Plan Review Details - Permit 04100615
Plan Review Stops For Permit 04100615
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-01-26 Cont ID  
Sent By jgomez Date 2005-01-26 Time 10:44 Rev Time 3.00
Received By jgomez Date 2005-01-26 Time 10:43 Sent To PC
Notes
2005-01-26 00:00:00BUILDING REVIEW PROVISO (PROVIDE THE
 FOLLOWING PRIOR TO INSTALLATION OR
 CONSTRUCTION TO AVOID DELAYS/CONFLICT):
  
 1-COMPLETE INFO. FOR STORM SHUTTERS
 UNDER A SEPARATE PERMIT.
  
 2-PROVIDE COMPLETE FLORIDA OR LOCAL
 PRODUCT APPROVAL FOR:
 A) WINDOW MULLIONS: PROVIDE ALL INFO
 SUBMITTED FOR FLORIDA PRODUCT APPROVAL
 INCLUDING DRAWINGS OR APPLY FOR LOCAL
 PRODUCT APPROVAL IF MIAMI DADE-COUNTY
 NOA IS TO BE USED.
 **NOTE: CLEARLY INDICATE MULLION SIZES
 AND FASTENERS TO BE USED.
 B)GARAGE DOORS: PROVIDE EXACT DRAWINGS
 SUBMITTED FOR FLORIDA PRODUCT APPROVAL
 OR APPLY FOR LOCAL PRODUCT APPROVAL IF
 USING DADE COUNTY NOA.
 ***NOTE: MAKE SURE DOORS MEET THE DESIGN
 PRESSURES CALCULATED BY THE ARCHITECT.
  
 C) CABANA BATHS AND MECHANICAL ROOM.
  
 D) ENTRY DOORS WITH EXACT DRAWINGS THAT
 WERE SUBMITTED FOR FLORIDA PRODUCT
 APPROVAL (NOTE: OWNERSHIP HAS NOTHING TO
 DO WITH PRODUCT APPROVAL THE ISSUE IS
 FOR THE SAME PRODUCT THAT WAS APPROVED
 NOT THE COMPANY). OR, APPLY FOR LOCAL
 PRODUCT APPROVAL IF DADE COUNTY NOA IS
 TO BE USED IN THIS PROJECT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-01-06 Cont ID  
Sent By jgomez Date 2005-01-06 Time 10:47 Rev Time 0.00
Received By jgomez Date 2005-01-06 Time 10:47 Sent To PC
Notes
2005-01-06 00:00:00BUILDING REVIEW CHECKLIST:
 1-ARCHITET'S RESPONSE LETTER WAS
 ADDRESSED TO WRONG BUILDING DEPARTMENT.
 THIS IS CITY OF WEST PALM BEACH NOT
 INDIAN RIVER COUNTY.
  
 2-AHU HANGING DETAILS: A) PROVIDE SPECS
 FOR SIZE OF CHAINS AND BOLTS (NOTE:
 THERE IS NOT MECHANICAL ENGINEER ON THIS
 PROJECT AS INDICATED BY ARCHITECT).
  
 B) THERE ARE 2 DIFFERENT DETAILS SHOWN
 ON SHEET A2 AND A4. CLARIFY AND PROVIDE
 ONLY ONE COMPLETE DETAIL WITH SPECS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 3-SPECIFY FASTENERS FOR ROOF TILE AS
 REQUIRED BY SEC. 104.2.1.1 OF CITY
 AMENDMENTS TO FBC 2001. THIS IS DESIGNER
 RESPONSIBILITY NOT CONTRACTOR.
 CONTRACTOR IS TO PROVIDE PRODUCT THAT
 MEETS DESIGNER DESIGN AND SPECS.
  
 4-PROVIDE 2 COMPLETE COPIES OF FLORIDA
 OR LOCAL PRODUCT APPROVAL FOR:
 A) MASONITE DOORS NEED DRAWINGS FOR
 SELECTED DOOR AND 2 COPIES.
  
