Plan Review Details - Permit 04100753
Plan Review Stops For Permit 04100753
Review Stop AD ADDRESSING
Rev No 1 Status P Date   Cont ID  
Sent By csiegber Date 2004-10-20 Time 13:55 Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-06-09 Cont ID  
Sent By jgomez Date 2005-06-09 Time 14:26 Rev Time 1.00
Received By jgomez Date 2005-06-09 Time 14:26 Sent To PC
Notes
2005-06-09 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- OWNER AGREED TO APPLY FOR SEPARATE
 PERMIT FOR BUTT GLAZING ASSEMBLY AT NOOK
 AREA.
  
 2- MODEL OF DOORS FOR GARAGE AND BATH #3
 SHOWN ON DADE COUNTY NOA DON'T MATCH
 MODELS SHOWN ON FLORIDA PRODUCT APPROVAL
 REPORT. SUBMIT DRAWINGS THAT MATCH THOSE
 IN THE FLORIDA PRODUCT APPROVAL OR APPLY
 FOR LOCAL PRODUCT APPROVAL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-05-12 Cont ID  
Sent By jgomez Date 2005-05-12 Time 10:33 Rev Time 1.50
Received By jgomez Date 2005-05-12 Time 10:33 Sent To PC
Notes
2005-05-12 00:00:00BUILDING REVIEW CHECKLIST:
 1- DRAWINGS STILL DON'T SHOW PALM BEACH
 COUNTY IMPACT FEES STAMP AND PAID
 RECEIPT STILL SHOWS $3.00 BALANCE.
  
 2- DADE COUNTY NOA ALONE IS NOT
 AUTOMATICALLY A FLORIDA STATE WIDE
 PRODUCT APPROVAL. PROVIDE FLORIDA
 PRODUCT APPROVAL OR APPLY FOR LOCAL
 PRODUCT APPROVAL AS REQUIRED BY RULE
 9B-72 OF THE FLORIDA BUILDING COMMISSION
 FOR:
 A) FRENCH DOOR WITH SIDELITES ASSEMBLY
 AT FAMILY ROOM.
  
 B) SOLID SWING DOOR AT GARAGE AND BATH
 #3 SIDE DOOR.
  
 C) ENTRY & MASTER BEDROOM DOORS.
  
 D) USP TRUSS CONNECTORS SPECIFIED ON
 PLANS.
  
 3- BAY WINDOW AT NOOK AREA WAS CHANGED
 FOR BUTT GLAZING SYSTEM. NEED TO PROVIDE
 FLORIDA PRODUCT APPROVAL OR APPLY FOR
 LOCAL PRODUCT APPROVAL.
 IF APPLYING FOR LOCAL PRODUCT APPROVAL
 ENGINEER TO READ SEC. 2406.2 FBC 2001
 AND PROVIDE ALL REQUIRED INFORMATION.
 ALSO, SEE WWW.FLORIDABUILDING.ORG FOR
 LOCAL PRODUCT APPROVAL REQUIREMENTS AS
 REQUIRED BY RULE 9B-72.
  
 4- NOTICE OF COMMENCEMENT EXPIRES AFTER
 90 DAYS. NEED RE-RECORDED NOTICE OF
 COMMENCEMNT.
  
 5- ENGINEER TO PROVIDE COMPLETE
 SPECIFICATIONS FOR BEAM #12. IS MISSING
 STIRRUPS REINFORCEMENT. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-02-28 Cont ID  
Sent By jgomez Date 2005-02-28 Time 16:13 Rev Time 2.00
Received By jgomez Date 2005-02-28 Time 16:13 Sent To PC
Notes
2005-02-28 00:00:00CHECKLIST:
 1- DRAWINGS NEED PALM BEACH COUNTY
 IMPACT FEES STAMP. ALSO, PAID RECEIPT
 SAYS THERE IS $3.00 BALANCE DUE. CLARIFY
 AND BRING BACK STAMPED DRAWINGS AND PAID
 IN FULL RECEIPT.
  
