| Plan Review Stops For Permit 04100804 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
P |
Date |
2006-05-23 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2006-05-23 |
Time |
09:29 |
Rev Time |
0.50 |
| Received By |
jgomez |
Date |
2006-05-23 |
Time |
09:29 |
Sent To |
PC |
|
| Notes |
| 2006-05-23 00:00:00 | MULLION DETAIL AND ENGINEER'S LETTER. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
F |
Date |
2006-04-05 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2006-04-05 |
Time |
14:46 |
Rev Time |
0.50 |
| Received By |
jgomez |
Date |
2006-04-05 |
Time |
14:46 |
Sent To |
M |
|
| Notes |
| 2006-04-05 00:00:00 | REVISION CHECKLIST: | | | | | | 1- DRAWING A1 OF 7: IDENTIFY MULLION | | | SIZE ABOVE 12' WIDE SLIDING GLASS DOORS | | | IN FAMILY ROOM. SEC. 104.2.1.2 OF CITY | | | AMENDMENTS TO FBC 2001. | | | REVISED DRAWING A1 ONLY CALLS FOR | | | STRUCTURAL MULLION AND ANCHORS TO BE | | | ATTACHED WITH. | | | (NOTE: ENGINEER'S DETAIL FOR 16' WIDE | | | SLIDING GLASS DOORS IS OK). | | | | | | 2- DADE COUNTY NOA #03-0225.07 FOR | | | ALUMINUM TUBE MULLIONS W/STEEL | | | REINFORCEMENTS PRODUCT APPROVAL | | | SUBMITTED DOESN'T WORK FOR 12'X8' | | | SLIDING GLASS DOORS AND TRANSOM ABOVE IN | | | FAMILY ROOM. MAXIMUMWINDOW WITDH | | | SHOWING IN TABLES IS 75". NEED 90" WIDTH | | | FOR PROPOSED INSTALLATION. | | | | | | 2- THE FOLLOWING WAS REQUESTED ON | | | CHECKLIST DATED 2-06-06 AND WAS NOT | | | PROVIDED: | | | SHEET A3 OF 7: PROVIDE CALCULATIONS TO | | | SHOW WHY ONLY 1 SCREW PER ROOF TILE IS | | | ENOUGH TO RESIST THE UPLIFT. SECTION | | | 1606.3.3 FBC 2001 AND SECTIONS 104.2.1.2 | | | AND 104.2.1.1 CITY AMENDMENTS TO FBC | | | 2001. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
F |
Date |
2006-02-06 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2006-02-06 |
Time |
16:32 |
Rev Time |
1.00 |
| Received By |
jgomez |
Date |
2006-02-06 |
Time |
07:45 |
Sent To |
Z |
|
| Notes |
| 2006-02-06 00:00:00 | BUILDING REVIEW CHECKLIST: | | | 1- A/C AREA WAS CHANGED AGAIN. NEED TO | | | REVISE THE ENERGY CALCULATIONS TO MATCH | | | A/C AREA SHOWN ON REVISED PLANS. | | | | | | 2- ARCHITECT TO SPECIFY MULLION SIZE AND | | | ANCHORS FOR STRUCTURAL MULLION ABOVE | | | SLIDING GLASS DOORS. SPECIFICATIONS | | | SHOWN ON SHEET A1 OF 7 ONLY SPECIFIES | | | THE TAPCONS. IT DOESN'T SPECIFY MULLION | | | SIZE. | | | NOTE: 2"X HEAVY WALL-ALUMINUM MULLION | | | DOESN'T RESIST THE DESIGN PRESSURES FOR | | | SLIDING GLASS DOOR AT LIVING ROOM. SEE | | | PRODUCT APPROVAL. | | | | | | 3- PROVIDE FLORIDA OR LOCAL PRODUCT | | | APPROVAL FOR SPECIFIED STRUCTURAL | | | MULLION BETWEEN SLIDING GLASS DOORS AND | | | TRANSOMS ABOVE. SEE ARCHITECT'S RESPONSE | | | TO ITEM #2 ABOVE. 2"X HEAVY | | | WALL-ALUMINUM MULLION SUBMITTED DOESN'T | | | WORK. | | | | | | 4- SHEET A3 OF 7: PROVIDE CALCULATIONS | | | TO SHOW WHY ONLY 1 SCREW PER ROOF TILE | | | IS ENOUGH TO RESIST THE UPLIFT. SEC. | | | 1606.3.3 FBC 2001 AND SEC. 104.2.1 AND | | | 104.2.1.1 CITY AMENDMENTS TO FBC 2001. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2005-12-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2005-12-07 |
Time |
11:27 |
Rev Time |
1.50 |
| Received By |
jgomez |
Date |
2005-12-07 |
Time |
07:49 |
Sent To |
PC |
|
| Notes |
