Plan Review Details - Permit 04100446
Plan Review Stops For Permit 04100446
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-02-28 Cont ID  
Sent By jwitmer Date 2006-02-28 Time 10:23 Rev Time 2.22
Received By jwitmer Date 2006-02-28 Time 08:19 Sent To PC
Notes
2006-02-28 00:00:00WOOD TRUSS SHOP DRAWINGS BLDG 1-4
 WINDOW SHOP DRAWINGS BLDG 1-4

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-12-20 Cont ID  
Sent By jwitmer Date 2005-12-20 Time 07:35 Rev Time 0.75
Received By jwitmer Date 2005-12-20 Time 07:15 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-11-30 Cont ID  
Sent By jwitmer Date 2005-11-30 Time 16:29 Rev Time 0.55
Received By jwitmer Date 2005-11-30 Time 16:29 Sent To PC
Notes
2005-11-30 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04100446
 ADD: 1185 25TH ST
 CONT:CHARLAND RUREY CONST
 TEL: (954)347-6365
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHOP DRAWINGS ARE TO BE REVIEWED BY
 THE DESIGN PROFESSIONAL WILL APPROVAL
 STAMP BEFORE SUBMITION TO THE BUILDING
 DEPARTMENT.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-08-27 Cont ID  
Sent By jwitmer Date 2005-08-27 Time 11:16 Rev Time 1.22
Received By jwitmer Date 2005-08-27 Time 10:14 Sent To  
Notes
2005-08-27 00:00:00BUILDING PROVISO: THAT ALLTERRA DOES THE
 ADDITIONAL TEST BORES TO VERIFY SOILS
 CONDITIONS AS PER LETTER 11-19-04

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-06-15 Cont ID  
Sent By jwitmer Date 2005-06-15 Time 16:06 Rev Time 0.00
Received By jwitmer Date 2005-06-15 Time 16:06 Sent To  
Notes
2005-06-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04100446
 ADD: NOT YET ASSIGNED
 PCN: 74-43-43-09-11-003-0000
 CONT: COMPLETE PROPERTY MANAGEMENT
 TEL: (561)252-8372
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
 2ND REVIEW
 ACTION: DENIED
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 INDICATE COMPLIANCE WITH 1804.2.2
 QUESTIONABLE SOILS, ALLTERRA REPORT
 DATED MARCH 5/ 2004 INDICATES THAT PEAT
 WAS DISCOVERED WITH BORING# 2, SHOW HOW
 YOU WILL COMPLY WITH THIS SECTION?
 BORING # 2 & 3 BOTH INDICATE THE
 EXISTANCE OF PEAT BENEATH THE BUILDING.
  
 2)COMMENT #3 FROM THE PREVIUOS REVIEW,
 FBC* 105.3RESIDENT INSPECTOR.
 SUBMIT INSPECTOR RESUME' AND LICENSE
 DOCUMENTS TO HAROLD PISKURA, DIRECTOR OF
 THE RESIDENT INSPECTOR PROGRAM.A
 RESIDENT INSPECTOR PROGRAM IS REQUIRED,
 ON THIS PROJECT, DUE TO ONE OR MORE OF
 THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN
 OR METHODS OF CONSTRUCTION
 CALL HAROLD PISKURA FOR THE SPECIAL
 INSPECTOR PROGRAM AT 805-6711.
  
 3) COMMENT# 6 FROM THE PEVIOUS REVIEW,
 BACK ENTRY DOORS INDICATE A 3/4 HR
 RATING, AS PER 705.1.1.2. THE SUBMITTED
 PRODUCT APPROVAL BENCHMARK EXTERIOR DOOR
  
 FL1190 IS TO BE USED FOR RESIDENTIAL
 USE, STEEL DOOR W/ WOOD JAMBS. PROVIDE
 THE FIRE TESTING REPORT OR PROVIDE
 ANOTHER PRODUCT.
  
 4) COMMENT # 9 FROM THE PREVIOUS REVIEW,
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) TRUSS ANCHORS
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4B) ROOFING: HIGHLIGHT WHICH TYPE OF
 ROOF TILE SHALL BE INSTALLED FROM THE
 TESTING REPORT.
  