 2-A) ENTRY PORCH ON SHEET 6/10 CALLS FOR
 CONCRETE BEAMS, WHILE, ROOF FRAMING PLAN
 AND PORCH DETAILS CALL FOR WOOD BEAMS.
 REVISE AS REQUIRED.
  
 B) ENTRY PORCH IN ROOF FRAMING PLAN
 SHOWS 3-2X12 BEAM WHILE PORCH DETAIL ON
 SHEET 8/10 SHOWS 2-2X12 BEAM. REVISE AS
 REQUIRED.
  
 3- SPECIFY HOW IS CANTILEVERED BEAM AT
 NOOK AREA ANCHORED TO THE SIDE COLUMNS.
 SPECIFY REINFORCING. SEC. 104.2.1.2 OF
 CITY AMENDMENTS TO FBC 2001.
  
 4- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR:
 A) ENTRY DOORS WITH DRAWINGS THAT MATCH
 FLORIDA PRODUCT APPROVAL INFORMATION.
 DRAWINGS SUBMITTED ARE FOR "BENCHMARK".
 NEED DRAWINGS FOR "THERMA-TRU" MODELS AS
 SPECIFIED ON FLORIDA PRODUCT APPROVAL
 #1170 SUBMITTED.
  
 B) DOOR WITH SIDELITES AS SHOWN ON PLANS
  
 C) 45 DEGREES FIXED WINDOW COMPLETE
 SYSTEMAS SHOWN ON NOOK AREA.
  
 D) GARAGE SIDE DOOR.
  
 5- STORM SHUTTERS: A) CLEARLY MARK ON
 DRAWINGS SPECIFIC MOUNTING CONDITIONS
 AND ANCHOR TYPE AND SPACING TO BE USED.
 CLEARLY MARK INSTALLATION SCHEDULE
 INSIDE ENGINEERED DRAWINGS TO VERIFY
 ANCHOR TYPE AND SPACING USED.
 **NOTE; SEE PLANS FOR ENGINEER'S
 CALCULATED DESIGN PRESSURES AT OPENINGS.
 VERIFY STRUCTURE TO BE ATTACHED TO: 3000
 PSI CONCRETE OR MASONRY.
 SEC. 104.2.1.2 CITY AMENDMETNS TO FBC.
 B) CLEARLY INDICATE TYPE OF SHUTTERS
 USED. 22 OR 24 GAUGE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-11-29 Cont ID  
Sent By jgomez Date 2004-11-29 Time 17:53 Rev Time 0.00
Received By jgomez Date 2004-11-29 Time 17:53 Sent To PC
Notes
2004-11-29 00:00:00CHECKLIST:
 1-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING BACKSTAMPED DRAWINGS AND PAID
 RECEIPT.
  
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
  
 3-RIGHT ELEVATION DON'T MATCH PLANS.
 THERE IS AN ADDITIONAL WINDOW SHOWN ON
 THE ELEVATION. REVISE AS REQUIRED.
  
 4-SPECIFY CONCRETE SLAB JOINTS OR
 SPECIFY WWM SUPPORTS & SPACING AS REQ'D
 BY SEC. 1909.3 FBC 2001.
  
 5-LINTEL SHEDULE DON'T MATCH SIZES. SEE
 FOUNDATION PLANS AND LINTEL SCHEDULE
 AND
 REVISE AS REQUIRED.
  
 6-SPECIFY BEAM AT NOOK AREA. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 7-TYPICAL WALL SECTION: A) SPECIFY
 FIREBLOCKING AS REQUIRED BY SECTION
 705.3.1.1 FBC 2001.
 B) INDICATE MIN. FOOTING EMBEDMENT AS
 REQUIRED BY SEC. 1804.1.3 FBC 2001.
  
