Plan Review Details - Permit 04100740
Plan Review Stops For Permit 04100740
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2005-10-04 Cont ID  
Sent By jwitmer Date 2005-10-04 Time 14:07 Rev Time 0.55
Received By jwitmer Date 2005-10-04 Time 14:07 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2005-09-14 Cont ID  
Sent By jwitmer Date 2005-09-14 Time 10:22 Rev Time 0.33
Received By jwitmer Date 2005-09-14 Time 10:21 Sent To PC
Notes
2005-09-14 00:00:00REVISION SK-3

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2005-07-19 Cont ID  
Sent By jwitmer Date 2005-07-19 Time 08:54 Rev Time 0.55
Received By jwitmer Date 2005-07-19 Time 08:54 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-06-06 Cont ID  
Sent By jwitmer Date 2005-06-06 Time 08:03 Rev Time 1.11
Received By jwitmer Date 2005-06-06 Time 08:03 Sent To PC
Notes
2005-06-06 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04100740
 ADD: 343 MONROE ST
 CONT: NICK RAICH BLDG
 TEL: (561) 718-1224
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVISION: PROVISO
 ACTION: REVIEWED
  
 1) 2111.1.9 WATERSTOP- WHERE EXTERIOR
 WALL MASONARY UNITS BEAR ON A CONCRETE
 FLOOR SURFACE A 1 1/2" RECESS SHALL BE
 PROVIDED TO MINIMIZE WATER INTRUSION
 INTO FINISHED AREAS.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-04-08 Cont ID  
Sent By jwitmer Date 2005-04-08 Time 13:53 Rev Time 2.22
Received By jwitmer Date 2005-04-08 Time 13:53 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-02-25 Cont ID  
Sent By jwitmer Date 2005-02-25 Time 16:00 Rev Time 1.11
Received By jwitmer Date 2005-02-25 Time 10:20 Sent To PC
Notes
2005-02-25 00:00:00BUILDING PROVISO:
 1) PLANS TO BO FOR IMPACT FEE ASSESSMENT
 2) PROVIDE PRODUCT APPROVAL FOR THE
 FRONT ANDREAR DOOR.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-01-20 Cont ID  
Sent By jwitmer Date 2005-01-20 Time 08:02 Rev Time 0.77
Received By jwitmer Date 2005-01-20 Time 08:02 Sent To  
Notes
2005-01-20 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04100740
 ADD: 343 MONROE
 CONT: NICK RAICH BLDG
 TEL: (561)718-1224
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 1)PROVIDE NOC RECORDED WITH THE CLERK OF
 COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS
 B) GLAZED EXTERIOR DOORS
 C)TRUSS ANCHORS
 D)ROOFING ASSEMBLIES
  
 2A) THE STOREFRONT FL PRODUCT APPROVAL
 AND MIAMI-DADE REPORT DOES NOT MATCH
 PROVIDE A DOOR AND WINDOW REPORT WITH
 CORRECT FL PRODUCT APPROVAL.
  
 3)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4) PLANS INDICATE A CHANGE OF OCCUPANCY
 REQUIRES THE FLOORS TO BE RECERTIFIED,
 FOR BUSINESS 50 PSF, AND FOR RETAIL 75
 PSF (LIVE LOADS) SEE TABLE 1604.1.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-11-04 Cont ID  
Sent By jwitmer Date 2004-11-04 Time 08:52 Rev Time 7.77
Received By jwitmer Date 2004-11-08 Time 09:22 Sent To  
Notes
2004-11-04 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04100740
 ADD: 343 MONROE DRIVE
 CONT: NICK RAICH BLDG
 TEL: (561)718-1224
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
 1STREVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1)PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) FIRE DISTRICT F102.1 THERE IS NO
 TYPE
 VI (WOOD) ALLOWED IN THE FIRE DISTRICT.
 PROVIDE ADDITIONAL INFO. WHAT TYPE OF
 MATERIALS ARE THE EXTERIOR WALLS? IF THE
 EXTERIOR WALLS ARE BLOCK OR CLAY TILE
 THE INFILL AROUND THE WINDOWS CAN NOT BE
  
 WOOD FRAMED.
  
 3) SHEET 2 OF 3 HEADER DETAIL INDICATES
 THE USE OF 2X6 HEADERS, SEE FBC TABLE
 2308.3A FOR HEADED SPANS, 24' WIDE
 BUILD
 ING FOR A 8'-0" WINDOW WILL REQUIRE
 (2)- 2X12, SEE FOOTNOTES, 2&4.
  
