Plan Review Details - Permit 04100804
Plan Review Stops For Permit 04100804
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2006-05-23 Cont ID  
Sent By jgomez Date 2006-05-23 Time 09:29 Rev Time 0.50
Received By jgomez Date 2006-05-23 Time 09:29 Sent To PC
Notes
2006-05-23 00:00:00MULLION DETAIL AND ENGINEER'S LETTER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2006-04-05 Cont ID  
Sent By jgomez Date 2006-04-05 Time 14:46 Rev Time 0.50
Received By jgomez Date 2006-04-05 Time 14:46 Sent To M
Notes
2006-04-05 00:00:00REVISION CHECKLIST:
  
 1- DRAWING A1 OF 7: IDENTIFY MULLION
 SIZE ABOVE 12' WIDE SLIDING GLASS DOORS
 IN FAMILY ROOM. SEC. 104.2.1.2 OF CITY
 AMENDMENTS TO FBC 2001.
 REVISED DRAWING A1 ONLY CALLS FOR
 STRUCTURAL MULLION AND ANCHORS TO BE
 ATTACHED WITH.
 (NOTE: ENGINEER'S DETAIL FOR 16' WIDE
 SLIDING GLASS DOORS IS OK).
  
 2- DADE COUNTY NOA #03-0225.07 FOR
 ALUMINUM TUBE MULLIONS W/STEEL
 REINFORCEMENTS PRODUCT APPROVAL
 SUBMITTED DOESN'T WORK FOR 12'X8'
 SLIDING GLASS DOORS AND TRANSOM ABOVE IN
 FAMILY ROOM. MAXIMUMWINDOW WITDH
 SHOWING IN TABLES IS 75". NEED 90" WIDTH
 FOR PROPOSED INSTALLATION.
  
 2- THE FOLLOWING WAS REQUESTED ON
 CHECKLIST DATED 2-06-06 AND WAS NOT
 PROVIDED:
 SHEET A3 OF 7: PROVIDE CALCULATIONS TO
 SHOW WHY ONLY 1 SCREW PER ROOF TILE IS
 ENOUGH TO RESIST THE UPLIFT. SECTION
 1606.3.3 FBC 2001 AND SECTIONS 104.2.1.2
 AND 104.2.1.1 CITY AMENDMENTS TO FBC
 2001.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2006-02-06 Cont ID  
Sent By jgomez Date 2006-02-06 Time 16:32 Rev Time 1.00
Received By jgomez Date 2006-02-06 Time 07:45 Sent To Z
Notes
2006-02-06 00:00:00BUILDING REVIEW CHECKLIST:
 1- A/C AREA WAS CHANGED AGAIN. NEED TO
 REVISE THE ENERGY CALCULATIONS TO MATCH
 A/C AREA SHOWN ON REVISED PLANS.
  
 2- ARCHITECT TO SPECIFY MULLION SIZE AND
 ANCHORS FOR STRUCTURAL MULLION ABOVE
 SLIDING GLASS DOORS. SPECIFICATIONS
 SHOWN ON SHEET A1 OF 7 ONLY SPECIFIES
 THE TAPCONS. IT DOESN'T SPECIFY MULLION
 SIZE.
 NOTE: 2"X HEAVY WALL-ALUMINUM MULLION
 DOESN'T RESIST THE DESIGN PRESSURES FOR
 SLIDING GLASS DOOR AT LIVING ROOM. SEE
 PRODUCT APPROVAL.
  
 3- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR SPECIFIED STRUCTURAL
 MULLION BETWEEN SLIDING GLASS DOORS AND
 TRANSOMS ABOVE. SEE ARCHITECT'S RESPONSE
 TO ITEM #2 ABOVE. 2"X HEAVY
 WALL-ALUMINUM MULLION SUBMITTED DOESN'T
 WORK.
  