 8-REVISE PORCH DETAIL TO MATCH PORCH
 CONSTRUCTION SHOWN ON PLANS. PORCH
 SHOWN
 IS FOR WOOD FRAMED STRUCTURE.
  
 9-SOIL TEST REPORT. REVISE SQUARE FOOT
 OF PROPOSED STRUCTURE. SEE PLANS.
  
 10-PROVIDE 2X STRUCTURAL BUCK DETAIL
 FOR
 SWING DOORS AS REQUIRED ON THE PRODUCT
 APPROVAL.
  
 11-PROVIDE FLORIDA/LOCAL PRODUCT
 APPROVAL FOR:
 A) ENTRY DOORS WITH DRAWINGS THAT MATCH
 THOSE SUBMITTED FOR FLORIDA BUILDING
 COMMISION REVIEW AND APPROVAL.
 B) DOOR W/ SIDELITES AS SHOWN ON PLANS.
 C) 45 DEGREES FIXED WINDOW SYSTEM.
 D) GARAGE SIDE DOOR.
  
 12-PROVIDE COMPLETE INFORMATION FOR
 STORM SHUTTERS INCLUDING:A) KEY PLAN
 AND
 COMPLETE INSTALLATION SCHEDULE (SEE
 ATTACHED SAMPLE)
 B)INDICATE ON DWGS SPECIFIC MOUNTING
 CONDITIONS AND ANCHOR TYPE AND SPACING
 TO BE USED ACCORDING TO THE DESIGN
 PRESSURES, EDGE DISTANCE, CONNECTION
 TYPE, PANEL SPAN AND STRUCTURE TO BE
 ATTACHED TO (MASONRY OR CONCRETE).
  
 13-SHEET 1/10: UPDATE INFORMATION. SEE
 COMMENTS ON PLANS.
  
 14-SPECIFY SIZE OF WINDOW TO BE
 INSTALLED AT NOOK AREA. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 15-UPDATE TRUSS ANCHOR SCHEDULE. SEE
 LATEST CATALOGUE. OR, PROVIDE COMPLETE
 ENGINEERING FOR TYPE AND NUMBER OF
 FASTENERS THAT DIFFER FROM APPROVED AND
 PUBLISHED ON MANUFATURER'S CATALOGUE.
 SEE COMMENTS ON PLANS.
 **CLARIFY WHY ARE THERE ADDITIONAL
 FASTENERS SHOWN ON RIGHT HAND SIDE
 COLUMN?
  
 16-WHICH ARE THE CONNECTORS A3 AND A4.
 THEY ARE NOT SHOWN ON TRUSS ANCHOR
 SCHEDULE.
  
 17-ROOF FRAMING PLAN AND PORCH DETAIL
 TO
 MATCH. THEY SPECIFY DIFFERENT NUMBER OF
 2X12'S. REVISE AS REQUIRED. SEE
 COMMENTS
 ON PLAN.
  
 18-OWES $203.82 FOR UPDATED VALUATION
 AND RADON FEES.
  
 19-OWNER/AGENT TO SIGN AND DATE ENERGY
 CALCULATIONS AS REQUIRED BY SEC. 103.1.2
 CHAPTER 13 FBC 2001.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-08-06 Cont ID  
Sent By dpalmer Date 2006-08-06 Time 12:37 Rev Time 0.00
Received By dpalmer Date 2006-08-06 Time 12:19 Sent To PC
Notes
2006-08-06 00:00:00** UNSAT **
  
 1) NOTE: PLEASE SEE PLANS SHALL CONTAIN
 THE PRINTED NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR PLANS AND DESIGN.
 PLEASE SEE PLANS SHOUDL STATE: DRAWN BY:
 AND SO ON.
 FBC 106.1.2 2004
 FBC 104.2.1 2001
  
 2) NOTE: PLEASE SEE WHIRLPOOL/JACUZZI
 TUB SHALL INDICATE THE REQUIRED GFI
 PROTECTION PER 680.71 EITHER BY BRKR OR
 DEVICE.
  