 4C) TAMCO ROOFING- MODIFIED,HIGHLIGHT
 WHICH DECK TYPE, DECK DESCRIPTION, &
 SYSTEM TYPE. SEE THE LIMITATIONS AND THE
 MAXIMUM DESIGN PRESSURE FOR EACH TYPE OF
 APPLICATION******
  
  
 5A) COMMENT # 10 FROM THE PREVIOUS
 REVIEW SHEET A-6 SOUTH ELEVATION
 INDICATES ARCHITECTURAL FEATURES ABOVE
 THE BEAMBUT NO INFORMATION, PLEASE
 PROVIDE?
  
 5B) THE SAME SHEET A-6 SHOWS VARIOUS
 REVEALS ON BOTH THE FRONT AND REAR OF
 THE BUILDING, HOW IS THIS TO BE CREATED?
  
 6) COMMENT# 11 FROM THE PREVIOUS REVIEW,
 BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 7) S-6 BEAM SCHEDULE NOT LEGABLE,
 104.2.1.3 THE BUILDING OFFICIAL MAY SET
 STANDARDS THROUGH DEPARTMENTAL POLICY
 STANDARDS FOR PLANS AND SPRCIFICATIONS.
 PLANS THAT ARE NOT LEGIBLE, STANDARDS
 ARE SET FOR CLARITY & CONTRAST.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-11-04 Cont ID  
Sent By kstevens Date 2004-11-05 Time 11:00 Rev Time 0.00
Received By JWITMER Date 2004-11-05 Time 15:29 Sent To  
Notes
2004-11-05 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04100446
 ADD: NOT YET ASSIGNED
 PCN: 74-43-43-09-11-003-0000
 CONT: COMPLETE PROPERTY MANAGEMENT
 TEL: (561)252-8372
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
 1ST REVIEW
 ACTION: DENIED
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 INDICATE COMPLIANCE WITH 1804.2.2
 QUESTIONABLE SOILS, ALLTERRA REPORT
 DATED MARCH 5/ 2004 INDICATES THAT PEAT
  
 WAS DISCOVERED WITH BORING# 2, SHOW HOW
 YOU WILL COMPLY WITH THIS SECTION?
  
 2) FOR BUILDING# 1 & BUILDING# 2, SHOW
 COMPLIANCE WITH TABLE 500 FOR STORAGE:
 A) BUILDING# 1 TABLE 500 FOR TYPE IV,
 UNPROTECTEDIF TAKING GENERAL AREA
 MODIF-
 ICATIONS YOU CAN ONLY TAKE THE AREA
 UNDER COLUMN(H)@ 100% THE AREA INCREASE
 WILL BRING YOU TO 32,000 SQ FT SHORT OF
 THE 35,123 SQ FT REQUIRED. ADDITIONAL
 OCCUPANCY MODIFICATIONS FOR STORAGE CAN
 BE TAKEN IF FIRE SPRINKLERS FOR STORAGE
  
 OCCUPANCY ARE INSTALLED. THERE IS AN
 EXCEPTION WITHA CLEAR 60' AREA AROUND
 THE STRUCTURE BUT WITH HAVING MORE THAN
  
 ONE TENANT THE EXCEPTION CAN NOT BE
 TAKEN BECAUSE OF NONCOMBUSTIBLE
 PRODUCTS
 AND WRAPPINGS CONTAINERS AND PALLETS.
 B) BUILDING# 2 CAN TAKE THE AREA
 INCRESE
 ON THREE SIDES, THE AREA INCREAS IS
 38.13% OF THE NON SPRINKLERED AREA OR AN
  
 ADDITIONAL 6080 SQ FT FOR A TOTAL OF
 22,080 TOTAL SQ FT.
 C) ONE WAY TO COMPLY WITH TABLE 500
 WOULD BE TO PUT A 4HR FIRE WALL
 CENTERED
 IN BOTH BUILDINGS, THIS WILL CREATE (4)
 BUILDINGS AND COMPLY WITH TABLE 500.IF
 THIS APPROACH IS CONSIDERED, SEE TABLE
 709.3.1 FOR EQUIVALLENT THICKNESS OF
 BEARING & NONBEARING CONCRETE MASONARY
 WALLS. PROVIDE FROM BLOCK MANUFACTURER.
  