 4) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS
 B) DOORS
 C) STORM SHUTTERS
 D) TRUSS ANCHORS
 E) ROOFING ASSEMBLIES
  
 5) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6) SHEET 2 DETAILS INDICATE THE GARAGE
 DOOR TO BE INFILLED. ADDITIONAL INFO:
 A) PLYWOOD SUB-SHEATHING:
 2304.5 CLEARENCE BETWEEN WOOD SIDING &
 EARTH ON THE EXTERIOR OF A BUILDING
 SHALL NOT BE LESS THAN 6" EXCEPT WHERE
 SIDING, SHEATHING AND FRAME WALL ARE OF
 APPROVED DURABLE WOOD OR APPROVED PRE-
 SERVATIVE TREATED WOOD.
 B)1403.1.6 IN OEDER TO PROVIDE FOR
 INSPECTION FOR TERMITE INFESTATION,
 CLEARENCE BETWEEN EXTERIOR WALL COVER-
 INGS AND FINAL EARTH GRADE ON THE
 EXTERIOR OF A BUILDING SHALL NOT BE LESS
 THAN 6 INCHES.
  
 7) PLANS DO NOT INDICATE THE MATERIAL OF
 THE EXISTING RETAIL AREA. CHANGE OF
 OCCUPANCY REQUIRES THE FLOOR TO BE
 RECERTIFIED, FOR BUSINESS 50 PSF, AND
 FOR RETAIL 75 PSF (LIVE LOAD).TABLE
 1604.1.
  
 8)TOPLANDING OF HANDICAPPED RAMP TO HAVE
 A 5'-0" LANDING IN THE DIRECTION OF TRAV
 EL.11-4.8.4.(2) LANDINGS. ALL LANDINGS
 ON RAMPS SHALL NOT BE LESS THAN 60"
 CLEAR, & THE BOTTOM OF EACH RAMP SHALL
 HAVE NOT LESS THAN 72" OF STRAIGHT &
 LEVEL CLEARENCE.
  
 9) 11.4.8.5. HANDRAILS: IF A RAMP HAS A
 RISE GREATER THAN 6" OR A HORIZONTAL
 PROJECTION GREATER THAN 72", THEN IT
 SHALL HAVE HANDRAILS ON BOTH SIDES.
  
 10) DOORWAY LEADING TO THE HANDICAPPED
 RESTROOM TO COMPLY WITH :
 11-4.13.5 DOORWAYS, MINIMUM
 CLEAR WIDTH: DOORWAY SHALL HAVE A MINI-
 MUM CLEAR OPENING OF 32" WITH THE DOOR
 OPEN 90 DEGREES, MEASURED BETWEEN THE
 FACE OF THE DOOR AND THE OPPOSITE STOP.
 THE CLEAR FLOOR SPACE BEFORE THE DOOR
 BEING 30" IS THE SAME DIMENSION AS THE
 DOORWAY.
  
 11) CHANGE OF OCCUPANCY IMPACT FEES
 DUE,
 BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-02-15 Cont ID  
Sent By dpalmer Date 2005-02-15 Time 04:29 Rev Time 0.25
Received By dpalmer Date 2005-02-15 Time 04:16 Sent To  
Notes
2005-02-15 00:00:00STAMPED TWO SETS ONLY DUE TO ONLY TWO
 "PERMIT SKECTHES" PROVIDED. ATTAHCED
 ELECTRICAL SKETCHES TO PLANS.
  
  
 REDLINED PLANS FOR AREA IN FRONT OF
 ELECTRICAL PANEL TO BE PAINTED FOR "NO
 STORAGE" . 408.7, 110.26

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-01-14 Cont ID  
Sent By dpalmer Date 2005-01-14 Time 11:49 Rev Time 0.50
Received By dpalmer Date 2005-01-14 Time 11:49 Sent To  
Notes
2005-01-14 00:00:00******** UNSAT *********
  
 1)NOTE: PLEASE CORRELATE CIRCUITING ON
 PLANS WITH PANEL SCHEDULE AND SHOW
 WINDOW RECEPTS.
 PLEASE SEE OUTSIDE LIGHTS SHOWN ON SHOW
 WINDOW CIRCUIT? NO OTHER LOADS ARE
 PERMITTED ON THIS.210.62,220.12
 **NOTE** PLEASE SEE PLANS INDICATE (7)
 SEPARATE CIRCUITS FOR SHOW WINDOWS?
  
 2)NOTE: PLEASE SEE PLANS SHOW PANEL IN
 STORAGE AREA. PLEASE SEE 408.7, AND
 110.26. PLANS NEED TO INDICATE CLEARENCE
 AND AREA TO BE PAINTED ON FLOOR INFRONT
 OF PANEL.
  
 3)NOTE: PLEASE SEE SEC'S SHOWN AS 110
 THWN? IS THIS SUPPOSE TO BE 1/0'S?
 MISPRINT ON PLANS.
  
  
 *** PLEASE SEE THAT THESE MAY BE DONE AS
 A "PROVISO" IF PLANS DO NOT COME BACK
 FOR ANY OTHER COMMENTS.****
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-10-23 Cont ID  
Sent By dpalmer Date 2004-10-23 Time 09:32 Rev Time 0.50
Received By dpalmer Date 2004-10-23 Time 09:12 Sent To  
Notes
2004-10-23 00:00:00*********** UNSAT ************
  
 1)NOTE: PLEASE SEE BLDG APPEARS TO BE A
 CHANGE IN OCCUPANCY?
 HOUSE/RES TO COMM.
  
 2)NOTE: PLEASE VERIFY LIGHTING FOR SPACE
 INSIDE. PLEASE ALSO CLARIFY EGRESS LTS
 LS 101 5-8.
 SWITCHES ARE SHOWN ON PLANS, BUT DO NOT
 APPEAR TO CONTROL ANYTHING??
  
 3)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL SCHEDULE.
 PLEASE SEE 700.12E FOR EM/EXT LTS.
  
 4)NOTE: PLEASE SEE RISER SHOWS GEC GOING
 TO FOOTER STEEL. THIS IS NOT REQUIRED
 ON AN EXISTING BLDG, HOWEVER IT IS
 PERMITTED. IF SHOWN ON PLANS THEN IT
 WILL BE REQUIRED. THIS IS ONLY A NOTE:
  
 5)NOTE: PLEASE SHOW REQUIRED DISC PER
 440.11
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY HAVE AN AFFECT
 ON ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-01-27 Cont ID  
Sent By mcarsill Date 2005-01-27 Time 14:20 Rev Time 0.00
Received By mcarsill Date 2005-01-27 Time 14:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-10-20 Cont ID  
Sent By mcarsill Date 2004-10-20 Time 16:34 Rev Time 0.00
Received By mcarsill Date 2004-10-20 Time 16:33 Sent To  
Notes
2004-10-20 00:00:001) PLEASE SHOW LOCATIONS USING THE
 APPROPRIATE LEGEND SYMBOL.
  
 2) THE ADDRESS NUMBER MUST BE
 INSTALLED ON THE BUILDING EXTERIOR
 NEAR THE FRONT ENTRANCE DOOR. THE
 NUMBER MUST BE AT LEAST 6" HIGH
 AND CONTRAST TO THE BACKGROUND.
  
 3) PLEASE INDICATE LOCATIONS AND
 TYPE OF FIRE EXTINGUISHERS.
  
 4) PLEASE SHOW LOCATIONS OF DUCT
 SMOKE DETECTORS IF THE AC AIR FLOW
 IS 2000 CFM'S OR GREATER.
  
 MIKE WENNERGREN, LIEUTENANT
 835-2950

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-09-27 Cont ID  
Sent By adarroug Date 2005-09-27 Time 16:06 Rev Time 0.00
Received By adarroug Date 2005-09-27 Time 16:06 Sent To B
Notes
2005-09-27 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-09-19 Cont ID  
Sent By adarroug Date 2005-09-19 Time 14:06 Rev Time 0.00
Received By adarroug Date 2005-09-19 Time 14:06 Sent To M
Notes
2005-09-19 00:00:00TO "PKRAUSS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-09-13 Cont ID  
Sent By adarroug Date 2005-09-13 Time 09:20 Rev Time 0.00
Received By adarroug Date 2005-09-13 Time 09:20 Sent To B
Notes
2005-09-13 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-07-18 Cont ID  
Sent By adarroug Date 2005-07-18 Time 14:49 Rev Time 0.00
Received By adarroug Date 2005-07-18 Time 14:49 Sent To B
Notes
2005-07-18 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-05-24 Cont ID  
Sent By adarroug Date 2005-05-24 Time 16:32 Rev Time 0.00
Received By adarroug Date 2005-05-24 Time 16:32 Sent To B
Notes
2005-05-24 00:00:00TO "JWITMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-04-08 Cont ID  
Sent By adarroug Date 2005-04-08 Time 09:15 Rev Time 0.00
Received By adarroug Date 2005-04-08 Time 09:15 Sent To B
Notes
2005-04-08 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-10 Cont ID  
Sent By adarroug Date 2005-02-10 Time 15:11 Rev Time 0.00
Received By adarroug Date   Time   Sent To  
Notes
2005-02-10 00:00:00TO "COMM" BD #10

