| Plan Review Stops For Permit 04100855 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2005-02-04 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-02-04 |
Time |
15:32 |
Rev Time |
1.00 |
| Received By |
shill |
Date |
2005-02-04 |
Time |
15:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-11-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2004-11-22 |
Time |
15:35 |
Rev Time |
3.00 |
| Received By |
shill |
Date |
2004-11-22 |
Time |
15:35 |
Sent To |
Z |
|
| Notes |
| 2004-11-23 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)OCCUPANCY IS NOT CLEAR.THE | | | APPLICATION REFERS TO THE SPACE AS A | | | "SHOP" (MERCANTILE), APPEARS TO BE | | | BUSINESS BASED ON THE USE OF THE ROOMS. | | | | | | 2.)THE DOORS AT THE ACCESSIBLE | | | BATHROOM AND OFFICE #2 DO NOT COMPLY | | | WITH FBC1012.1.4; OBSTRUCT OVER HALF THE | | | REQUIRED WIDTH OF EGRESS. | | | | | 2004-11-22 00:00:00 | THESE PLANS ARE @ SH DESK. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2005-02-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-02-01 |
Time |
16:16 |
Rev Time |
0.30 |
| Received By |
dpalmer |
Date |
2005-02-01 |
Time |
16:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-10-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-10-26 |
Time |
13:02 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2004-10-26 |
Time |
10:46 |
Sent To |
|
|
| Notes |
| 2004-10-26 00:00:00 | *************** UNSAT ************** | | | | | | 1)NOTE: PLEASE PROVIDE ALL INFORMATION | | | ON TITLE BLOCK AS REQUIRED UDNER FAC | | | 61G1-16.004 AND FS 481.219. | | | PLEASE SEE MISSING FIRM LICENSE #. | | | THIS IS REQUIRED ON ALL SHEETS AND FOR | | | ALL TRADES WHEATHER OR NOT COMMENT IS | | | MADE BY OTHER REVIEWER(S). | | | | | | 2)NOTE: PLEASE SEE RISER AND PANEL SCHED | | | -ULE BOTH INDICATE 200A PANEL AS NEW. | | | PLEASE SEE PLAN LAYOUT SHOWS PANEL AS | | | EXISTING?? PLEASE CORRELATE. | | | | | | 3)NOTE: PLEASE SEE EXT/ EM LTS APPEAR | | | TO BE SHOWN AS BEING SWITCHED?? | | | THESE ARE NOT PERMITTED TO BE SWITCHED | | | AND MAY JUST NEED A NOTE TO MENTION: | | | "TO BE WIRED AHEAD OF ANY LOCAL SWITCH" | | | ?? | | | | | | 4)NOTE: PLEASE ALSO PROVIDE AIC RATING | | | FOR NEW MCB SHOWN BELOW METER. | | | AIC RATING OF NEW PANEL IS NOTED: | | | 110.9,215.5 | | | | | | 5)NOTE: PLEASE PROVIDE LOAD ON EXISTING | | | 800A WIREWAY. | | | 215..5,220 | | | | | | 6)NOTE: PLEASE SEE 220.13 FOR MIN 180VA | | | PER RECEPT/YOKE. PLEASE SEE LOADS ON | | | PANEL SCHEDULE DO NOT SEEM TO CORRELATE | | | WITH THE # OF RECEPTS ON SOME RECEPT | | | CIRCUITS. | | | | | | PLEASE SEE POSSIBLE COMMENTS FROM OTHER | | | REVIEWER(S) WHICH MAY AFFECT ELECTRICAL | | | PLANS. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AN | | | INSERT NEW INTO TWO COMPLETE SETS FOR | | | REVIEW AND STAMPING. | | | | | | ***PLEASE NOTE: THIS IS ONLY IN FOR PLAN | | | REVIEW AT THIS TIME AND NOT FOR PERMIT. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2005-02-07 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2005-02-07 |
Time |
13:18 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2005-02-07 |
Time |
13:18 |
Sent To |
|
|
| Notes |
| 2005-02-07 00:00:00 | REVIEWED AND APPROVED BY MIKE CARSILLO | | | ON 02-04-05 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2004-11-12 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-11-12 |
Time |
11:22 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-11-12 |
Time |
11:22 |
Sent To |
|
|
| Notes |
| 2004-11-12 00:00:00 | 1) PLEASE EXPLAIN EXIT ACCESS | | | WIDTHS OF 32 INCHES. IT APPEARS | | | THAT DOORS OPEN INTO EXIT ACCESS | | | AREAS WHICH REDUCES THE WIDTH | | | USED FOR EXITING. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-01-26 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-01-26 |
Time |
16:14 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2005-01-26 |
Time |
16:14 |
Sent To |
|
|
| Notes |
| 2005-01-26 00:00:00 | TO "COMM BD#29" /RESUB. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-12-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2004-12-07 |
Time |
10:49 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2004-11-22 |
Time |
13:37 |
Sent To |
|
|
| Notes |