 B) PREMDOR EXTERIOR DOORSFOR OPAQUE
 DOORS AND GLAZED DOORS NEED FLORIDA OR
 APPLY FOR LOCAL PRODUCT APPROVAL.
 ONLY FLORIDA PRODUCT APPROVAL IS FOR USE
 STATEWIDE. DADE COUNTY PRODUCT APPROVALS
 REQUIRE MANUFACTURER TO APPLY FOR LOCAL
 PRODUCT APPROVAL WITH THE CITY AS
 REQUIRED BY CHAPTER 9B-72 OF D.C.A.
  
 C)SLIDING GLASS DOORS WITH SIZE AS SHOWN
 ON PLANS.
  
 D)GARAGE DOORS: CLEARLY IDENTIFY DOOR TO
 BE USED AND PROVIDE CLEAR DRAWINGS FOR
 SUCH DOOR.
  
 E)WINDOW MULLIONS: PROVIDE DRWINGS AND
 CLEARLY IDENTIFY MULLION SIZE AND
 FASTENING. SEC. 104.2.1.2 CITY
 AMENDEMNTS TO FBC 2001.
  
 5-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS OR APPLY FOR A SEPARATE
 PERMIT.
  
 6-OWES $15.94 FOR UPDATED/REVISED AREA
 FOR RADON FEES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-11-18 Cont ID  
Sent By jgomez Date 2004-11-18 Time 13:44 Rev Time 0.00
Received By jgomez Date 2004-11-18 Time 13:44 Sent To PC
Notes
2004-11-18 00:00:00CHECKLIST:
 1-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING BACK STAMPED DRAWINGS AND PAID
 RECEIPT.
  
 2-AHU HANGING DETAILS: SPECIFY SIZE OF
 HANGING CHAINS AND BOLTS. SEC.
 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 3-SPECIFY FASTENERS FOR ROOF TILE AS
 REQUIRED BY SEC. 104.2.1.1 CITY
 AMENDMENTS TO FBC 2001.
  
 4-SHEET A1: FOOTING F4 SHOWN ON
 FOUNDATION PLAN DOESN'T MATCH FOOTING
 F4
 SHOWN ON SCHEDULE. CLARIFY/REVISE AS
 REQUIRED.
  
 5-SHEET A5: A) MISSING SOME CONNECTORS.
 SEE PLANS AND SPECIFY THEM.
 B) DETAIL 7/A5: PROVIDE COMPLETE DETAIL
 SHOWING SPECS FOR L POST CAP. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 C) REVISE DETAIL 10/A5. NEED TO USE 2X
 AT ARCH AREA SO WINDOW FASTENERS HAVE
 COMPLETE EMBEDMENT. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 D) DETAIL 2/A5 AND 4/A5. UPDATE NUMBER
 AND TYPE OF FASTENERS. SEE LATEST USP
 CATALOGUE.
 E) REVISE DETAIL 14/A5 USP PA28
 CONNECTOR DOESN'T APPLY ON THIS
 INSTALLATION. THIS IS A WOOD POST CAP.
  
 6-PROVIDE FLORIDA O APPLY FOR LOCAL
 PRODUCT APPROVAL FOR:
 A) ENTRY DOOR.
 B) OUTSWING SIDE DOOR AT MECHANICAL
 ROOM
 C) OUTSWING DOORS AT MASTER BEDROOM AND
 CABANA BATH.
 D) SLIDING GLASS DOORS.
 E)FIXED WINDOWS INCLUDING WINDOW SIZES
 AS SHOWN ON PLANS.
 F) SINGLE HUNG WINDOWS.
 G) ROOF TILE.
 H) GARAGE DOOR WITH LEGIBLE DRAWINGS
 THAT WERE SUBMITTED TO THE FLORIDA
 BUILDING COMMISSION FOR APPROVAL AND
 CLEARLY INDICATE WHICH SPECIFIC MODELS
 WILL BE INSTALLED.
 I) ARCHED WINDOWS AS SHOWN ON PLANS.
 J) WINDOW AND DOOR MULLIONS AND CLEARLY
 INDICATED SIZE OF MULLIONS AND
 FASTENERS
 TO BE USED.
  
 7-PROVIDE COMPLETE INFORMATION FOR
 STORM
 SHUTTERS: A) FLORIDA OR LOCAL PRODUCT
 APPROVAL.
 B) SHUTTERS INFORMATION SUBMITTED
 APPLIES TO 110MPH WIND ZONE. THE CITY
 OF
 WEST PALM BEACH IS ON 140MPH WIND ZONE.
 C) DRAWINGS NEED TO HAVE ENGINEER'S
 ORIGINAL SEAL AND SIGNATURE SINCE
 ENGINEER NOTED THAT DRAWINGS ARE "FOR
 ONE PERMIT ONLY".
  
 8-OWES $ 1875.71 FOR UPDATED VALUATION
 AND RADON FEES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-02-09 Cont ID  
Sent By btrobaug Date 2006-02-09 Time 15:54 Rev Time 0.50
Received By btrobaug Date 2006-02-09 Time 15:54 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-01-21 Cont ID  
Sent By jleahy Date 2006-01-21 Time 08:19 Rev Time 0.30
Received By jleahy Date 2006-01-21 Time 08:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-10-27 Cont ID  
Sent By btrobaug Date 2004-10-27 Time 12:54 Rev Time 0.50
Received By btrobaug Date 2004-10-27 Time 12:34 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-01-31 Cont ID  
Sent By ptjomsto Date 2006-01-31 Time 08:33 Rev Time 0.00
Received By ptjomsto Date 2006-01-31 Time 08:33 Sent To  
Notes
2006-01-31 00:00:00REV/ELEC GIVEN TO BILL TROBAUGH

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-01-17 Cont ID  
Sent By adarroug Date 2006-01-17 Time 09:01 Rev Time 0.00
Received By adarroug Date 2006-01-17 Time 09:01 Sent To E
Notes
2006-01-17 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-01-18 Cont ID  
Sent By mjacobs Date 2005-01-18 Time 11:09 Rev Time 0.00
Received By mjacobs Date 2005-01-18 Time 11:09 Sent To B
Notes
2005-01-18 00:00:00TO "JG" DESK/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-12-08 Cont ID  
Sent By mjacobs Date 2004-12-08 Time 15:43 Rev Time 0.00
Received By mjacobs Date 2004-12-08 Time 15:43 Sent To M
Notes
2004-12-08 00:00:00SENT TO "M/AC" BOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By mmclean Date 2004-10-26 Time 12:45 Rev Time 0.00
Received By csiegber Date 2004-10-18 Time 17:40 Sent To  
Notes
2004-10-27 00:00:00TO SFD RACK/E
2004-10-18 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By prafter Date 2005-01-03 Time 08:15 Sent To  
Notes
2005-01-03 00:00:00 
  
 A/C PROVISO ON A/C PLAN .
 PAT RAFTER 1/05/05561/805/6719 .

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-11-01 Cont ID  
Sent By btrobaug Date 2004-10-27 Time 12:54 Rev Time 0.35
Received By pkrauss Date 2004-11-01 Time 12:28 Sent To P
Notes
2004-11-01 00:00:00DENIED:
 1.PLANS ARE REQUIRED TO BE SIGNED,
 SEALED & DATED BY THE ENGINEER/ARCHITECT
 INDICATED ON THE TITLE BLOCK PER FS
 471.025/481.221 & FAC 61G15-23.002 /
 61G1-16.004.PLEASE PROVIDE REQUIRED
 SIGNATURES, ETC. OR REMOVE THE TITLE
 BLOCK.
  
 2.SUPPLY AIR DUCT INTO BEDROOM 5 IS
 NOT VISIBLE.
  
 3.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS @ (561)805-6719.
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-01-25 Cont ID  
Sent By kstevens Date 2005-01-25 Time 15:44 Rev Time 0.33
Received By kstevens Date 2005-01-25 Time 15:44 Sent To  
Notes
2005-01-25 00:00:00NEW SHEETS RESUBMITTED

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-11-04 Cont ID  
Sent By kstevens Date 2004-11-04 Time 18:56 Rev Time 0.33
Received By kstevens Date 2004-11-04 Time 18:56 Sent To B1
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-10-26 Cont ID  
Sent By mmclean Date 2004-10-26 Time 12:44 Rev Time 0.00
Received By mmclean Date 2004-10-26 Time 12:44 Sent To I
Notes
***NONE***