| 2004-11-18 00:00:00 | DENIED |
| | |
| | |
| | 1. 713.13 F.S.A NOTICE OF COMMENCEMENT |
| | SHALL BE RECORDED AT PALM BEACH COUNTY |
| | COURTHOUSE AND A COPY SUBMITTED TO THIS |
| | OFFICE BEFORE A PERMIT CAN BE ISSUED. |
| | BLANK FORMS ARE AVAILABLE FROM THIS |
| | OFFICE. |
| | NOTE: THE NOTICE OF COMMENCEMENT MUST BE |
| | RE-RECORDED IF THE DESCRIBED IMPROVEMENT |
| | OR CONSTRUCTION IS NOT COMMENCED WITHIN |
| | 90 DAYS OF RECORDING. |
| | |
| | |
| | 2.BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 3.ALL PLANS SUBMITTED SHALL BEAR THE |
| | NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN.FBC104.2.1 |
| | |
| | 4.SUBMIT 2 COPIES OF ENERGY CALCS. |
| | |
| | 5.SHOW METHOD OF CRAWL SPACE |
| | VENTILATION. |
| | |
| | 6.SHOW FASTENING SCHEDULE FOR NAILING |
| | OF ROOF AND WALL SHEATHING. |
| | |
| | 7.SUBMIT TWO COMPLETE COPIES OF |
| | PRODUCT APPROVALS FOR EXTERIOR DOORS, |
| | WINDOWS, ROOFING AND STRAPS AND |
| | TIE-DOWNS. |
| | QUALITY ASSURANCE TESTING IS TO BE |
| | INCLUDED WITH THE FOLLOWING. |
| | |
| | |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 8.SHOW SIZE OF BEDROOM WINDOWS AND |
| | TYPES SO THAT EMERGENCY ESCAPE OPENING |
| | SIZES CAN BE CALCULATED. FBC 1005.4.4 |
| | |
| | 9.SHOW SIZES OF BATHROOM DOORS. AT |
| | LEAST ONE DOOR SHALL MEET A CLEAR |
| | OPENING OF 29 INCHES.FBC11-11 |
| | |
| | 10.SUBMIT TWO COPIES OF A SITE PLAN |
| | SHOWING EXISTING BUIDINGS ON PROPERTY |
| | AND NEW ROOM ADDITION. |
| | |
| | 11.SHOW METHOD OF TIE-IN FROM EXISTING |
| | SLAB TO NEW SLAB. |
| | |
| | 12.SHOW ON PLANS EXISTING BUILDING AND |
| | SHOW NEW WORK SPECIFIED ON PLANS. |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | ART LANGE |
| | BUILDING PLANS EXAMINER |
| | 805-6672 |