| 2004-11-22 00:00:00 | THESE PLANS ARE @ SH DESK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
|
Date |
2004-11-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2004-11-23 |
Time |
15:06 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2004-10-25 |
Time |
14:57 |
Sent To |
|
|
| Notes |
| 2004-10-25 00:00:00 | TO COMM BD#49 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2005-02-08 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-02-08 |
Time |
15:28 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2005-02-08 |
Time |
13:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2004-11-16 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-11-16 |
Time |
12:36 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2004-11-16 |
Time |
12:33 |
Sent To |
|
|
| Notes |
| 2004-11-16 00:00:00 | DENIED: | | | 1.PLAN SHEET M101, PLAN INDICATES | | | BATHROOM EXHAUST "EXISTING FLEX".PER | | | 2001 FBC(M) 501.5, EXHAUST DUCTS SHALL | | | BE OF METAL. | | | | | | 2.PLAN ALSO INDICATES RETURN AIR FROM | | | THE BATHROOM AREAS, AIR SHALL NOT BE | | | RECIRCULATED PER 2001 FBC(M) 403.3 & | | | 501.2. | | | | | | 3.PLAN SHEET A100 INDICATES TREATMENT | | | RM #7 AS A "CLOSED SYSTEM", PLEASE | | | CLARIFY WHAT IS MEANT BY A "CLOSED | | | SYSTEM".WHAT TYPE OF "TREATMENT" WILL | | | BE CONDUCTED? | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS @ (561)805-6719. | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2005-02-17 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-02-17 |
Time |
09:20 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2005-02-17 |
Time |
09:20 |
Sent To |
|
|
| Notes |
| 2005-02-17 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 11 | | | | | | 1) SHT A101 IF TOILET ROOMS ARE PROVIDED | | | THEN EACH PUBLIC AND COMMON USE TOILET | | | ROOM SHALL COMPLY WITH SECTION 11-4.22. | | | PLEASE SHOW CLEAR FLOOR SPACE FOR EACH | | | FIXTURE AND THE 5' TURNING AREA FOR | | | TOILET ROOM #4. ALSO SHOW GRAB BARS ON | | | FLOOR PLAN PER SECTION 11-4.16.4.ALSO | | | DOORS SHALL NOT SWING INTO THE CLEAR | | | FLOOR SPACE REQUIRED FOR ANY FIXTURE. | | | SECTION 11-4.22.2. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2004-11-09 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-11-09 |
Time |
13:33 |
Rev Time |
0.75 |
| Received By |
kstevens |
Date |
2004-11-09 |
Time |
13:33 |
Sent To |
|
|
| Notes |
| 2004-11-09 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1) MORE INFORMATION REQUIRED. INDICATE | | | TYPE OF BUSINESS SO AS TO ESTABLISH THE | | | OCCUPANCY OF THE SHOP. SECTION 104.2.1 | | | 2) INDICATE SQUARE FOOTAGE OF SPACE. | | | SECTION 104.2.1 | | | 3) IF BATHING ROOMS ARE PROVIDED, THEN | | | EACH PUBLIC AND COMMON USE BATHROM | | | SHALL | | | COMPLY WITH 11-4.23. SUBMIT A DETAIL | | | FOR | | | ALL FIXTURES IN TOILET ROOMS 4 & 5. | | | SHOW | | | COMPLIANCE WITH 11-4.26, 11-4.19, | | | 11-4.21, AND 11-4.23 AND ALL | | | SUBSECTIONS. | | | 4) SINK IN WORK ROOM #8 SHALL COMPLY | | | WITH 11-4.24. AND ALL SUBSECTIONS. | | | 5) SHT P101 THERMAL EXPANSION CONTROL | | | IS | | | REQUIRED PER SECTION 607.3. SHOW ON | | | HEATER. | | | 6) SHT P101 PLUMBING FIXTURE & LEGEND: | | | CTI COLON THERAPY INSTRUMENT "WATER | | | SUPPLY AND DRAINAGE ACCORDING TO | | | MANUFACTURER'S SHOP DRAWINGS. SUBMIT | | | DRAWINGS TO VERIFY CONNECTIONS. SUBMIT | | | MANUFACTURE SPECIFICATIONS FOR LTI | | | UNIT, | | | SHOWING APPROVAL FOR FIXTURE. NO WATER | | | CONNECTION SHOWN ON WATER RISER | | | DIAGRAM. | | | PLEASE CLARIFY. IF WATER CONNECTION, | | | BACKFLOW PROTECTION REQUIRED | | | PER SECTION 609.6. | | | 7) SHT P101 SANITARY RISER DIAGRAM DOES | | | NOT MEET CODE REQUIREMENTS. LT1 SINK | | | UPSTREAM OF TOILET ROOM #4 NOT VENTED. | | | 8) FIRM LICENSE NUMBER REQUIRED | | | (CERTIFICATE OF AUTHORIZATION) | | | 61G1-16.004(2) - FS 481.219 | | | | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2004-12-06 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2004-12-06 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2004-12-06 |
Time |
11:09 |
Sent To |
B |
|
| Notes |
| 2004-12-06 00:00:00 | ALL INTERIOR CHANGES.TYPE OF USE IS | | | ALLOWED IN GC (OFFICE, THERAPUTIC | | | MASSAGE). PLANS GIVEN TO SAMATHA H |
|
|