 3) FBC* 105.3RESIDENT INSPECTOR.
 SUBMIT INSPECTOR RESUME' AND LICENSE
 DOCUMENTS TO HAROLD PISKURA, DIRECTOR OF
 THE RESIDENT INSPECTOR PROGRAM.A
 RESIDENT INSPECTOR PROGRAM IS REQUIRED,
 ON THIS PROJECT, DUE TO ONE OR MORE OF
 THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN
 OR METHODS OF CONSTRUCTION
 CALL HAROLD PISKURA FOR THE SPECIAL
 INSPECTOR PROGRAM AT 805-6711.
  
 4)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SP-1 DRAWING INDEX INDICATES STRUCTURAL
 PLANS S1-8, PLANS SUBMITTED ARE S1-4
 FOR
 THE FOUNDATION ONLY.THERE IS NO
 FONDATION, COLUMN NOR BEAM SCHEDULE.
  
 5) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 THE STRUCTURAL PLANS (S1-4) INDICATE THE
  
 USE OF 12" BLOCK FOR THE FRONT OF THE
 BUILDING WITH A RECESS 8"BLOCK AT THE
  
 GARAGE OPENINGS, HOW WILL THE BLOCK TIE
  
 TOGETHER, WILL A RUNNING BOND BE USED
 VERSES STACK BOND?
  
 6) BLDG# 2, BACK ENTRY DOORS INDICATE A
 3/4HR RATING, AS PER 705.1.1.2, THE
 SUBMITTED PRODUCT APPROVAL BENCHMARK
 EXTERIOR DOOR FL1190 IS FOR RESIDENTIAL
 USE, STEEL DOOR WITH WOOD DOOR JAMBS.
 PROVIDE THE FIRE TESTING REPORT.
  
 7) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED, SHEET#
 7 DETAIL# 2 INDICATES THE HOLLOWCORE
 ROOF DECK SYSTEM PARARLLEL WITH THE
 FRONT OF THE BUILDINGS, PLANS DO NOT
 PROVIDE THE LENGHTS OF THE PLANKS,
 SHEET
 A-2 INDICATES 6" METAL STUD PARTITION,
 DOES THE ROOF PLANK SYSTEM SPAN THIS
 OR IS THIS A BEARING WALL? PLANS DO NOT
 PROVIDE INFORMATION FOR THIS PARTION,
 STUD GAUGE, SPACING C/C HEIGHT, DRYWALL
 THICKNESS, ETC...
 8) PLANS DO NOT PROVIDE THE FOLLOWING
 INFORMATION:
 FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 9 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) TRUSS ANCHORS/ WOOD/WOOD CONNECTORS
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 10) SHEET A-6, SOUTH ELEVATION INDICATES
 ARCHITECTURE FEATURES ABOVE THE BEAM
 BUT
 NO INFORMATION.
  
  
 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-08-11 Cont ID  
Sent By dpalmer Date 2005-08-11 Time 19:19 Rev Time 0.75
Received By dpalmer Date 2005-08-11 Time 19:19 Sent To  
Notes
2005-08-11 00:00:00 
 ALL EM/ EXT LIGHTS.700.12E
 THE BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-06-13 Cont ID  
Sent By dpalmer Date 2005-06-13 Time 08:58 Rev Time 2.00
Received By dpalmer Date 2005-06-09 Time 16:39 Sent To  
Notes
2005-06-13 00:00:00************* UNSAT *********
  
 1)NOTE: PLEASE SEE NOTE #2 FROM PREVIOUS
 REVIEW.
  
 2)NOTE: PLEASE SEE SEC'S BLDG -1, SHOWS
 250MCM FOR 600A SERVICE W/ 300A FUSES.
 PLEASE SEE 310.16,240.4. FOR MIN SEC'S.
 PLEASE CORRELATE SEC SIZING WITH LOAD AS
 SHOWN ON LOAD CALCULATIONS.
  
 3)NOTE: PLEASECLARIFY NOTE AT LOWER
 LEFT OF BLDG'S #3 AND #4 RISER:
 NOTE: NO 3 0. - ALL 1 0 22KAIC.?????
  
 4)NOTE: PLEASE SEE ALL SUB PANELS ARE
 SHOWN AS MLB? PLEASE CLARIFY IF THESE
 PANELS ARE MCB(MAIN CIRCUIT BRKR) OR
 MLO( MAIN LUG ONLY)?
  
