Plan Review Details - Permit 04100733
Plan Review Stops For Permit 04100733
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-11-21 Cont ID  
Sent By shill Date 2004-11-21 Time 16:56 Rev Time 3.00
Received By shill Date 2004-11-21 Time 16:56 Sent To  
Notes
2004-11-21 00:00:00****CORRECTIONS****
 FIRST REVIEW
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)PROVIDE A COPY OF THE RECORDED
 UNITY OF TITLE, OR PROVIDE THE
 BOOK/PAGE.
  
 2.)TWO DIFFERENT ADDRESSES WERE
 PROVIDED FOR THIS COMBINED PARCEL.
 PLEASE PROVIDE THE ADDRESS OF THE
 EXISTING RESTAURANT.THE PROPERTY
 APPRAISER USUALLY ASSIGNS THE LOWEST
 PARCEL ID AND ADDRESS WHEN TWO LOTS ARE
 COMBINED.PLEASE ADVISE AS TO WHETHER
 THIS IS ACCEPTABLE.
  
 3.)THE PARCEL BOUNDARY LINES ARE NOT
 CLEAR ON THE SURVEY.PLEASE PROVIDE
 LOT
 BOUNDARIES AND DIMENSIONS TO PROPOSED
 IMPROVEMENTS.
  
 4.)DECLARE A BUILDING TYPE AND
 INDICATE WHETHER OR NOT THE EXISTING
 BUILDING IS SPRINKLED TO SHOW FBC TABLE
 500 COMPLIANCE.
  
 5.)IMPACT FEES MAY BE DUE (PALM BEACH
 COUNTY).THE PLANS MUST BE STAMPED AND
 THE RECEIPT ATTACHED TO THE
 APPLICATION.
 233-5025.
  
 6.)THIS PARCEL IS IN A FLOOD ZONE,
 SEE
 SURVEY (A8).PROVIDE MINIMUM FLOOR
 ELEVATION, CITY OF WEST PALM BEACH
 MUNICIPAL CODE SEC.94-546(B)(2) (MIN.
 6"
 ABOVE BFE).
  
 7.)PROVIDE A SOILS INVESTIGATION
 REPORT, FBC1804.2.2.
  
 8.)PROVIDE ALL STRUCTURAL INFORMATION
 FOR THE AWNING.THIS CANNOT BE
 SUBMITTED AS SHOP DRAWINGS, REQUIRES
 PLAN REVIEW FOR CODE COMPLIANCE.
 PROVIDE DETAILS AND DESIGN LOAD
 INFORMATION, INCLUDING WIND DESIGN LOAD
 INFORMATION REQUIRED BY FBC1606.1.7.
 THERE IS A NOTE STATING THAT THE AWNING
 IS FLAME RETARDANT BUT NO OTHER
 INFORMATION IN REGARDS TO MATERIALS IS
 GIVEN FOR THE AWNING STRUCTURE.SHOW
 HOW IT WILL BE SUPPORTED STRUCTURALLY ON
 THE BUILDING SIDE, PROVIDE DETAIL OF
 ATTACHMENT.
  
 9.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 10.) SEPARATE PERMITS FOR TRADES
 REQUIRED.
  
 11.)STATE OR LOCAL PRODUCT APPROVALS
 AND TEST REPORTS REQUIRED FOR THE
 WINDOW, DOOR, SHUTTERS, STRUCTURAL
 CONNECTORS, SEE FAC9B-72,
 WWW.FLORIDABUILDING.ORG.
  
 12.) ADDITIONAL FEES DUE (RADON),
 $9.00.
  
 13.)WHERE WILL THE HURRICANE SHUTTERS
 SHOWN ON THE PLAN BE STORED?
  
 14.)PROVIDE DIMENSIONS ON THE PLAN FOR
 THE AWNING.EDGE OF AWNING IS SHOWN,
 BUT NOT CONSISTENT WITH ELEVATIONS.
  
 15.)SHOW GRADE ON THE WALL SECTION
 A2.1.BOTTOM OF FOOTER IS TO BE NO LESS
 THAN 12" BELOW GRADE, FBC1804.1.3.
  
 16.)PROVIDE EMBEDMENT LENGTH OF STEEL
 INTO EXISTING, A2.1.
  
 17.)PROVIDE COUNTER HEIGHT; SHOW
 COMPLIANCE WITH FBC11-5.2.
  
 18.)IS THE SEATING FIXED?FBC11-5.1.
  
 19.)PROVIDE A FOUNDATION PLAN,
 FBC104.3.1.1(8).
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-11-24 Cont ID  
Sent By dpalmer Date 2004-11-24 Time 05:40 Rev Time 0.25
Received By dpalmer Date 2004-11-24 Time 05:40 Sent To  
Notes
2004-11-24 00:00:00PASSED ELECTRICAL PENDING REVIEW
 COMMENTS FROM BLDG/FIRE ETC.
 STAMPED ELECTRICAL PLANS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-10-25 Cont ID  
Sent By dpalmer Date 2004-10-25 Time 09:30 Rev Time 0.50
Received By dpalmer Date 2004-10-25 Time 09:30 Sent To  
Notes
2004-10-25 00:00:00****** UNSAT ******
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS. PLEASE SEE EM/EXT LTS. 700.12E
  
 2)NOTE: PLEASE CLARIFY LIGHTING IN THE
 NEW BAR AREA. COULD NOT LOCATE ANY NEW
 LIGHTING?
 DO FANS CONTAIN LTS?LS101 5-8
  
 3)NOTE: PLEASE SEE RISER DIAGRAM SHOWS
 A 3P-60A BRKR TO FEED NEW PANEL, YET
 PLANS SHOWS/NOTES A 2P-60A?
 PANEL SCHEDULE INDICATES A 3-PHASE PANEL
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWERS WHICH MAY HAVE AN AFFECT
 ON ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2004-12-20 Cont ID  
Sent By nmccray Date 2004-12-20 Time 10:49 Rev Time 0.00
Received By nmccray Date 2004-12-20 Time 10:49 Sent To  
Notes
2004-12-20 00:00:00FIRE REVIEW
  
 1) THIS OUTSIDE PATIO IS AN EXTENSION
 OF THE FIRE SPRINKLER STRUCTURE. SO
 THIS PATIO IS REQUIRED TO BE FIRE
 SPRINKLER PROTECTED.
  