| 2005-12-07 00:00:00 | BUILDING REVIEW REVISION CHECKLIST: | | | | | | 1- REVISION INCLUDES CHANGE IN THE | | | SQUARE FOOTAGE OF THE HOUSE. THEREFORE | | | OWES $30.42 FOR UPDATED SQUARE FOOTAGE | | | VALUATION. | | | | | | 2- A)PRODUCT APPROVAL FOR ENTRY DOORS | | | REQUESTED ON PROVISO DATED 12-14-04 WAS | | | NEVER SUBMITTED. SUBMIT FLORIDA OR LOCAL | | | PRODUCT APPROVAL AS REQUIRED BY RULE | | | 9B-72 DEPARTMENT OF COMMUNTIY AFFAIRS | | | (DCA) NOW TO AVOID DELAYS OR CONFLICTS. | | | | | | B)PROVIDE FLORIDA OR LOCAL PRODUCT | | | APPROVAL AS REQUIRED BY RULE 9B-72FOR | | | FRENCH DOORS ALSO. THERE IS NOT PRODUCT | | | APPROVAL IN FILE. | | | | | | 3- REVISED PLANS SHOW SLIDING GLASS | | | DOORS. PROVIDE FLORIDA OR LOCAL PRODUCT | | | APPROVAL FOR IMPACT SLIDING GLASS DOORS | | | AT LIVING ROOM AND FAMILY ROOM. SEE | | | PLANS FOR SIZES. | | | | | | 4- ARCHITECT TO SPECIFY SIZE AND ANCHORS | | | TO BE USED FOR STRUCTURAL MULLIONS | | | BETWEEN SLIDING GLASS DOORS AND FIXED | | | WINDOWS IN LIVING AND FAMILY ROOM AREAS. | | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC | | | 2001 AND SEC. 1606 FBC 2001. | | | | | | 5- PROVIDE FLORIDA OR LOCAL PRODUCT | | | APPROVAL FOR STRUCTURAL MULLION | | | SPECIFIED IN ITEM #4 ABOVE. | | | | | | 6- ROOF LOADS CHART IN DRAWING A3 IS | | | MISSING INFORMATION. PROVIDE ALL | | | INFORMATION. REMEMBER TO SPECIFY THE | | | ATTIC LIVE LOAD REQUIRED BY TABLE 1604.1 | | | FBC 2001. | | | | | | 7- CLARIFY IF ENTRY PORCH COLUMNS ARE | | | STEEL COLUMNS OR CONCRETE COLUMNS. SHEET | | | A1 AND A2 SPECIFY STEEL COLUMNS, WHILE | | | SHEET A5, FRONT ELEVATION, SPECIFIES 16" | | | ROUND CONCRETE COLUMN WITH 2#5'S. | | | REVISE/CLARIFY AS REQUIRED. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2005-05-24 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2005-05-24 |
Time |
15:06 |
Rev Time |
0.33 |
| Received By |
jgomez |
Date |
2005-05-24 |
Time |
15:06 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2005-05-13 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2005-05-13 |
Time |
09:40 |
Rev Time |
0.75 |
| Received By |
jgomez |
Date |
2005-05-13 |
Time |
09:40 |
Sent To |
PC |
|
| Notes |
| 2005-05-13 00:00:00 | BUILDING REVIEW CHECKLIST: | | | 1- NEED NOC FOR NEW LOT. | | | | | | 2- NEED PALM BEACH COUNTY IMPACT FEES | | | STAMP ON DRAWINGS FOR TRANSFERING ONE | | | LOT TO THE OTHER. | | | ALSO, BRING BACK PAID RECEIPT FOR | | | TRANSFERED FEES. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ AT (561)805-6712. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2004-12-14 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2004-12-14 |
Time |
15:17 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2004-12-14 |
Time |
15:17 |
Sent To |
PC |
|
| Notes |
| 2004-12-14 00:00:00 | BUILDING REVIEW PROVISO: | | | PROVIDE FOLLOWING INFORMATION PRIOR TO | | | CONSTRUCTION/INSTALLATION TO AVOID | | | DELAYS OR CONFLICTS AT INSPECTIONS: | | | | | | 1-REVISE DETAILS CI AND C2 ON SHEET A6 | | | TO MATCH CONDITIONS SHOWN ON ROOF | | | FRAMING PLAN. TAKE INTO CONSIDERATION: | | | A) TRUSS BEARING ELEVATION. | | | B) 2-2X12 BEAM. | | | | | | **ALSO, SPECIFY HOW ARE 2X12'S INSTALLED | | | ON MASONRY WALL. SEC. 104.2.1.2 CITY | | | AMENDMENTS TO FBC 2001. | | | | | | 2-PROVIDE FLORIDA/LOCAL PRODUCT APPROVAL | | | FOR TYPE OF ENTRY DOORS AS SHOWN ON | | | PLANS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-11-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-05-09 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2004-11-24 |
Time |
17:48 |
Sent To |
B |
|
| Notes |