 4- SHEET A3 OF 7: PROVIDE CALCULATIONS
 TO SHOW WHY ONLY 1 SCREW PER ROOF TILE
 IS ENOUGH TO RESIST THE UPLIFT. SEC.
 1606.3.3 FBC 2001 AND SEC. 104.2.1 AND
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2005-12-07 Cont ID  
Sent By jgomez Date 2005-12-07 Time 11:27 Rev Time 1.50
Received By jgomez Date 2005-12-07 Time 07:49 Sent To PC
Notes
2005-12-07 00:00:00BUILDING REVIEW REVISION CHECKLIST:
  
 1- REVISION INCLUDES CHANGE IN THE
 SQUARE FOOTAGE OF THE HOUSE. THEREFORE
 OWES $30.42 FOR UPDATED SQUARE FOOTAGE
 VALUATION.
  
 2- A)PRODUCT APPROVAL FOR ENTRY DOORS
 REQUESTED ON PROVISO DATED 12-14-04 WAS
 NEVER SUBMITTED. SUBMIT FLORIDA OR LOCAL
 PRODUCT APPROVAL AS REQUIRED BY RULE
 9B-72 DEPARTMENT OF COMMUNTIY AFFAIRS
 (DCA) NOW TO AVOID DELAYS OR CONFLICTS.
  
 B)PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL AS REQUIRED BY RULE 9B-72FOR
 FRENCH DOORS ALSO. THERE IS NOT PRODUCT
 APPROVAL IN FILE.
  
 3- REVISED PLANS SHOW SLIDING GLASS
 DOORS. PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR IMPACT SLIDING GLASS DOORS
 AT LIVING ROOM AND FAMILY ROOM. SEE
 PLANS FOR SIZES.
  
 4- ARCHITECT TO SPECIFY SIZE AND ANCHORS
 TO BE USED FOR STRUCTURAL MULLIONS
 BETWEEN SLIDING GLASS DOORS AND FIXED
 WINDOWS IN LIVING AND FAMILY ROOM AREAS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC
 2001 AND SEC. 1606 FBC 2001.
  
 5- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR STRUCTURAL MULLION
 SPECIFIED IN ITEM #4 ABOVE.
  
 6- ROOF LOADS CHART IN DRAWING A3 IS
 MISSING INFORMATION. PROVIDE ALL
 INFORMATION. REMEMBER TO SPECIFY THE
 ATTIC LIVE LOAD REQUIRED BY TABLE 1604.1
 FBC 2001.
  
 7- CLARIFY IF ENTRY PORCH COLUMNS ARE
 STEEL COLUMNS OR CONCRETE COLUMNS. SHEET
 A1 AND A2 SPECIFY STEEL COLUMNS, WHILE
 SHEET A5, FRONT ELEVATION, SPECIFIES 16"
 ROUND CONCRETE COLUMN WITH 2#5'S.
 REVISE/CLARIFY AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-05-24 Cont ID  
Sent By jgomez Date 2005-05-24 Time 15:06 Rev Time 0.33
Received By jgomez Date 2005-05-24 Time 15:06 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-05-13 Cont ID  
Sent By jgomez Date 2005-05-13 Time 09:40 Rev Time 0.75
Received By jgomez Date 2005-05-13 Time 09:40 Sent To PC
Notes
2005-05-13 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED NOC FOR NEW LOT.
  
 2- NEED PALM BEACH COUNTY IMPACT FEES
 STAMP ON DRAWINGS FOR TRANSFERING ONE
 LOT TO THE OTHER.
 ALSO, BRING BACK PAID RECEIPT FOR
 TRANSFERED FEES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-12-14 Cont ID  
Sent By jgomez Date 2004-12-14 Time 15:17 Rev Time 0.00
Received By jgomez Date 2004-12-14 Time 15:17 Sent To PC
Notes
2004-12-14 00:00:00BUILDING REVIEW PROVISO:
 PROVIDE FOLLOWING INFORMATION PRIOR TO
 CONSTRUCTION/INSTALLATION TO AVOID
 DELAYS OR CONFLICTS AT INSPECTIONS:
  
 1-REVISE DETAILS CI AND C2 ON SHEET A6
 TO MATCH CONDITIONS SHOWN ON ROOF
 FRAMING PLAN. TAKE INTO CONSIDERATION:
 A) TRUSS BEARING ELEVATION.
 B) 2-2X12 BEAM.
  
 **ALSO, SPECIFY HOW ARE 2X12'S INSTALLED
 ON MASONRY WALL. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 2-PROVIDE FLORIDA/LOCAL PRODUCT APPROVAL
 FOR TYPE OF ENTRY DOORS AS SHOWN ON
 PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-11-24 Cont ID  
Sent By adarroug Date 2005-05-09 Time 10:18 Rev Time 0.00
Received By jgomez Date 2004-11-24 Time 17:48 Sent To B
Notes
2004-11-24 00:00:00CHECKLIST:
 1-SHEET A3: A) REVISE ROOF LOAD TABLE
 TO
 INCLUDE THE 10PSF OR 30PSF ATTIC LIVE
 LOAD AS REQ'D BY TABLE 1604.1 FBC 2001.
 B) REVISE DETAIL SECTIONS TO MATCH
 CORRECT DETAIL AND PAGE AS SHOWN ON
 PAGE
 A-6.
 C) REVISE ZONE 3 TO INCLUDE ALL
 CORNERS,
 SEE FIGURE 1606.2(C) FBC 2001.
  
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
  
 3-OWNER/AGENT TO SIGN AND DATE ENERGY
 CALCULATIONS AS REQUIRED BY SECTION
 103.3 OF CHAPTER 13 FBC 2001.
  
 4-REVISE DETAIL C/7 ON SHEET A6 TO
 MATCH
 ACTUAL CONDITIONS AS SHOWN ON ROOF
 FRAMING PLAN. SPECIFY ALL FASTENERS
 INCLUDING STUDS FASTENING. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 5-NEED FLORIDA/LOCAL PRODUCT APPROVAL
 FOR: A) FIXED WINDOWS FOR LARGE MISSILE
 IMPACT, NOT FOR SMALL MISSILE IMPACT.
 B) ENTRY DOORS WITH MISSILE IMPACT
 PROTECTION AS SPECIFIED ON PLANS.
  
 6-OWES $1871.56 FOR UPDATE VALUATION AND
 BALANCE OWED AT TIME OF APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-02-03 Cont ID  
Sent By dpalmer Date 2006-02-03 Time 21:44 Rev Time 0.00
Received By dpalmer Date 2006-02-03 Time 21:14 Sent To PC
Notes
2006-02-03 00:00:00REV'S SUBMITTED FOR FINALS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-11-09 Cont ID  
Sent By dpalmer Date 2005-11-09 Time 11:37 Rev Time 0.50
Received By dpalmer Date 2005-11-09 Time 11:37 Sent To P
Notes
2005-11-09 00:00:00REDLINED
  
  
 DISH/DISP SHOWS 6KW ON 2-POLE 20A BRKR.
  
 BATH GFI SHOWN AS #14, 15A.
 210.11C3

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-11-12 Cont ID  
Sent By kstevens Date 2004-11-12 Time 08:18 Rev Time 0.00
Received By dpalmer Date 2004-11-12 Time 08:55 Sent To M
Notes
2004-11-12 00:00:00REDLINED MISSING EQUIPMENT GRND FROM
 MAINS TO PANELS.

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-05-05 Cont ID  
Sent By adarroug Date 2006-05-05 Time 14:01 Rev Time 0.00
Received By adarroug Date 2006-05-05 Time 14:00 Sent To B
Notes
2006-05-05 00:00:00TO "JGOMEZ' DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-03-23 Cont ID  
Sent By dpalmer Date 2006-03-23 Time 14:21 Rev Time 0.00
Received By dpalmer Date 2006-03-23 Time 14:21 Sent To B
Notes
2006-03-23 00:00:00SENT TO JG'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-02-01 Cont ID  
Sent By adarroug Date 2006-02-01 Time 18:55 Rev Time 0.00
Received By adarroug Date 2006-02-01 Time 18:55 Sent To B
Notes
2006-02-01 00:00:00TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-02-01 Cont ID  
Sent By adarroug Date 2006-02-01 Time 18:48 Rev Time 0.00
Received By adarroug Date 2006-02-01 Time 18:48 Sent To E
Notes
2006-02-01 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-10-21 Cont ID  
Sent By adarroug Date 2005-10-21 Time 13:24 Rev Time 0.00
Received By adarroug Date 2005-10-21 Time 13:24 Sent To E
Notes
2005-10-21 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-10-04 Cont ID  
Sent By adarroug Date 2005-10-04 Time 10:24 Rev Time 0.00
Received By adarroug Date 2005-10-04 Time 10:24 Sent To Z
Notes
2005-10-04 00:00:00TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-05-09 Cont ID  
Sent By adarroug Date 2005-05-09 Time 10:21 Rev Time 0.00
Received By adarroug Date 2005-05-09 Time 10:21 Sent To B
Notes
2005-05-09 00:00:00TO "JGOMEZ" DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date 2005-05-09 Cont ID  
Sent By adarroug Date 2005-04-29 Time 10:18 Rev Time 0.00
Received By adarroug Date 2005-04-29 Time 18:01 Sent To  
Notes
2005-04-29 00:00:00TO "Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-12-10 Cont ID  
Sent By mjacobs Date 2004-12-10 Time 12:51 Rev Time 0.00
Received By mjacobs Date 2004-12-10 Time 12:51 Sent To B
Notes
2004-12-10 00:00:00SENT TO "JG" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-11-24 Cont ID  
Sent By jgomez Date 2004-11-24 Time 17:57 Rev Time 0.00
Received By jgomez Date 2004-10-20 Time 16:55 Sent To PC
Notes
2004-11-08 00:00:00TO SFD RACK/E
2004-10-20 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-04-06 Cont ID  
Sent By tgordon Date 2006-04-06 Time 08:17 Rev Time 0.20
Received By tgordon Date 2006-04-06 Time 08:17 Sent To  
Notes
2006-04-06 00:00:00REVISION TO ENERGY CAL'S. .

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-12-06 Cont ID  
Sent By tgordon Date 2005-12-06 Time 14:00 Rev Time 0.30
Received By tgordon Date 2005-12-06 Time 14:00 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-11-18 Cont ID  
Sent By drunnels Date 2004-11-18 Time 07:36 Rev Time 0.45
Received By drunnels Date 2004-11-18 Time 07:35 Sent To P
Notes
2004-11-18 00:00:00REV PATRAFTER

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-12-06 Cont ID  
Sent By jleech Date 2005-12-06 Time 13:11 Rev Time 0.33
Received By jleech Date 2005-12-06 Time 13:11 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-11-12 Cont ID  
Sent By kstevens Date 2004-11-12 Time 08:01 Rev Time 0.33
Received By kstevens Date 2004-11-12 Time 07:30 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2006-02-09 Cont ID  
Sent By mmclean Date 2006-02-09 Time 19:36 Rev Time 0.00
Received By mmclean Date 2006-02-09 Time 19:36 Sent To  
Notes
2006-02-09 00:00:00APPROVE REVISION.

Review Stop Z ZONING
Rev No 3 Status P Date 2005-10-18 Cont ID  
Sent By mmclean Date 2005-10-18 Time 15:13 Rev Time 0.00
Received By mmclean Date 2005-10-18 Time 15:13 Sent To I
Notes
2005-10-18 00:00:00REVISION TO CHANGE IN THE DESIGN AND
 SETBACK OF THE STRUCTURE.
  
 NOTE: MUST PULL A SEPERATE PERMIT FOR
 POOL/SPA/DECK.

Review Stop Z ZONING
Rev No 2 Status P Date 2005-05-06 Cont ID  
Sent By mmclean Date 2005-05-06 Time 17:38 Rev Time 0.00
Received By mmclean Date 2005-05-06 Time 17:38 Sent To I
Notes
2005-05-06 00:00:00REVISION APPROVED FOR TRANSFER FROM LOT#
 13 TO LOT #12

Review Stop Z ZONING
Rev No 1 Status P Date 2004-11-06 Cont ID  
Sent By mmclean Date 2004-11-06 Time 11:16 Rev Time 0.00
Received By mmclean Date 2004-11-06 Time 11:16 Sent To I
Notes
2004-11-06 00:00:00NOTE: MUST PULL SEPERATE PERMIT FOR
 POOL/DECK MM