Plan Review Details - Permit 04100556
| Plan Review Stops For Permit 04100556 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2005-07-06 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-07-06 |
Time |
10:07 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-07-06 |
Time |
10:07 |
Sent To |
|
|
| Notes |
| 2005-07-06 00:00:00 | SHEETS #12, 13 RED LINED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2005-06-02 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-06-02 |
Time |
09:33 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-06-02 |
Time |
09:32 |
Sent To |
|
|
| Notes |
| 2005-06-02 00:00:00 | ****DENIED**** | | | | | | 1) AT 8 STORIES IN HEIGHT, IT WOULD | | | APPEAR THAT THIS BUILDING MEETS THE | | | DEFINITION OF A HIGHRISE STRUCTURE. | | | PLEASE CLARIFY. | | | | | | 2) PLEASE ILLUSTRATE HOW THE NFPA 72 | | | REQUIREMENT FOR SURVIVABILITY WILL BE | | | MET. | | | | | | 3) HORNSTROBES AND SPEAKERS APPEAR TO BE | | | MISSING IN THE CORRIDORS AT THE PARTIAL | | | 2ND GROUND FLOOR LEVEL, SHEETS # 12&13. | | | | | | 4) PLEASE PROVIDE FURTHER EXPLANATION IN | | | REGARDS TO WHAT DEVICES WILL ACTIVATE | | | STAIRWELL PRESSURIZATION. | | | | | | | | | MIKE WENNERGREN, A/CAPTAIN | | | WPBFR(561) 835-2951 OR 805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2004-10-25 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-10-15 |
Time |
10:52 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2004-10-25 |
Time |
10:50 |
Sent To |
|
|
| Notes |
| 2004-10-25 00:00:00 | *******DENIED*************************** | | | | | | 1) NEW FIRE ALARM SYSTEMS SHALL BE | | | LISTED FOR CENTRAL STATION SERVICE. | | | | | | 2) ALL NEW FIRE ALARM SYSTEMS THAT | | | SUPERVISE FIRE SPRINKLER SYSTEMS SHALL | | | BE UL CERTIFICATED AND HAVE DOCUMENT | | | ATTESTING TO THIS CERTIFICATION PRIOR TO | | | FINAL APPROVAL OF THE FIRE ALARM SYSTEM. | | | | | | 3) THE WEST PALM BEACH FIRE MARSHAL | | | OFFICE REQUIRES DUCT DETECTORS TO SEND | | | A GENERAL FIRE ALARM NOT A SUPERVISORY. | | | | | | 4) THE FIRE ALARM SYSTEM SHALL BE | | | CLASS "A" OR FULLY ADDRESSABLE. | | | | | | | | | NATE MCCRAY, CAPTAIN | | | 561-835-2910 OR 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-07-05 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-07-05 |
Time |
13:29 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-07-05 |
Time |
13:29 |
Sent To |
FIRE |
|
| Notes |
| 2005-07-05 00:00:00 | TO "NMCRAY" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-05-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-05-19 |
Time |
16:08 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-05-19 |
Time |
15:37 |
Sent To |
FIRE |
|
| Notes |
| 2005-05-19 00:00:00 | TO "F" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-10-15 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-10-15 |
Time |
10:52 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-10-15 |
Time |
10:52 |
Sent To |
FIRE |
|
| Notes |
|
|
|