Plan Review Details - Permit 04100911
Plan Review Stops For Permit 04100911
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-01-25 Cont ID  
Sent By alange Date 2005-01-25 Time 07:48 Rev Time 1.25
Received By alange Date 2005-01-25 Time 07:37 Sent To  
Notes
2005-01-25 00:00:00DENIED
  
  
 1.PLANS DO NOT REFLECT WORK ON
 ORIGONAL APPLICATION.
  
 2.SHOW ON PLANS NEW AND EXISTING
 WORK.
  
 3. PLANS SHOW FOUNDATION WORK.SHOW NEW
 AND EXISTING AREAS. IS THE EXTERIOR
 BEARING WALL ON SECTION "A" CANTELEVERED
 OUT 2 FT?
  
 4.SHOW NEW WINDOWS AND DOORS, TYPES
 AND SIZES.
  
 5.SUBMIT PRODUCT APPROVALS FOR THE
 FOLLOWING.STRAPS AND TIEDOWNS,
 ROOFING, WINDOWS, EXTERIOR DOORS AND
 IMPACT PROTECTION.
 ALL PRODUCT APPROVALS REQUIRE THE
 FOLLOWING TO BE ATTACHED TO THE QUALITY
 ASSURANCE REPORTS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-10-26 Cont ID  
Sent By spalmer Date 2004-10-26 Time 08:22 Rev Time 0.25
Received By spalmer Date   Time   Sent To  
Notes
2004-10-26 00:00:00APPROVED PER STEVE NICOLOSI

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-01-24 Cont ID  
Sent By dpalmer Date 2005-01-24 Time 08:31 Rev Time 0.50
Received By dpalmer Date 2005-01-24 Time 08:31 Sent To B
Notes
2005-01-24 00:00:00************ UNSAT ****************
  
 1)NOTE: PLEASE CLARIFY SCOPE OF WORK.
 PLANS APPEAR TO SHOW SOME NEW
 ELECTRICAL YET EXISTING IS NOT
 INDICATED?
 IF SCOPE OF WORK IS FOR NEW RE-WIRE DUE
 TO FIRE, PLEASE SUBMIT PLANS FOR
 COMPLATE LAYOUT OF ELECTRICAL DEVICES
 PER 2002 NEC AND NFPA-72 FOR SD'S.
 PLEASE SEE
 210.52,210.52C1,210.8A6,210.52D/210.11C3
 10.52,210.52C1,210.8A6,210.52D/210.11C3
 210.52E,210.63,440.11.
 PLEASE ALSO SEE 220.31 FOR LOAD
 CALCUALTIONS, AHU/HEAT SHOWN AT 40%
 DERATING??.
  
 2)NOTE: PLEASE SEE THIS PERMIT CAME IN
 FOR A $50,000 MISC PERMIT. AN MISC
 INSPECTION BY AN ELECTRICAL INSPECTOR
 MAY BE NEEDED TO DETERMINE COMPLETE
 SCOPE OF WORK.
 PLEASE ALSO SEE CHAPTER 34 FO THE FBC
 FOR REWORK OF EXISTING HOUSES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-13 Cont ID  
Sent By mjacobs Date 2005-01-13 Time 16:22 Rev Time 0.00
Received By mjacobs Date 2005-01-13 Time 16:22 Sent To E
Notes
2005-01-13 00:00:00TO "DP" DESK./REV.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-10-22 Cont ID  
Sent By spalmer Date 2004-10-22 Time 11:43 Rev Time 0.25
Received By spalmer Date   Time   Sent To  
Notes
2004-10-22 00:00:00NO PLANS SUBMITTED FOR WORK ON THIS
 PROPERTY