 3) NOTE: PLEASE SEE KITCHEN COUNTER
 SPACE AS A RECEPT IS BEING SHOWN W/OUT
 SYMBOL FOR GFI PROTECTION.
 210.8A6
  
 4) NOTE: PLEASE SEE DISHWASHER DISPOSAL
 IS BEING SHOWN WITH TWO SEPARATE
 DEVICE/RECEPTS ON PLANS , YET FED BY A
 2-POLE BRKR.
 210.4
  
 5) NOTE: PLEASE STATE THE 2002
 NFPA-70(NEC) ON PLANS
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-04-25 Cont ID  
Sent By dpalmer Date 2005-04-25 Time 19:57 Rev Time 0.40
Received By dpalmer Date 2005-04-25 Time 19:50 Sent To P
Notes
2005-04-25 00:00:00**REDLINED **
  
 MISSING TWO RECEPTS PER 210.52,
 REDLINED, NO NEED TO REVISE OR CORRECT
 PLANS.
 STAMPED ELECTRICAL PLANS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-02-15 Cont ID  
Sent By dpalmer Date 2005-02-15 Time 06:58 Rev Time 0.33
Received By dpalmer Date 2005-02-15 Time 06:46 Sent To P
Notes
2005-02-15 00:00:00******** UNSAT 2ND REVIEW *********
  
 PLEASE SEE SOME NOTES FROM FIRST REVIEW
 STILL NEED TO BE ADDRESSED.
  
 1)NOTE: NOTE #1, OK, TITLE BLOCK FOR
 JOHN AVERCAMP REMOVED.
  
 2)NOTE: NOTE #2 NO.
 SUBMIT AIC RATING S FOR MAINS/ SERVICE
 PER 110.9/215.5
  
 3)NOTE: NOTE #3 OK.
 NOTED ON PLANS.
  
 4)NOTE: NOTE #4 NO, PLEASE SEE BOTH
 BATHS AND GEN LTS FOR BATHS ARE SHOWN ON
 SAME CIRCUIT.
 PLEASE SEE 210.52D,210.11C3
  
 5)NOTE: NOTE #5, OK.
 MOVED SD'S.
  
 6)NOTE: NOTE #6 NO, PLEASE SEE
 IRRIGATION PUMP STILL SHOWS 30A OCP ON
 #12 AWG.
 PLEASE SEE OTHER ITEMS WERE REVISED.
  
 7)NOTE: NOTE #7 #8 AND #9 OK.
  
 8)NOTE: NOTE#10 NO. NOTE ADDED FOR ARC
 FAULT PROTECTION, HOWEVER PLEASE SEE
 NOTE # 6 ON ELECTRICAL NOTES.
  
 11)NOTE: NOTE #11, YES/NO, PLEASE SEE
 DISC WERE ADDED HOWEVER, MANUFACTURE
 SPECS NOT SUBMITTED.
 PLEASE SUBMIT SPECS SHOWING LISTING FROM
 A NRTL.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS FOR
 REVIEW AND STAMPING.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-11-12 Cont ID  
Sent By dpalmer Date 2004-11-12 Time 09:06 Rev Time 0.50
Received By dpalmer Date 2004-11-12 Time 09:06 Sent To M
Notes
2004-11-12 00:00:00******** UNSAT **************
  
 1)NOTE: PLEASE SEE PLANS CONTAINING
 TITLE BLOCKS, ARE REQUIRED TO BE SIGNED,
 DATED AND SEALED BY PERSON RESPONSIBLE
 FOR PLANS.
 FS 481.221, 471.025
 PLEASE ALSO SEE FAC 61G15-23.002,
 61G1-16.004 FOR MISSING LICENSE #'S AS
 REQUIRED UNDER FS 481.219 AND 471.023
 FOR FIRMS ETC.
 THIS IS REQUIRED ON ALL SHEETS WHEATHER
 OR NOT COMMENT IS MADE BY OTHER
 REVIEWERS.
 FBC 104.2.1
  