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 PLEASE ONLY INSERT NEW REVISED SHEETS
 INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
  
 PLEASE SEE ANY OTHER COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-10-27 Cont ID  
Sent By dpalmer Date 2004-10-27 Time 05:47 Rev Time 0.50
Received By dpalmer Date 2004-10-27 Time 05:37 Sent To  
Notes
2004-10-27 00:00:00********** UNSAT ***********
  
 1)NOTE:PLEASE SEE PLANS ARE NOT COMPLETE
 AT THIS TIME FOR COMPLETE REVIEW.
 PLEASE SUBMIT SERVICE(S) RISER,PANEL
 SCHEDULES, GROUNDING ETC.
 215.5
  
 2)NOTE: PLEASE SEE PLANS ARE REQUIRED TO
 BE SIGNED, DATED AND SEALED BY A PE.
 UNDER FS 471.003H1
  
 3)NOTE: PLANS NOTE: ALL EM/EXT LTS
 CIRCUITED W/ LOCAL BRANCH CIRCUIT,HOW-
 -EVER THESE APPEAR TO BE SHOWN ON OTHER
 CIRCUITS AND UNABLE TO VERIFY AT THIS
 TIME. (NO PANEL SCHEDULES)
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWER(S) AS IT MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 DUE TO PLANS NOT BEING COMPLETE AT THIS
 TIME, THERE MAY BE OTHER COMMENTS ON
 NEXT REVIEW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2005-06-13 Cont ID  
Sent By mamini Date 2005-06-13 Time 15:28 Rev Time 1.00
Received By mamini Date 2005-06-13 Time 15:28 Sent To  
Notes
2005-06-13 00:00:00PASSED WITH PROVISOS:
  
  
 1. EROSION AND SEDIMENTATION CONTROL
 DEVICES SHALL BE IN PLACE PRIOR TO
 BEGINNING CLEARING OR GRUBBING,
 DEMOLITION, OR OTHER SUCH CONSTRUCTION
 ACTIVITIES.THE DEVICES SHALL BE
 INSTALLED, MONITORED, AND MAINTAINED IN
 ACCORDANCE WITH ALL APPLICABLE FEDERAL,
 STATE, AND LOCAL REQUIREMENTS.
  
 2. WORK WITHIN PUBLIC R.O.W REQUIRES A
 PERMIT FROM PUBLIC UTILITIES AND
 ENGINEERING, PLEASE SUBMIT M.O.T PLANS
 ALSO AT THE TIME OF APPLICATION ATT:
 WINDEL PALMER, 494-1086.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2004-10-15 Cont ID  
Sent By mamini Date 2004-10-15 Time 13:48 Rev Time 1.00
Received By mamini Date 2004-10-15 Time 13:48 Sent To  
Notes
2004-10-15 00:00:00FAILED:
 1. ALL THE ISSUES REGARDING THE EXISTING
 EASEMENTS AND CONSTRUCTION IN THESE AREA
 MUST BE ADDRESSED WITH PUBLIC UTILITIES
 AND ENGINEERING,494-1085 MANNY GONZALEZ.
 2. ALL THE CONNECTIONS TO THE SEVICES
 MUST BE REVIEWED, APPROVED AND SIZED
 BY THE PUBLIC UTILITIES AND ENGINEERING,
 PLEASE SUBMIT CIVIL PLANS ONLY ATT;MANNY
 GONZALEZ.
 3. PLANS SHOWS THAT SEWER BEING
 CONNECTED TO THE EXISTING CITY LIFT
 STATION, NO DETAILS FOR THIS CONNECTION
 IS SHOWN.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-08-30 Cont ID  
Sent By mwennerg Date 2005-08-30 Time 14:33 Rev Time 0.00
Received By mwennerg Date 2005-08-30 Time 14:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2005-06-14 Cont ID  
Sent By mwennerg Date 2005-06-14 Time 14:20 Rev Time 0.00
Received By mwennerg Date 2005-06-14 Time 14:19 Sent To  
Notes
2005-06-14 00:00:00****DENIED****
  
 PLEASE NOTE THAT COMMENTS FROM THE FIRST
 FIRE REVIEW HAVE NOT BEEN ADDRESSED.
 PLEASE ADDRESS THESE COMMENTS AND SHOW
 CHANGES OR ADDITIONS ON THE DRAWINGS.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 805-6722 OR 835-2951

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-11-05 Cont ID  
Sent By mcarsill Date 2004-11-05 Time 15:09 Rev Time 0.00
Received By mcarsill Date 2004-11-05 Time 15:09 Sent To  
Notes
2004-11-05 00:00:001) BUILDING ADDRESSES REQUIRED. A
 MINIMUM OF AT SIX HIGH NUMBERS ARE
 REQUIRED.
  
