Plan Review Details - Permit 04100693
Plan Review Stops For Permit 04100693
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-12-14 Cont ID  
Sent By rmcdouga Date 2004-12-14 Time 11:16 Rev Time 0.00
Received By rmcdouga Date 2004-12-14 Time 09:38 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-12-14 Cont ID  
Sent By rmcdouga Date 2004-11-16 Time 15:16 Rev Time 0.00
Received By rmcdouga Date 2004-11-16 Time 15:16 Sent To  
Notes
2004-11-16 00:00:00DENIED
  
  
 1)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
 PLANS MUST BE STAMPED BY COUNNTY EVEN IF
 NO FEES ARE DUE.
  
 2) SUBMIT A SIGNED AND SEALED SURVEY
 SHOWING THE LOCATION OF THE STRUCTURE ON
 THE LOT.
  
 3) IF PLANS ARE DRAWN BY AN ARCHITECT,
 THEY MUST BE SIGNED AND SEALED BY HIM
 AND HAVE A TITLE BLOCK WITH ALL
 INFORMATION REQUIRED BY FAC 61G-16.004.
  
 4) FIRE BLOCKING IS REQUIRED AT THE
 CONCEALED SPACES BETWEEN STRINGERS PER
 FBC 2305.1.4. SPECIFY THIS ON PLAN.
  
 5) THE NOTE ON A4 REQUIRES ARCHITECTS
 APPROVAL FOR STUCCO FINISH. REVISE NOTE
 IF THEIR IS NO ARCHITECT ON THIS JOB.
  
 6) FBC 11-4.23.2 REQUIRES THE DOOR TO
 THE HALF BATH ON THE FIRST FLOOR TO HAVE
 A 29" CLEAR OPENING.
  
 7) SPECIFY THE DIMENSIONS TO THE WALL
 WITH THE ENTRY DOOR ON SHEET A1.
  
 8) PLEASE CLARIFY ON THE ROOF NOTE ON
 SHEETS A3,A4,A5 AND A6 WHAT THE @
 24"O.C.IS REFERING TO.
  
 9) SPECIFY THE MEAN ROOF HEIGHT ON THE
 PLANS.
  
 10) SPECIFY THE DIMENSIONS ON THE
 FOUNDATION PLAN ON S1.
  
 11) THE DETAIL FOR THE STEEL COLUMN SC2
 THAT IS SPECIFIED IN THE COLUMN SCHEDULE
 AS BEING ON SHEET S1 IS NOT GIVEN.
  
 12) ON SHEETS S1 AND S2 THE C1 8X16
 CONCRETE COLUMN IS SHOWN AS A DOUBLE
 FILLED CELL MASONRY COLUMN. PLEASE
 CORRECT.
  
 13) THE COMPONENT AND CLADDING PRESSURES
 GIVEN ON S2 CONFLICT WITH THOSE LISTED
 ON S6.
  
 14) TB-1 IS SPECIFIED ON THE SECOND
 FLOOR FRAMING PLAN ON S2 BUT IS NOT
 LISTED IN THE CONCRETE BEAM SCHEDULE.
  
 15) ON S2 THE STEEL COLUMN CAP 'A'
 REFERS TO DETAIL 3 ON S2, WHICH IS NOT
 GIVEN.
  
 16) PLEASE CLARIFY THE NOTE IN THE WOOD
 BEAM SCHEDULE ON S2 THAT REFERS TO A 2X
 6 SECOND FLOOR WALL.
  
 17) CORRECT THE TYPOS IN THE JAMB
 DETAILS ON S2. SEE NOTATIONS ON THE
 PLAN.
  
 18) THE LATERAL (F2) VALUE FOR THE USP
 HTA16-18 IS INCORRECT. IT IS 325.
  
 19) THE MAXIMUM NEGATIVE PRESSURE FOR
 ZONE 4 ON S2 IS SPECIFIED WITH A
 POSITIVE SIGN. PLEASE CORRECT.
  
 20) THE TRUSS ANCHOR ID MARKS ON THE
 LOWER ROOF DO NOT INDICATE WHICH TRUSSES
 THEY ARE TO BE USED ON.
  
 21) CITY OF WPB AMENDMENTS TO FBC TABLE
 2306.1 REQUIRES 8D RING SHANK NAILS IN
 ZONE 3 FOR A MEAN ROOF HEIGHT OF 25'.
  
 22) THE OVERHEAD GARAGE DOOR FL PRODUCT
 APPROVAL HAS THE WRONG INSTALLATION
 DRAWING ATTACHED. SEE DRAWING #S LISTED
 ON THE FL COVER SHEET AND THE WEBSITE
 FOR THE CORRECT INFO.
  
 23) THE FRENCH DOOR PRODUCT APPROVAL HAS
 A JELD-WEN FL 498 COVER SHEET ON A PGT
 NOA. PLEASE CORRECT.
  