  
 2) NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
  
 3)NOTE: PLEASE SHOW ALL RECEPTS
 SERVING KITCHEN COUNTERSPACE AS GFI/GFI
 PROTECTED PER 210.8A-6
  
  
 4) NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 5)NOTE: PLEASE SEE NFPA -72 8-1.4.2 FOR
 LOCATIONS OF SD'S. A MIN OF 3' FROM BATH
 DRS.
  
 6)NOTE: PLEASE CORRELATE LOADS/OCP AND
 AWG ON PANEL SCHEDULE.
 PLEASE SEE INSTA-HOTS UNITS, SHOWS
 2P30A
 WITH 11.8KW LOAD?
 PLEASE ALSO SEE LOADS SHOWN FOR COND
 UNIST AS 10KW, THIS SHOULD BE FOR AHU'S
 HOWEVER THESE ARE NOT LISTED.
 PLEASE ALSO SEE 424.3B FOR OCP ETC.
 310.16, 240.4
  
 7)NOTE: PLEASE SEE 210.52E FOR MISSING
 FRONT AND REAR RECEPTS.
  
 8)NOTE: PLEASE SEE 210.8 FOR ALL RECEPTS
 TO BE GFI/ GFI PROTECTED.
  
 9)NOTE: PLEASE SEE 250.6,250.24, AN
 EQUIPMENT GRND IS NOT INSTALLEDFROM
 METER TO FIRST MEANS OF DISC.
  
 10)NOTE: PLEASE SEE 2002 NEC 210.12,
 PLEASE LIST ARC FAULT PROETCTION ON
 PANEL SCHEDULE.
 NOTES MENTIONS SD' TO BE WIRED INTO
 KITCHEN/BATH LTS? THIS WOULD REQUIRED
 THESE TO ALSO BE ARC FAULT PROTECTED.
  
 11)NOTE: PLEASE SHOW DISCONNECTING MEANS
 FOR INSTA-HOT UNITS. IF OCP, THEN THESE
 MUST MEET 110.26.
 PLEASE ALSO SEE MANUFACTS SPECS FOR
 CLEARENCE REQ',MENTS FOR UNITS.
  
 PLEASE SEE ONE SET OF ELECTRICAL PLANS
 HAVE BEEN REDLINED FOR MOST OF THE ABOVE
 ITEMS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD MAY BE SUBMITTED FOR
 REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
 NOTES MENTIONS SD'S TO BE WIRED TO
  
 7

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-08-02 Cont ID  
Sent By adarroug Date 2006-08-02 Time 10:14 Rev Time 0.00
Received By adarroug Date 2006-08-02 Time 10:13 Sent To E
Notes
2006-08-02 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-06-08 Cont ID  
Sent By mjacobs Date 2005-06-08 Time 14:53 Rev Time 0.00
Received By mjacobs Date 2005-06-08 Time 14:53 Sent To B
Notes
2005-06-08 00:00:00TO 'JG' DESK.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-04-25 Cont ID  
Sent By adarroug Date 2005-04-25 Time 10:11 Rev Time 0.00
Received By adarroug Date 2005-04-25 Time 10:11 Sent To E
Notes
2005-04-25 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-02-09 Cont ID  
Sent By adarroug Date 2005-02-09 Time 14:43 Rev Time 0.00
Received By adarroug Date 2005-02-09 Time 14:43 Sent To E
Notes
2005-02-09 00:00:00TO DPALMER DESK/RESUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-11-29 Cont ID  
Sent By csiegber Date 2004-11-29 Time 17:56 Rev Time 0.00
Received By jgomez Date 2004-10-20 Time 13:55 Sent To PC
Notes
2004-11-08 00:00:00TO SFD RACK/E
2004-10-25 00:00:00TO Z
2004-10-20 00:00:00TO JH BOX/ADDRESSING

