Plan Review Details - Permit 04100921
Plan Review Stops For Permit 04100921
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-10-29 Cont ID  
Sent By dpalmer Date 2004-10-29 Time 11:13 Rev Time 1.00
Received By dpalmer Date 2004-10-28 Time 16:49 Sent To  
Notes
2004-10-29 00:00:00********** UNSAT ***********
  
 1)NOTE: PLEASE SEE ARCH'S TITLE BLOCK
 AND MISSING LICENSE INFOMATION REQUIRED
 PER FS 481.219 AND FAC 61G1-16.004.
  
 2)NOTE: PLEASE INCLUDE REQUIRED "SHOW"
 WINDOW RECEPTS. PER 210.62
 PLEASE ALSO SEE 220.12 FOR LOADING.
  
 3 )NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
  
 4)NOTE: PLEASE NOTE: ALL RECEPTS IN
 KITCHEN TO BE GFI/GFI PROTECTED.
 210.8
  
 5)NOTE: PLEASE PROVIDE NOTE FOR SHUT-
 DOWN OF ALL ELECTRICAL EQUIPMENT IN
 HOODS/EXHAUST ETC.
 PLEASE SEE NFPA-96
 CHAPTER 7
 CHAPTER 10
  
 6)NOTE: PLEASE PROVIDE LOAD ON THE EXIST
 -ING MDP SHOWN.
 215.5,220
  
 PLEASE SEE POSSIBLE NOTES FROM OTHER
 REVIEWER(S) WHICHY MAY HAVE AN AFFECT
 ON ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT ONLY NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-11-12 Cont ID  
Sent By mcarsill Date 2004-11-12 Time 09:51 Rev Time 0.00
Received By mcarsill Date 2004-11-12 Time 09:51 Sent To  
Notes
2004-11-12 00:00:001) PANIC HARDWARE REQUIRED ON EXIT
 DOORS SUBJECT TO AN OCCUPANCY OF
 100 OR MORE PERSONS.
  
 2) HOW WILL EXITING BE MAINTAINED
 IN THE REAR OF THE ESTABLISHMENT.
 AREAS ARE NOTED AS STORAGE AREAS.
  
 3) SEPARATE PLANS AND PERMITS
 REQUIRED FOR ANY HOOD,DUCT, AND
 SUPPRESSION SYSTEMS.
  
 4) PLEASE PROVIDE DRAWING OF SIGN
 PLANNED FOR THE FRONT DOOR INDICATING
 DOOR TO REMAIN UNLOCKED DURING
 BUSINESS HOURS.
  
 5) PLEASE INDICATE INTERIOR FINSH
 CLASSIFICATION FOR WALLS AND
 CEILINGS.
  
 6) IS THE BUILDING FIRE SPRINKLER
 PROTECTED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By csiegber Date 2004-10-25 Time 15:40 Sent To  
Notes
2004-10-25 00:00:00TO COMM BD#22

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-11-16 Cont ID  
Sent By pkrauss Date 2004-11-16 Time 13:24 Rev Time 0.50
Received By pkrauss Date 2004-11-16 Time 12:58 Sent To  
Notes
2004-11-16 00:00:00DENIED:
 1.PLAN SHEET M2.01 CONDENSER MOUNTING
 DETAIL - PLAN INDICATES 18" FROM THE
 ROOF SURFACE TO THE BOTTOM OF THE
 SUPPORT RAIL.THE 18" CLEARANCE IS
 OKAY
 IF THE WIDTH OF THE CONDENSER IS
 GREATER
 THAN 24" AND LESS THAN 36".SEE 2001
 FBC 1511.7 FOR PROPER CLEARANCE.
  
 2.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 SHALL HAVE NOTIFICATION TO ALARM/STROBE
 IN NORMALLY OCCUPIED AREAS PER 2001
 FBC(M)606.4.1.
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPPRESSION, AND WALK-IN COOLERS.
 PLEASE PROVIDE MANUFACTURER INSTALLATION
 INSTRUCTIONS, CUT SHEETS AND PLAN
 SHOWING GREASE DUCT TERMINATION, LAYOUT,
 CLEANOUTS, AND CLEARANCES TO
 COMBUSTIBLES WITH THE PERMIT
 APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS @(561)805-6719.

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-11-18 Cont ID  
Sent By kstevens Date 2004-11-18 Time 12:43 Rev Time 2.15
Received By kstevens Date 2004-11-18 Time 12:43 Sent To  
Notes
2004-11-18 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) CONTACT RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE FOR THE SIZING OF THE GREASE
 INTERCEPTOR. WASTE ORD. #2938-96 (561)
 837-4074. ATTACH COPY OF RESPONSE
 LETTER
 FROM MR. COMPO TO PLANS WHEN
 RESUBMITTING.
 2) SHTS P1.01 AND P2.01 SAFE WASTE NOT
 APPROVED AT ICE MACHINE. FLOOR DRAIN
 NOT
 APPROVED FOR INDIRECT WASTE. SECTIONS
 802.3 & 802.3.2. (ALSO DELETE SAFE
 WASTE
 DETAIL)
 3) DISH WASHER SHALL NOT CONNECT TO
 GREASE SYSTEM. DISH WASHER SHALL
 CONNECT
 TO THE SANITARY SYSTEM.
 4) SHTS P1.01 & P2.01 SHALL NOT DRAIN
 THROUGH THE HORIZONTAL WET VENT OF THE
 BATHROOM FIXTURES. SECTION 909.1. HAND
 SINK SHALL DISCHARGE DOWNSTREAM OF THE
 BATHROOM FIXTURES.
 5) THE FOLLOWING INFORMATION IS
 REQUIRED
 FOR THE GAS PERMIT. SEPARATE GAS PERMIT
 REQUIRED.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. TYPE OF GAS, (LP OR NATURAL)
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM
 PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 E. SUBMIT MANUFACTURE SHEETS FOR ALL
 GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 F. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY
 LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS,
 BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 G. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 H. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 6) SHOW CLEAR FLOOR SPACE AND TURNING
 AREA FOR EACH TOILET ROOM PER SECTIONS
 11-4.16.2, 11-4.19.3, AND 11-4.22.3.
 7) THE FIRM LICENSE NUMBER SHALL BE
 CONTAINED IN THE TITLE BLOCK PER FAC
 61G1-16.004(2) & FS 481.219
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]