Plan Review Details - Permit 04100830
Plan Review Stops For Permit 04100830
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-01-25 Cont ID  
Sent By jwitmer Date 2005-01-25 Time 12:38 Rev Time 0.25
Received By jwitmer Date 2005-01-25 Time 12:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-12-16 Cont ID  
Sent By jwitmer Date 2004-12-16 Time 15:02 Rev Time 0.55
Received By jwitmer Date 2004-12-16 Time 15:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-11-23 Cont ID  
Sent By jwitmer Date 2004-11-23 Time 12:21 Rev Time 0.75
Received By jwitmer Date 2004-11-23 Time 12:21 Sent To PC
Notes
2004-11-23 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04100830
 ADD: 2505 OKEECHOBEE BLVD
 CONT: PRO BUILD INC
 TEL: (305)301-1817
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
  
 1)PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 3) PROVIDE WHAT TYPE OF FLEXIBLE
 ASSEMBLY THAT WILL BE USED AT THE
 DEMISSING WALL/ ROOF FOR FIRE RATING?
 705.7.1 JOINTS INSTALLED IN OR BE-
 TWEEN FIRE RESISTANT WALLS, FIRE RESIS-
 TANT FLOORS OR FLOOR/ CEILING ASSEMBLIES
 AND FIRE RESISTANT ROOFS OR ROOF/ CEIL-
 ING ASSEMBLIES SHALL BE PROTECTED BY AN
 APPROVED FIRE RESISTANT JOINT SYSTEM
 DESIGNED TO RESIST THE PASSAGE OF FIRE
 FOR A PERIOD NOT LESS THAN THE RE-
 QUIRED FIRE RESISTANCE RATING OF THE
 WALL, FLOOR OR FLOOR IN OR BETWEEN
 WHICH IT IS INSTALLED.
  
 4) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PROVIDE
 THE WIDTH OF THE HALLWAY DIRECTLY IN
 FRONT OF THE HANDICAPPED RESTROOMS?
 1012.1.4. DURING ITS SWING, ANY DOOR
 IN A MEANS OF EGRESS SHALL LEAVE
 UNOBSTRUCTED AT LEAST 1/2 OF THE REQUIRE
 REQUIRED WIDTH OF AN AISLE, CORRIDOR,
 PASSAGEWAY, OR LANDING, NOR PROJECT MORE
 THAN 7" INTO THE REQUIRED WIDTH.
  
 5)TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-01-20 Cont ID  
Sent By dpalmer Date 2005-01-20 Time 13:31 Rev Time 0.30
Received By dpalmer Date 2005-01-20 Time 13:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-12-23 Cont ID  
Sent By dpalmer Date 2004-12-23 Time 10:35 Rev Time 0.33
Received By dpalmer Date 2004-12-23 Time 10:17 Sent To  
Notes
2004-12-23 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE SEE NOTE #1 FROM PREVIOUS
 REVIEW STILL NEEDS TO BE ADDRESSED.
 PLEASE SEE FAC 61G15-23.002 AND
 FS471.023.
 THIS IS REQUIRED ON ALL PLANS WHICH
 CONTAIN TITLE BLOCK FOR ENGINEERING FIRM
 AS SHOWN.
  
 2)NOTE: PLEASE ALSO SEE ORIGINAL NOTES
 REQUESTED ALL OLD/VOIDED SHEETS TO
 REMOVED AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING.
 THIS WAS NOT DONE.
 ONE SET OF EACH OF OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED SEPARATELY FOR
 REFERENCE ONLY.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-10-25 Cont ID  
Sent By dpalmer Date 2004-10-25 Time 16:04 Rev Time 0.75
Received By dpalmer Date 2004-10-25 Time 16:04 Sent To  
Notes
2004-10-25 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE INCLUDE ALL LICENSE #'S
 ON TITLE BLOCK AS REQUIRED UNDER FAC
 61G15-23.002, FS 471.023.
  
 2)NOTE: PLEASE SEE PANEL SCHEDULE INDI-
 -CATES NEW AND EXISTING SIGN CIRCUIT,
 HOWEVER THIS COULD NOT BE LOCATED ON
 PLANS AT LOCATION REQUIRED PER 600.5
  
 3 )NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
 PLEASE ALSO SHOW LOADING/CALCS FOR TRK
 LTS PER 220.12
  
 4)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULES. PLEASE SEE 700.12E
 FOR CIRCUITING OF EM/EXT LTS.
  
 5)NOTE: PLEASE SEE RISER DIAGRAM
 MENTIONS TO VERIFY A MIN OF 100A SERVICE
 TO EACH PANEL.
 THIS NEEDS TO BE VERIFIED AT THIS TIME
 AND PLACE ON PLANS FOR CODE COMPLIANCE
 AND MEETING MIN LOADS.
 215.5
  
 PLEASE SEE POSSIBLE COMMENT FROM OTHER
 REVIEWER(S) AS THEY MAY HAVE AN AFFECT
 ON ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND INSERT ONLY NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD/VOIDED SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-12-29 Cont ID  
Sent By nmccray Date 2004-12-29 Time 15:30 Rev Time 0.00
Received By nmccray Date 2004-12-29 Time 15:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-11-12 Cont ID  
Sent By mcarsill Date 2004-11-12 Time 10:44 Rev Time 0.00
Received By mcarsill Date 2004-11-12 Time 10:44 Sent To  
Notes
2004-11-12 00:00:001) DEMOLITION, RENOVATION AND
 CONSTRUCTION TO COMPLY WITH
 NFPA 241.
  
 2) DEBRIS SHALL BE REMOVED FROM
 THE SITE DAILY.
  
 3) ENSURE THAT ALL EXISTING
 EMERGENCY LIGHT FIXTURE AND EXIT
 SIGNS ARE IN GOOD WORKING ORDER.
  
 4) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND
 CEILINGS. ALSO PLEASE PROVIDE
 FLAMESPREAD INFORMATION FOR
 DRESSING ROOM CURTAINS.
  
 5) PLEASE INDICATE LOCATIONS OF
 ALL PORTABLE FIRE EXTINGUISHERS.
  
 6) PLEASE PROVIDE A LIFE SAFETY PLAN
 INDICATING TRAVEL DISTANCES AND
 OCCUPANT
 LOADS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-01-13 Cont ID  
Sent By mjacobs Date 2005-01-13 Time 15:23 Rev Time 0.00
Received By mjacobs Date 2005-01-13 Time 15:23 Sent To  
Notes
2005-01-13 00:00:00TO "COMM BD#31"/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-12-10 Cont ID  
Sent By mjacobs Date 2004-12-10 Time 15:31 Rev Time 0.00
Received By mjacobs Date 2004-12-10 Time 15:30 Sent To  
Notes
2004-12-10 00:00:00SENT TO COMM BD#13/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-11-23 Cont ID  
Sent By jwitmer Date 2004-11-23 Time 12:47 Rev Time 0.00
Received By jwitmer Date 2004-10-25 Time 13:54 Sent To PC
Notes
2004-10-25 00:00:00TO COMM BD#17

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-01-28 Cont ID  
Sent By kstevens Date 2005-01-28 Time 14:47 Rev Time 0.64
Received By kstevens Date 2005-01-28 Time 14:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-01-10 Cont ID  
Sent By kstevens Date 2005-01-10 Time 18:08 Rev Time 0.33
Received By kstevens Date 2005-01-10 Time 18:08 Sent To  
Notes
2005-01-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) FROM PREVIOUS REVIEW:
 SUBMIT A DETAIL FOR DRINKING FOUNTAIN
 SHOWING COMPLIANCE WITH SECTION 11-4.15
 AND ALL SUBSECTIONS.
 2) FROM PREVIOUS REVIEW:
 IF PRACTICING THROUGH A DULY AUTHORIZED
 ENGINEERING BUSINESS, ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME AND LICENSE
 NUMBER, AS WELL AS THE NAME, ADDRESS,
 AND CERTIFICATE OF AUTHROIZATION NUMBER
 OF THE ENGINEERING BUSINESS ON EACH
 SHEET. FAC 61G15-23.002(2) & FS
 471.025.
 *********NEW COMMENTS*********
 1B) REMOVE ALL VOIDED SHEETS AND SUBMIT
 ONE SET OF VOIDED SHEETS FOR COMPAIRSON.
 SUBMIT TWO SETS OF PLANS FOR REVIEW.
 SECTION 104.2.1.
 2B) SEE ATTACHED SHEET CONCERNING DESIGN
 PROFESSIONAL AND FS 553.80(2)(B).
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-11-08 Cont ID  
Sent By kstevens Date 2004-11-08 Time 16:26 Rev Time 57.00
Received By kstevens Date 2004-11-08 Time 16:26 Sent To  
Notes
2004-11-08 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SUBMIT A DETAIL FOR DRINKING FOUNTAIN
 SHOWING COMPLIANCE WITH SECTION 11-4.15
 AND ALL SUBSECTIONS. SECTION 104.2.1.
 2) IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS,
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME AND LICENSE NUMBER, AS WELL AS THE
 NAME, ADDRESSM, AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. 61G15-23.002(2)
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]