 2) WHAT TYPES OF COMMODITIES WILL
 BE STORED IN THE BUILDING. ANY
 FLAMMABLE
 GASES, LIQUIDS OR SOLIDS PLANNED TO
 BE STORED. ANY COMBUSTIBLES LIQUIDS
 OR SOLIDS PLANNED. ALSO ANY HAZARDOUS
 CHEMICALS PLANNED.
  
 3) TENANT SEPARATION WALLS REQUIRED
 BETWEEN TENANTS IF DIFFERENT.
  
 4) PLEASE PROVIDE INFORMATION ON
 HOURLY RATINGS FOR DEMISING WALLS.
  
 5) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND CEILINGS.
  
 6) NO MENTION OF ANY PORTABLE FIRE
 EXTINGUISHERS.
  
 7) A FIRE ALARM SYSTEM MAY BE REQUIRED
 IF EXCEPTIONS OF THE CODE CANNOT
 BE MET.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-01-10 Cont ID  
Sent By adarroug Date 2007-01-10 Time 08:37 Rev Time 0.00
Received By adarroug Date 2007-01-10 Time 08:37 Sent To Z
Notes
2007-01-10 08:38:11TO "Z" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-11-15 Cont ID  
Sent By adarroug Date 2006-11-15 Time 09:48 Rev Time 0.00
Received By adarroug Date 2006-11-15 Time 09:48 Sent To P
Notes
2006-11-15 09:48:50TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-02-19 Cont ID  
Sent By adarroug Date 2006-02-19 Time 10:26 Rev Time 0.00
Received By adarroug Date 2006-02-19 Time 10:26 Sent To B
Notes
2006-02-19 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-12-13 Cont ID  
Sent By adarroug Date 2005-12-13 Time 18:12 Rev Time 0.00
Received By adarroug Date 2005-12-13 Time 18:12 Sent To B
Notes
2005-12-13 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-11-29 Cont ID  
Sent By adarroug Date 2005-11-29 Time 14:47 Rev Time 0.00
Received By adarroug Date 2005-11-29 Time 14:47 Sent To B
Notes
2005-11-29 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-09-01 Cont ID  
Sent By adarroug Date 2005-09-01 Time 17:04 Rev Time 0.00
Received By adarroug Date 2005-09-01 Time 17:04 Sent To P
Notes
2005-09-01 00:00:00TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-08-04 Cont ID  
Sent By adarroug Date 2005-08-04 Time 14:29 Rev Time 0.00
Received By adarroug Date 2005-08-04 Time 14:29 Sent To  
Notes
2005-08-05 00:00:00TO "COMM" BD#54
2005-08-04 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-05-16 Cont ID  
Sent By adarroug Date 2005-05-16 Time 14:49 Rev Time 0.00
Received By adarroug Date 2005-05-16 Time 14:49 Sent To  
Notes
2005-05-27 00:00:00TO "COMM" BD#23
2005-05-16 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date 2005-11-05 Time   Rev Time 0.00
Received By csiegber Date 2004-10-14 Time 09:57 Sent To  
Notes
2004-10-14 00:00:00TO COMM BD#16

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2005-08-16 Cont ID  
Sent By pkrauss Date 2005-08-16 Time 16:40 Rev Time 0.20
Received By pkrauss Date 2005-08-16 Time 16:28 Sent To  
Notes
2005-08-16 00:00:00MECHANICAL CONTRACTOR TO SUBMIT PLANS
 WITH MECHANICAL PERMIT APPLICATION.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-06-21 Cont ID  
Sent By hmoser Date 2005-06-21 Time 14:19 Rev Time 0.00
Received By hmoser Date 2005-06-21 Time 14:10 Sent To  
Notes
2005-06-21 00:00:00NO COMMENTS WERE ANCERED FRON LAST
 REVIEW.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-11-04 Cont ID  
Sent By pkrauss Date 2004-11-04 Time 11:32 Rev Time 0.40
Received By pkrauss Date 2004-11-04 Time 11:32 Sent To  
Notes
2004-11-04 00:00:00DENIED:
 1.PLAN SHEET SP-1 DRAWING INDEX, PLANS
 S-5 THROUGH S-8 ARE NOT INCLUDED WITH
 SUBMITTAL.
  