 24) THE INSTALLATION DRAWINGS FOR THE
 OXO AND XO CONFIGURATIONS OF THE PGT
 SGD-70 (SLIDING GLASS DOOR)ARE REQUIRED
 IN ADDITION TO THE OXXO THAT WAS
 SUBMITTED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL :
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-10-10 Cont ID  
Sent By btrobaug Date 2006-10-10 Time 17:09 Rev Time 0.50
Received By btrobaug Date 2006-10-10 Time 16:37 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-11-01 Cont ID  
Sent By btrobaug Date 2004-11-01 Time 16:14 Rev Time 0.00
Received By btrobaug Date 2004-11-01 Time 07:55 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-10-10 Cont ID  
Sent By adarroug Date 2006-10-10 Time 09:20 Rev Time 0.00
Received By adarroug Date 2006-10-10 Time 09:19 Sent To E
Notes
2006-10-10 09:20:07TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-10-04 Cont ID  
Sent By adarroug Date 2006-10-04 Time 13:47 Rev Time 0.00
Received By adarroug Date 2006-10-04 Time 13:47 Sent To M
Notes
2006-10-04 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-12-03 Cont ID  
Sent By mjacobs Date 2004-12-03 Time 15:37 Rev Time 0.00
Received By mjacobs Date 2004-12-03 Time 15:37 Sent To P
Notes
2004-12-03 00:00:00SENT TO "P" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-11-16 Cont ID  
Sent By mmclean Date 2004-10-29 Time 12:50 Rev Time 0.00
Received By rmcdouga Date 2004-10-18 Time 16:26 Sent To  
Notes
2004-10-29 00:00:00TO SFD RACK/E
2004-10-18 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-11-04 Cont ID  
Sent By pkrauss Date 2004-11-04 Time 17:38 Rev Time 0.35
Received By pkrauss Date 2004-11-04 Time 17:22 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-12-14 Cont ID  
Sent By rmcdouga Date 2004-12-14 Time 09:37 Rev Time 0.00
Received By rmcdouga Date 2004-12-11 Time 10:47 Sent To  
Notes
2004-12-14 00:00:00OK PER J LEECH 12/11/04

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-11-05 Cont ID  
Sent By kstevens Date 2004-11-05 Time 07:15 Rev Time 0.50
Received By kstevens Date 2004-11-05 Time 07:14 Sent To B1
Notes
2004-11-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 A) SHT P1 SANITARY PLUMBING RISER
 1) FITTINGS SHALL BE INSTALLED TO GUIDE
 SEWAGE AND WASTE IN THE DIRECTION OF
 FLOW. SEE THE AREA AT THE POWDER ROOM
 AND THE AREA DOWNSTREAM OF THE KITCHEN.
 SECTION 706.3
 2) THE BIDET AND THE WATER CLOSET ARE
 NOT LOCATED ON THE RISER AS THEY ARE ON
 THE FLOOR PLAN. SECTION 104.2.1
 3) THE BIDET REQUIRES A TRAP. SECTION
 1002.1
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2005-01-06 Cont ID  
Sent By mmclean Date 2005-01-06 Time 09:14 Rev Time 0.00
Received By mmclean Date 2005-01-06 Time 09:14 Sent To B
Notes
2005-01-06 00:00:00DRIVEWAY REDUCE TO 15FT IN THE FIRST
 25FT FRONT SETBACK.RETURNED PLANS TO
 LUIS M TO ISSUE PERMIT.ZEEK P/U PERMIT

Review Stop Z ZONING
Rev No 3 Status F Date 2005-01-05 Cont ID  
Sent By mmclean Date 2005-01-05 Time 16:23 Rev Time 0.00
Received By mmclean Date 2005-01-05 Time 16:23 Sent To B
Notes
2005-01-05 00:00:00DENIED, NEED TO REDUCE THE DRIVEWAY TO
 15FT IN ORDER TO MEET THE ZONING
 GUILDELINES FOR LANDSCAPE/PARKING.
 CALLED LEFT MSG ON MICHELLE'S VOICE
 MAIL.RETURNED PLANS TO LUIS MARTINEZ.
  
 PHONE NUMBER PROVIDED 315-3677 BELONGS
 TO SOMEONE ELSE, CALLED OTHER NUMBER
 PROVIDED ON RESUB 248-8886 LEFT MSG ON
 VOICE MAIL.

Review Stop Z ZONING
Rev No 2 Status F Date 2004-12-15 Cont ID  
Sent By mmclean Date 2004-12-14 Time 12:55 Rev Time 0.00
Received By mmclean Date 2004-12-14 Time 12:55 Sent To  
Notes
2004-12-15 00:00:00DENIED, CONTRACTOR DID NOT MAKE CHANGES
 TO DRIVEWAY.MUST REDUCE DRIVEWAY TO
 MEET ZONING GUIDELINES, 1000SQ FT OR 75%
 OF LANDSCAPE IN THE FIRST 25FT FRONT
 SETBACK.CALLED CONTRACTOR LEFT MSG ON
 VOICE MAIL, FILE D FOR P/U MM

Review Stop Z ZONING
Rev No 1 Status F Date 2004-10-28 Cont ID  
Sent By mmclean Date 2004-10-29 Time 12:49 Rev Time 0.00
Received By mmclean Date 2004-10-28 Time 16:41 Sent To I
Notes
2004-10-28 00:00:00DENIED, TOO MUCH CONCRETE IN THE FRONT
 MUST MEET 1000SQ FT OR 75% OF LANDSCAPE
 IN THE FIRST 25FT OF FRONT SETBACK
 WHICHEVER IS LESS CALLED CONTR. MM


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved