IN THE VICINITY BESIDES THE ONE
 LOCATED NEXT TO THE FIRE DEPARTMENT
 CONNECTION.
  
 3) SEPARATE PLANS AND PERMITS
 REQUIRED FOR FIRE ALARM EQUIPMENT.
  
 4) SEPARATE PLANS AND PERMITS
 REQUIRED FOR ANY FIRE SPRINKLER
 SYSTEM REMODEL.
  
 5) THE FIRE ALARM SYSTEM SHALL BE
 MONITORED BY A LICENSED UL LISTED
 FIRE ALARM COMPANY FOR CENTRAL STATION
 SERVICE.
  
 6) HOW DOES FIRE RESCUE ACCESS THE
 PROPERTY LOCATED BEHIND THE
 SLIDING GATE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-08-09 Cont ID  
Sent By adarroug Date 2005-08-09 Time 17:44 Rev Time 0.00
Received By adarroug Date 2005-08-09 Time 17:44 Sent To E
Notes
2005-08-09 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-03-23 Cont ID  
Sent By adarroug Date 2005-03-23 Time 16:01 Rev Time 0.00
Received By adarroug Date 2005-03-23 Time 16:01 Sent To E
Notes
2005-03-23 00:00:00TO "DPALMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-01-25 Cont ID  
Sent By mjacobs Date 2005-01-25 Time 08:47 Rev Time 0.00
Received By mjacobs Date 2005-01-25 Time 08:47 Sent To  
Notes
2005-01-25 00:00:00TO "COMM BD#52/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-12-14 Cont ID  
Sent By mjacobs Date 2004-12-14 Time 10:54 Rev Time 0.00
Received By mjacobs Date 2004-12-14 Time 10:54 Sent To  
Notes
2004-12-14 00:00:00SENT TO COMM BD#31

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By rgranber Date 2004-10-28 Time 16:53 Rev Time 0.00
Received By csiegber Date 2004-10-25 Time 14:06 Sent To  
Notes
2004-10-25 00:00:00TO COMM BD#47

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-02-17 Cont ID  
Sent By pkrauss Date 2005-02-17 Time 11:32 Rev Time 0.25
Received By pkrauss Date 2005-02-17 Time 11:32 Sent To  
Notes
2005-02-17 00:00:00NO MECHANICAL PLANS OR CONTRACTOR
 SUBMITTED WITH PERMIT APPLICATION.
 PLEASE NOTE, PLAN SHEET A-4 INDICATES
 ROOF TOP UNITS FOR FUTURE INSTALLATION.
 CURBS SHALL COMPLY WITH 2001 FBC 1511.7
 FOR MINIMUM HEIGHT REQUIREMENT ABOVE THE
 ROOF SURFACE.PROVIDE DETAIL WITH
 MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATT KRAUSS AT (561)805-6719.
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-02-17 Cont ID  
Sent By kstevens Date 2005-02-17 Time 11:06 Rev Time 0.76
Received By kstevens Date 2005-02-17 Time 11:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-01-11 Cont ID  
Sent By kstevens Date 2005-01-11 Time 16:29 Rev Time 0.50
Received By kstevens Date 2005-01-11 Time 16:29 Sent To  
Notes
2005-01-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 FROM PREVIOUS REVIEW:
 2) SUBMIT CALCULATIONS FOR PRIMARY ROOF
 DRAINS. SHOW SQUARE FEET AREA OF ROOF
 AND 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS ADDED TO THE AREA OF
 THE ROOF. SHOW THE AREA OF ROOF DRAINED
 AT EACH DOWNSPOUT. INDICATE THE SLOPE
 OF
 THE GUTTER PER TABLE 1106.6.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-11-09 Cont ID  
Sent By kstevens Date 2004-11-09 Time 17:23 Rev Time 0.64
Received By kstevens Date 2004-11-09 Time 17:23 Sent To  
Notes
2004-11-09 00:00:00DENIED
 REFERNEC: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) PER TABLE 403.1 A DRINKING FOUNTAIN
 AND A SERVICE SINK ARE REQUIREDL.
  
 2) SUBMIT A ROOF DETAIL. SHOW PRIMARY
 AND SECONDARY ROOF DRAINS. SUBMIT
 CALCULATIONS FOR PRIMARY AND SECONDARY
 ROOF DRAINS. SHOW SQUARE FEET AREA OF
 ROOF AND 1/2 AREA OF ALL VERTICAL WALLS
 ADDED TO THE AREA OF THE ROOF. SHOW ALL
 PIPE SIZES OF ROOF LEADERS AND/OR
 GUTTERS AND DOWNSPOUTS. IF GUTTERS AND
 DOWNSPOUTS SHOW SIZE OF EACH AND SHOW
 SLOPE OF GUTTER ALONG WITH THE HIGH
 POINTS OF GUTTERS PER TABLE 1106.6
  
 3) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE. SECTION 608.13.2
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2004-10-28 Cont ID  
Sent By rgranber Date 2004-10-28 Time 16:53 Rev Time 0.15
Received By rgranber Date 2004-10-28 Time 16:50 Sent To I
Notes
***NONE***