| 2004-11-24 00:00:00 | CHECKLIST: | | | 1-SHEET A3: A) REVISE ROOF LOAD TABLE | | | TO | | | INCLUDE THE 10PSF OR 30PSF ATTIC LIVE | | | LOAD AS REQ'D BY TABLE 1604.1 FBC 2001. | | | B) REVISE DETAIL SECTIONS TO MATCH | | | CORRECT DETAIL AND PAGE AS SHOWN ON | | | PAGE | | | A-6. | | | C) REVISE ZONE 3 TO INCLUDE ALL | | | CORNERS, | | | SEE FIGURE 1606.2(C) FBC 2001. | | | | | | 2-NEED RECORDED NOTICE OF COMMENCEMENT. | | | | | | 3-OWNER/AGENT TO SIGN AND DATE ENERGY | | | CALCULATIONS AS REQUIRED BY SECTION | | | 103.3 OF CHAPTER 13 FBC 2001. | | | | | | 4-REVISE DETAIL C/7 ON SHEET A6 TO | | | MATCH | | | ACTUAL CONDITIONS AS SHOWN ON ROOF | | | FRAMING PLAN. SPECIFY ALL FASTENERS | | | INCLUDING STUDS FASTENING. SECTION | | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | | | | | 5-NEED FLORIDA/LOCAL PRODUCT APPROVAL | | | FOR: A) FIXED WINDOWS FOR LARGE MISSILE | | | IMPACT, NOT FOR SMALL MISSILE IMPACT. | | | B) ENTRY DOORS WITH MISSILE IMPACT | | | PROTECTION AS SPECIFIED ON PLANS. | | | | | | 6-OWES $1871.56 FOR UPDATE VALUATION AND | | | BALANCE OWED AT TIME OF APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ AT (561)805-6712. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2006-02-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-02-03 |
Time |
21:44 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-02-03 |
Time |
21:14 |
Sent To |
PC |
|
| Notes |
| 2006-02-03 00:00:00 | REV'S SUBMITTED FOR FINALS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2005-11-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-11-09 |
Time |
11:37 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2005-11-09 |
Time |
11:37 |
Sent To |
P |
|
| Notes |
| 2005-11-09 00:00:00 | REDLINED | | | | | | | | | DISH/DISP SHOWS 6KW ON 2-POLE 20A BRKR. | | | | | | BATH GFI SHOWN AS #14, 15A. | | | 210.11C3 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2004-11-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-11-12 |
Time |
08:18 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2004-11-12 |
Time |
08:55 |
Sent To |
M |
|
| Notes |
| 2004-11-12 00:00:00 | REDLINED MISSING EQUIPMENT GRND FROM | | | MAINS TO PANELS. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2006-05-05 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-05-05 |
Time |
14:01 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-05-05 |
Time |
14:00 |
Sent To |
B |
|
| Notes |
| 2006-05-05 00:00:00 | TO "JGOMEZ' DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2006-03-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-03-23 |
Time |
14:21 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-03-23 |
Time |
14:21 |
Sent To |
B |
|
| Notes |
| 2006-03-23 00:00:00 | SENT TO JG'S DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2006-02-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-02-01 |
Time |
18:55 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-02-01 |
Time |
18:55 |
Sent To |
B |
|
| Notes |
| 2006-02-01 00:00:00 | TO "JGOMEZ" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2006-02-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-02-01 |
Time |
18:48 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-02-01 |
Time |
18:48 |
Sent To |
E |
|
| Notes |
| 2006-02-01 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2005-10-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-10-21 |
Time |
13:24 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-10-21 |
Time |
13:24 |
Sent To |
E |
|
| Notes |
| 2005-10-21 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2005-10-04 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-10-04 |
Time |
10:24 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-10-04 |
Time |
10:24 |
Sent To |
Z |
|
| Notes |
| 2005-10-04 00:00:00 | TO "Z" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-05-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-05-09 |