 2.ENERGY CALCULATIONS ARE REQUIRED PER
 2001 FBC CHAPTER 13 IN ACCORDANCE WITH
 CHAPTER 4.
  
 3.PROVIDE MECHANICAL PLANS.PLEASE
 INDCLUDE THE FOLLOWING:
 1) EQUIPMENT SCHEDULE
 2) LOCATION OF EQUIPMENT.
 3) PROVIDE DETAIL OR MANUFACTURER
 SUBMITTAL/INSTALLATION INSTRUCTIONS
  
 FOR ANY CURBS OR STANDS LOCATED ON
 THE ROOF.
 4) INDICATE CONDENSATE LINE SIZE,
 TERMINATION & PIPE MATERIAL.
 5) INDICATE ACCESS TO ROOF.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS @ (561)805-6719
  

Review Stop P PLUMBING
Rev No 6 Status P Date 2006-12-26 Cont ID  
Sent By jleech Date 2006-12-26 Time 15:04 Rev Time 0.00
Received By jleech Date 2006-12-26 Time 15:04 Sent To  
Notes
2006-12-26 15:05:20REVISED SANITARY RISER DIAGRAM

Review Stop P PLUMBING
Rev No 5 Status F Date 2006-11-21 Cont ID  
Sent By jleech Date 2006-11-21 Time 15:03 Rev Time 0.00
Received By jleech Date 2006-11-21 Time 15:03 Sent To  
Notes
2006-11-21 15:19:21DENIED;
  
 1. RISER DIAGRAM DOES NOT MATCH FLOOR PLANS. BATHROOMS
 ARE BACK TO BACK . EATHER CHANGE THE BATHROOM PIPING OR
 THE BUILDING DRAIN.
 2. RISER DIAGRAM SHOWS MORE BATHROOMS THAN ARE SHOWN ON
 FLOOR PLAN.
 3. MOP SINK CANNOT BE PART OF THE BATHROOM WET VENT SEE
 FBC-2001 PLUMBING SECTION 909.1.
 4. AS NOTED ON APPROVED PLUMBING PAGE A PROVISO WAS
 NOTED THAT ONE 3" STACK IS REQUIRED FOR EACH BUILDING.
 NOT SHOWN ON REVISED SANITARY RISER DIAGRAM.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-09-16 Cont ID  
Sent By pschmitz Date 2005-09-16 Time 10:23 Rev Time 0.00
Received By pschmitz Date 2005-09-16 Time 10:22 Sent To  
Notes
2005-09-16 00:00:00PROVISO:
 SEE SHT P-1.
  
 ONE 3" VTR ON EACH SANITARY LATERIAL.

Review Stop P PLUMBING
Rev No 3 Status F Date 2005-08-28 Cont ID  
Sent By pschmitz Date 2005-08-28 Time 12:39 Rev Time 0.00
Received By pschmitz Date 2005-08-28 Time 12:40 Sent To  
Notes
2005-08-28 00:00:00PLUMBING PLAN REVIEW EXAMINER, FBC 2001
 PAUL SCHMITZ561-805-6692
  
 [email protected]
 FBC- P2001
 FBC- B2001
 DENIED
 1.)SHT P-1, TYPICAL, 3" VTR THRU 8" BEAM
 NOT APPROVED
 ?1907.3.5 EXCEPT WHEN PLANS FOR
 CONDUITS AND PIPES ARE APPROVED BY THE
 ENGINEER, CONDUITS AND PIPES EMBEDDED
 WITHIN A SLAB, WALL OR BEAM (OTHER
 THAN THOSE MERELY PASSING THROUGH)
 SHALL SATISFY THE FOLLOWING:
 1. THEY SHALL NOT BE LARGER IN
 OUTSIDE DIMENSION THAN ONE-THIRD THE
 OVERALL THICKNESS OF SLAB, WALL OR
 BEAM IN WHICH THEY ARE EMBEDDED.
 2. THEY SHALL NOT BE SPACED CLOSER
 THAN THREE DIAMETERS OR WIDTHS ON
 CENTER.
 3. THEY SHALL NOT IMPAIR
 SIGNIFICANTLY THE STRENGTH OF THE
 CONSTRUCTION.
  
