Plan Review Details - Permit 04100738
Plan Review Stops For Permit 04100738
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-12-17 Cont ID  
Sent By mjacobs Date 2004-12-17 Time 08:03 Rev Time 0.00
Received By mjacobs Date 2004-12-17 Time 08:03 Sent To M
Notes
2004-12-17 00:00:00SENT TO "M/AC" BOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-10-19 Cont ID  
Sent By csiegber Date 2004-10-19 Time 15:43 Rev Time 0.00
Received By csiegber Date 2004-10-19 Time 15:43 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status   Date 2005-01-28 Cont ID  
Sent By pkrauss Date 2005-01-28 Time 14:53 Rev Time 0.00
Received By pkrauss Date 2005-01-28 Time 14:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-12-23 Cont ID  
Sent By pkrauss Date 2004-12-23 Time 10:39 Rev Time 0.40
Received By pkrauss Date 2004-12-23 Time 10:36 Sent To  
Notes
2004-12-23 00:00:00PROVISO:
 EXHAUST AND OA DUCT SHALL BE OF METAL
 AND COMPLY WITH CHAPTER 6 & 1105.8.2.
  
 EXHAUST AIR SHALL TERMINATE AS NOT TO BE
 DRAWN IN BY THE FRESH AIR INTAKE.2001
 FBC(M)501.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-10-26 Cont ID  
Sent By pkrauss Date 2004-10-25 Time 16:58 Rev Time 0.40
Received By pkrauss Date 2004-10-25 Time 16:57 Sent To  
Notes
2004-10-26 00:00:00DENIED:
 INSUFFICIENT INFORMATION FOR REVIEW,
 PLEASE PROVIDE THE FOLLOWING:
 1.ENERGY CALCUALTIONS PER 2001
 FBC CHAPTER 13 SUB-CHAPTER 4.
  
 2.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS PER 2001 FBC(M) 403.3.
  
 3.PLAN INDICATES AREAS SECTIONED OFF,
 ARE THESE INDIVIDUAL OFFICES?RETURN
 AIR REQUIRED FROM THESE AREAS SHOULD
 THEY BE ISOLATED FROM THE RETURN AIR.
  
 4.MECHANICAL ROOM IS INDICATED ON
 THE PLAN WITH A "FREE RETURN" THROUGH
 A LOUVERED DOOR.THIS AREA CANNOT BE
 USED FOR STORAGE AND SHALL COMPLY WITH
 2001 FBC CHAPTER 13 SUB-SECTION
 410.1.ABCD.3.7 (MECHANICAL CLOSETS).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.