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-07 Cont ID  
Sent By mjacobs Date 2005-01-07 Time 14:19 Rev Time 0.00
Received By mjacobs Date 2005-01-07 Time 14:19 Sent To  
Notes
2005-01-07 00:00:00TO "COMM BD#46"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-11-16 Cont ID  
Sent By pkrauss Date 2004-11-16 Time 12:05 Rev Time 0.05
Received By pkrauss Date 2004-10-19 Time 15:44 Sent To  
Notes
2004-10-19 00:00:00TO COMM BD#9

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-01-21 Cont ID  
Sent By pkrauss Date 2005-01-21 Time 12:18 Rev Time 0.40
Received By pkrauss Date 2005-01-21 Time 09:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-11-16 Cont ID  
Sent By pkrauss Date 2004-11-16 Time 11:49 Rev Time 0.45
Received By pkrauss Date 2004-11-16 Time 11:42 Sent To  
Notes
2004-11-16 00:00:00DENIED:
 1.PROVIDE EQUIPMENT SCHEDULE ON
 PLANS.
  
 2.PLEASE INDICATE WHAT WILL STORED IN
 THE STORAGE ROOM, (I.E. COMBUSTIBLES?).
  
 3.PLAN SHEET 3 OF 3 INDICATES 10" X 8"
 UP INTO A 36" X 12" CHASE.PLEASE
 CLARIFY, WILL THIS BE INTO THE ATTIC
 AREA?
  
 4.PLEASE NOTE, THE CONDENSATE SHALL
 TERMINATE A MINIMUM OF 12" AWAY FROM THE
 BUILDING STRUCTURE PER 2001 FBC
 1503.4.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS @ (561)805-6719.
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-01-28 Cont ID  
Sent By kstevens Date 2005-01-28 Time 13:13 Rev Time 0.52
Received By kstevens Date 2005-01-28 Time 13:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-11-08 Cont ID  
Sent By kstevens Date 2004-11-08 Time 09:24 Rev Time 0.64
Received By kstevens Date 2004-11-08 Time 09:24 Sent To  
Notes
2004-11-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) PER TABLE 403.1 A DRINKING FOUNTAIN
 IS REQUIRED. ALSO SEE SECTION 410.1
 IF A DRINKING FOUNTAIN IS INSTALLED,
 SUBMIT A DETAIL SHOWING COMPLIANCE WITH
 SECTION 11-4.15 AND ALL SUBSECTIONS
 INCLUDING 11-4.1.3(10)(A)
 2) TOILET ROOM IS NOT WIDE ENOUGH.
 MINIMUM SIZE OF A TOILET ROOM SHALL BE
 5'3". W/C SHALL BE 18" TO CENTER OF
 FIXTURE TO WALL. 30" REQUIRED FROM
 CENTER OF W/C TO C/L OF LAV. LAV TO BE
 MIN. 15" FROM CENTER OF FIXTURE TO WALL.
  
 SECTION 405.3.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2005-01-18 Cont ID  
Sent By mmclean Date 2005-01-18 Time 12:06 Rev Time 0.00
Received By mmclean Date 2005-01-18 Time 12:06 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2004-10-28 Cont ID  
Sent By mmclean Date 2004-10-28 Time 16:32 Rev Time 0.00
Received By mmclean Date 2004-10-28 Time 16:32 Sent To  
Notes
2004-10-28 00:00:00DENIED, NEED TO PROVIDE A SITE PLAN TO
 SCALE WITH THE SETBACK (REAR/FRONT/SIDE)
 CALLED & LEFT MSG ON JOHN'S VOICE MAIL