 2.)SHT P-1, TYPICAL, WATER RISER:
 TABLE 604.5, MINIMUM SIZE OF FIXTURE
 WATER SUPPLY, 1/2"
  
 3.)SHT P-1 PREVIOUS NOTE:
 "EXAMLPE PROVIDED"
 SHT P-1 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS. NO FITTINGS
 APPROVED AS SHOWN ON RISER. SEE EXAMPLE
 OF TYPICAL BACK-TO-BACK AND SINGLE
 TOILET ROOM PIPING FOR RISER.
  
 4.) SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL AND FS 553.80(2)(B)
  
 END OF COMMENTS

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-06-20 Cont ID  
Sent By kstevens Date 2005-06-20 Time 11:16 Rev Time 1.00
Received By kstevens Date 2005-06-20 Time 11:16 Sent To  
Notes
2005-06-20 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
 1. SHTS A-1 THRU A-4 A SERVICE SINK IS
 REQUIRED IN EACH SPACE PER TALBE 403.1.
 - NO RESPONSE, COMMENT NOT ADDRESSED.
 ****************NEW COMMENT*************
 1B. SEAL SHALL CONTAIN THE INFORMATION
 REQUIRED BY FAC 61G1-16.002 AND THIS
 INFORMATION SHALL BE IMPRESSED ON EACH
 SHEET. FS 481.221 - NO INFORMATIONS CAN
 BE GLEANED FROM THE SEAL.
 2B. SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL AND FS 553.80(2)(B)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-11-01 Cont ID  
Sent By kstevens Date 2004-11-01 Time 15:19 Rev Time 1.25
Received By kstevens Date 2004-11-01 Time 15:07 Sent To  
Notes
2004-11-01 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHTS A-1 THRU A-4 A SERVICE SINK IS
 REQUIRED IN EACH SPACE PER TABLE 403.1
 2) SHT P-1 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS. NO FITTINGS
 APPROVED AS SHOWN ON RISER. SEE EXAMPLE
 OF TYPICAL BACK-TO-BACK AND SINGLE
 TOILET ROOM PIPING FOR RISER.
 2) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SUPPLY TO THE BLDG. SECTION
 608.13.2
 3) INDICATE IF WATER RISER IS OVERHEAD
 OR UNDERGROUND. SECTION 104.2.1
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2005-08-16 Cont ID  
Sent By mmclean Date 2005-08-16 Time 09:21 Rev Time 0.00
Received By mmclean Date 2005-08-16 Time 09:21 Sent To  
Notes
2005-08-16 00:00:00APPROVED BY ANGELLA JONES-VANN

Review Stop Z ZONING
Rev No 2 Status F Date 2005-06-14 Cont ID  
Sent By mmclean Date 2005-06-14 Time 10:27 Rev Time 0.00
Received By mmclean Date 2005-06-14 Time 10:27 Sent To  
Notes
2005-06-14 00:00:00DENIED,
 1. RESOLUTION NO 420-04 - CONDITION
 2/3/4 HAVE NOT BEEN MET
  
 ANGELLA JONES-VANN
 ZONING ADMINISTRATOR
 822-1435

Review Stop Z ZONING
Rev No 1 Status F Date 2004-10-25 Cont ID  
Sent By ajones Date 2004-10-25 Time 16:41 Rev Time 0.25
Received By ajones Date 2004-10-25 Time 16:41 Sent To  
Notes
2004-10-25 00:00:001. SOUTH ELEVATION OF BUILDING #1 NEEDS
 TO MATCH THE FACADE OF THE SOUTH ELEVATI
 ON OF BUILDING #2.
 2.NO LANDSCAPE PLAN WAS PROVIDED WITH
 THE SUBMITTAL.
 3.NO UTILITITY EASEMENTS WERE PROVIDED
 AS PER THE COMMISSION APPROVAL
 4.APPLICANT NEED TO OBTAIN APPROVAL FR
 OM THE PUBLIC UTILITIES DEPT. TO PLACE T
 THE LANDSCAPE BUFFER ALONG THE SOUTH PRO
 PERTY LINE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved