Plan Review Details - Permit 04100371
Plan Review Stops For Permit 04100371
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-10-28 Cont ID  
Sent By kstevens Date 2004-10-27 Time 17:23 Rev Time 0.00
Received By lsmith Date 2004-11-06 Time 07:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-10-25 Cont ID  
Sent By csiegber Date 2004-10-25 Time 10:29 Rev Time 0.33
Received By btrobaug Date 2004-10-25 Time 11:58 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-11-01 Cont ID  
Sent By csiegber Date 2004-11-01 Time 15:40 Rev Time 0.00
Received By csiegber Date 2004-11-01 Time 15:40 Sent To P
Notes
2004-11-01 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-10-25 Cont ID  
Sent By csiegber Date 2004-10-25 Time 10:29 Rev Time 0.00
Received By csiegber Date 2004-10-25 Time 10:29 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-10-12 Cont ID  
Sent By mmclean Date 2004-10-22 Time 11:23 Rev Time 0.00
Received By csiegber Date 2004-10-12 Time 11:40 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-11-06 Cont ID  
Sent By pschmitz Date 2004-11-06 Time 07:29 Rev Time 0.00
Received By pschmitz Date 2004-11-06 Time 07:29 Sent To  
Notes
2004-11-06 00:00:00BACK FLOW PREVENTER INSTALLED PRIOR TO
 STARTING WORK ON POOL

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-10-27 Cont ID  
Sent By btrobaug Date 2004-10-25 Time 12:44 Rev Time 0.00
Received By kstevens Date 2004-11-06 Time 06:48 Sent To B
Notes
2004-10-27 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 2) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 3) FBC-2001 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-10-22 Cont ID  
Sent By csiegber Date 2004-10-12 Time 11:40 Rev Time 0.00
Received By mmclean Date 2004-10-22 Time 11:23 Sent To I
Notes
***NONE***