Plan Review Details - Permit 04100367
Plan Review Stops For Permit 04100367
Review Stop G GAS REVIEW
Rev No 1 Status P Date 2005-03-17 Cont ID  
Sent By gsalfeld Date 2005-03-17 Time 14:20 Rev Time 0.50
Received By gsalfeld Date 2005-03-17 Time 14:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-10-12 Cont ID  
Sent By csiegber Date 2004-10-12 Time 11:22 Rev Time 0.00
Received By csiegber Date 2004-10-12 Time 11:22 Sent To P
Notes
2004-10-12 00:00:00TO GAS

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-10-26 Cont ID  
Sent By csiegber Date 2004-10-12 Time 11:22 Rev Time 1.00
Received By kstevens Date 2004-10-26 Time 11:18 Sent To  
Notes
2004-10-26 00:00:00 
  
  
  
 PER N. MELICK MANUFACTURE INFO
 NOT REQUIRED FOR 1 & 2 FAMILY HOMES.
 JULY 17, 2002 OFFICAL INTERPRETATION.
 THE FIELD INSPECTOR SHALL VERIFY THE
 INSTALLED EQUIPMENT INPUT DOES NOT EX-
 CEED THE PIPE SIZING.
  
 IF DRYER/HEATER ROOM IS A CONFINED SPACE
 OPENINGS REQUIRED PER SECTION 304.3.1 0R
 SECTION 304.3.2 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED DRYER.
 MINIMUM 4,500 CUBIC FEET REQUIRED FOR
 WATER HEATER ROOM
  
  
  
  
  
  
  
  
  
  
 B