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-11-18 Cont ID  
Sent By drunnels Date 2004-11-18 Time 07:42 Rev Time 0.45
Received By drunnels Date 2004-11-18 Time 07:41 Sent To P
Notes
2004-11-18 00:00:00PAT RAFTER

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-05-06 Cont ID  
Sent By jleech Date 2005-05-06 Time 13:25 Rev Time 0.33
Received By jleech Date 2005-05-06 Time 13:25 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-02-23 Cont ID  
Sent By kstevens Date 2005-02-23 Time 11:00 Rev Time 0.33
Received By kstevens Date 2005-02-23 Time 11:00 Sent To B1
Notes
2005-02-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 FROM PREVIOUS REVIEW:
 1) KITCHEN SINK IS NOT VENTED. SECTION
 901.2.1. - IF THIS IS AN AIR ADMITTENCE
 VALVE, THEN SHOW IT AS SUCH ON THE RISER
 DIAGRAM.
 2) WASH MACHINE REQUIRES A STANDPIPE,
 AND THE CLEANOUT SHALL BE INSTALLED 4'
 ABOVE THE FLOOR FOR ACCESS. SECTIONS
 1002.1 AND 708.10
 3) ANY PORTION OF THE DRAINAGE SYSTEM
 INSTALLED UNDERGROUND, SHALL NOT BE LESS
 THAN 2" IN DIAMETER. SECTION 710.3
  
 2) SEE SHEET 3/10 FOR RED LINE
 CORRECTIONS TO BE MADE TO THE SANT.
 RISER DIAGRAM.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-11-12 Cont ID  
Sent By kstevens Date 2004-11-12 Time 08:20 Rev Time 0.50
Received By kstevens Date 2004-11-12 Time 08:20 Sent To E
Notes
2004-11-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT 5 SANITARY RISER DIAGRAM DOES NOT
 MEET THE CODE REQUIREMENTS, NOR DOES IF
 RELEECT THE FLOOR PLAN. SECTION
 104.2.1.
 A) KITCHEN SINK IS NOT VENTED. SECTION
 902.1.
 B) WASH MACHINE IS NOT VENTED, REQUIRES
 A STADPIPE, AND THE CLEANOUT SHALL BE
 INSTALLED 4 FT. ABOVE THE FLOOR FOR
 ACCESS. SECTIONS 902.1, 1002.1, &
 708.10
 C) MASTER BATH SHOWS 2 SHOWERE ON THE
 SANT. RISER DIAGRAM, BUT ONLY ONE ON THE
 FLOOR PLAN. PLEASE CLARIFY. SECTION
 104.2.1.
 D) BATH #2 IS SHOWN AS CONNECTING TO
 THE BLDG DRAIN DOWNSTREAM OF THE
 KITCHEN, WASH MACHINE, AND MASTER BATH
 ON THE RISER DIATRAM, BUT UPSTREAM OF
 THESE FIXTURES ON THE FLOOR PLAN. PLEASE
 SHOW THE RISER AS IT WILL BE INSTALLED.
 SECTION 104.2.1.
  
 2) SEE ATTACHED SHEET SHOWING AN EXAMPLE
 OF A SANITARY RISER DIAGRAM THAT MEETS
 THE CODE REQUIREMENTS AND REFLECT THE
 FLOOR PLAN.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-11-06 Cont ID  
Sent By mmclean Date 2004-11-06 Time 11:23 Rev Time 0.00
Received By mmclean Date 2004-11-06 Time 11:23 Sent To I
Notes
2004-11-06 00:00:00NOTE: DRIVEWAY MUST MEET ZONING
 GUIDELINES OF 1000SQ FT OR 75% WHICHEVER
 IS LESS IN THE FIRST 25FT FRONT SETBACK.