Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-11-15 Cont ID  
Sent By lmartine Date 2004-11-15 Time 16:44 Rev Time  
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-10-26 Cont ID  
Sent By dpalmer Date 2004-10-26 Time 09:47 Rev Time 0.25
Received By dpalmer Date 2004-10-26 Time 09:46 Sent To  
Notes
2004-10-26 00:00:00SPOKE TO ARCHITECT, EXISTING LOCATIONS,
 REPAIR AND REPLACE DRYWALL ONLY.
 OK, STAMPED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-10-25 Cont ID  
Sent By dpalmer Date 2004-10-25 Time 15:32 Rev Time 0.33
Received By dpalmer Date 2004-10-25 Time 14:43 Sent To  
Notes
2004-10-25 00:00:00************* UNSAT ***************
  
 1)NOTE: PLEASE SHOW CIRCUITING ON PLANS
 AND CORRELATE WITH A PANEL SCHEDULE.
  
 2)NOTE: PLEASE CLARIFY NEW OR EXISTING
 SIGN CIRCUIT. 600.5 IS THIS A TENANT
 SPACE?
  
 3)NOTE: PLEASE SEE POSSIBLE FIRE REVIEW
 COMMENTS FOR ANY EM/EXT LTS AND SEE
 700.12E FOR CIRCUITING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2004-11-15 Cont ID  
Sent By lmartine Date 2004-11-15 Time 16:46 Rev Time  
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-12-07 Cont ID  
Sent By nmccray Date 2004-12-07 Time 12:46 Rev Time 0.00
Received By nmccray Date 2004-12-07 Time 12:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status N Date 2004-11-30 Cont ID  
Sent By mjacobs Date 2004-11-30 Time 15:39 Rev Time 0.00
Received By mjacobs Date 2004-11-30 Time 15:39 Sent To FIRE
Notes
2004-11-30 00:00:00SENT TO "FIRE" BOX/RESUB.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-11-12 Cont ID  
Sent By mcarsill Date 2004-11-12 Time 10:06 Rev Time 0.00
Received By mcarsill Date 2004-11-12 Time 10:06 Sent To  
Notes
2004-11-12 00:00:001) PLANS DO NOT INDICATE LOCATIONS
 OF ANY EXISTING NEW OR EXISTING
 EMERGENCY LIGHTS OR EXIT SIGNS.
  
 2) THE PLANS DO NOT ILLUSTRATE
 EXITING EXITS OR EXIT ROUTES.
  
 3) HOW DOES THE FUTURE LOFT AFFECT
 THE EXISTING SPACE.
  
 4) PLEASE INDICATE PROPOSED
 OCCUPANT LOAD FOR THE BUILDING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-10-25 Cont ID  
Sent By csiegber Date 2004-10-25 Time 13:48 Rev Time 0.00
Received By csiegber Date 2004-10-25 Time 13:48 Sent To  
Notes
2004-10-25 00:00:00TO COMM BD#30

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-11-16 Cont ID  
Sent By lmartine Date 2004-11-16 Time 13:40 Rev Time  
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2004-11-15 Cont ID  
Sent By lmartine Date 2004-11-15 Time 16:49 Rev Time  
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2004-11-15 Cont ID  
Sent By lmartine Date 2004-11-15 Time 16:50 Rev Time  
Received By lmartine Date   Time   Sent To  
Notes
***NONE***