Time |
10:21 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-05-09 |
Time |
10:21 |
Sent To |
B |
|
| Notes |
| 2005-05-09 00:00:00 | TO "JGOMEZ" DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
|
Date |
2005-05-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-04-29 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-04-29 |
Time |
18:01 |
Sent To |
|
|
| Notes |
| 2005-04-29 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-12-10 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2004-12-10 |
Time |
12:51 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2004-12-10 |
Time |
12:51 |
Sent To |
B |
|
| Notes |
| 2004-12-10 00:00:00 | SENT TO "JG" DESK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-11-24 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2004-11-24 |
Time |
17:57 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2004-10-20 |
Time |
16:55 |
Sent To |
PC |
|
| Notes |
| 2004-11-08 00:00:00 | TO SFD RACK/E | | 2004-10-20 00:00:00 | TO Z |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2006-04-06 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-04-06 |
Time |
08:17 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2006-04-06 |
Time |
08:17 |
Sent To |
|
|
| Notes |
| 2006-04-06 00:00:00 | REVISION TO ENERGY CAL'S. . |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2005-12-06 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2005-12-06 |
Time |
14:00 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2005-12-06 |
Time |
14:00 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2004-11-18 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2004-11-18 |
Time |
07:36 |
Rev Time |
0.45 |
| Received By |
drunnels |
Date |
2004-11-18 |
Time |
07:35 |
Sent To |
P |
|
| Notes |
| 2004-11-18 00:00:00 | REV PATRAFTER |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2005-12-06 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-12-06 |
Time |
13:11 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2005-12-06 |
Time |
13:11 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2004-11-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-11-12 |
Time |
08:01 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2004-11-12 |
Time |
07:30 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2006-02-09 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-02-09 |
Time |
19:36 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-02-09 |
Time |
19:36 |
Sent To |
|
|
| Notes |
| 2006-02-09 00:00:00 | APPROVE REVISION. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2005-10-18 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-10-18 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-10-18 |
Time |
15:13 |
Sent To |
I |
|
| Notes |
| 2005-10-18 00:00:00 | REVISION TO CHANGE IN THE DESIGN AND | | | SETBACK OF THE STRUCTURE. | | | | | | NOTE: MUST PULL A SEPERATE PERMIT FOR | | | POOL/SPA/DECK. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2005-05-06 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-05-06 |
Time |
17:38 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-05-06 |
Time |
17:38 |
Sent To |
I |
|
| Notes |
| 2005-05-06 00:00:00 | REVISION APPROVED FOR TRANSFER FROM LOT# | | | 13 TO LOT #12 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2004-11-06 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2004-11-06 |
Time |
11:16 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2004-11-06 |
Time |
11:16 |
Sent To |
I |
|
| Notes |
| 2004-11-06 00:00:00 | NOTE: MUST PULL SEPERATE PERMIT FOR | | | POOL/DECK MM |
|
|