 2) SEPARATE PLANS AND PERMIT
 APPLICATION ARE REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM SYSTEMS
 REMODEL.
  
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-11-12 Cont ID  
Sent By mcarsill Date 2004-11-12 Time 09:35 Rev Time 0.00
Received By mcarsill Date 2004-11-12 Time 09:35 Sent To  
Notes
2004-11-12 00:00:001) PLEASE INDICATE LOCATIONS OF
 EMERGENCY LIGHTING IN OUTSIDE AREA.
  
 2) DOES THE EXITING GATE HAVE A
 CRASH BAR LIKE THE OTHER ONE SHOWN
 ON THE PLANS.
  
 3) ARE NEW AWNINGS PROPOSED FLAME
 RETARDANT.
  
 4) IS THE PROPOSED WORK AREA
 FIRE SPRINKLER PROTECTED.
  
 5) HOW WIDE ARE THE GATES.
  
 6) WHAT IS THE PROPOSED HEIGHT
 OF THE PANCI BAR ON THE GATE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date   Cont ID  
Sent By mjacobs Date 2004-11-19 Time 16:50 Rev Time  
Received By mjacobs Date 2004-11-19 Time 16:50 Sent To  
Notes
2004-11-19 00:00:00SENT TO COMM BD#47

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-11-19 Cont ID  
Sent By csiegber Date 2004-11-19 Time 14:28 Rev Time 0.00
Received By csiegber Date 2004-11-19 Time 14:28 Sent To B
Notes
2004-11-19 00:00:00TO LM DESK/RESUB/NO BLDG REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By csiegber Date 2004-10-19 Time 16:22 Sent To  
Notes
2004-10-19 00:00:00TO COMM BD#25

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-12-16 Cont ID  
Sent By pkrauss Date 2004-12-16 Time 16:40 Rev Time 0.15
Received By pkrauss Date 2004-12-16 Time 16:36 Sent To  
Notes
2004-12-16 00:00:00NO MECHANICAL WORK OR CONTRACTOR
 INDICATED WITH PERMIT APPLICATION.
 PERMIT INDICATES OUTSIDE BAR & AND
 SEATING FOR EXISTING RESTAURANT.

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-12-13 Cont ID  
Sent By kstevens Date 2004-12-13 Time 13:07 Rev Time 0.50
Received By kstevens Date 2004-12-13 Time 13:06 Sent To  
Notes
2004-12-13 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
  
 1) FROM PREVIOUS REVIEW: INDICATE IF
 SEATING IS FIXED OR NOT FIXED. TABLES
 1003.1 AND 403.1. THIS SHALL DETERMINE
 THE TOTAL FACILITIES REQUIRED.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-11-08 Cont ID  
Sent By kstevens Date 2004-11-08 Time 14:21 Rev Time 0.59
Received By kstevens Date 2004-11-08 Time 14:21 Sent To  
Notes
2004-11-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT A4.0 SANITARY RISER DIAGRAM, 2"
 HUB DRAIN SHALL NOT CONNECT AS A "SAFE
 WASTE" AND SHALL HAVE ITS OWN TRAP. HUB
 DRAIN SHALL CONNTEC TO THE VENTED LINE
 A
 MAXIMUM OF 6 FEET FROM VENTED LINE.
 SECTION 912.2 AND TABLE 906.1.
 2) SUBMIT CALCULATIONS FOR MINIMUM
 FIXTURE FACILITIES. SHOW EXISTING
 TOILET
 ROOMS AND INDICATE NUMBER OF EXISTING
 W/C'S, URINALS, LAV'S ECT. - INDICATE
 EXISTING SEATING, AND SQUARE FOOTAGE OF
 BUILDING. SHOW NEW TOTALS FOR SQUARE
 FOOTAGE AND SEATING. INDICATE IF
 SEATING
 IS FIXED OR NOT FIXED. TABLES 1003.1
 AND
 403.1.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2004-12-16 Cont ID  
Sent By jroach Date 2004-12-16 Time 09:31 Rev Time 0.00
Received By jroach Date 2004-12-16 Time 09:31 Sent To  
Notes
2004-12-16 00:00:0012/16/04 - ***PASSED***
  
 APPROVED BY MINOR PD AMENDMENT AND
 FORMAL SITE PLAN REVIEW (PB CASE NOS.
 834D&E). JOHN ROACH, PLANNER.

Review Stop Z ZONING
Rev No 1 Status F Date 2004-10-25 Cont ID  
Sent By mmclean Date 2004-10-25 Time 14:00 Rev Time 0.00
Received By mmclean Date 2004-10-25 Time 14:00 Sent To  
Notes
2004-10-25 00:00:00DENIED, NEED TO APPLY FOR A MINOR
 AMENDMENT.JOHN ROACH, PLANNER 822-
 1448 CALLED CONTR LEFT MSG MM