Plan Review Details - Permit 04100287
Plan Review Stops For Permit 04100287
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-10-29 Cont ID  
Sent By jwitmer Date 2004-10-29 Time 08:41 Rev Time 1.11
Received By jwitmer Date 2004-10-29 Time 07:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-10-18 Cont ID  
Sent By dpalmer Date 2004-10-18 Time 08:28 Rev Time 0.33
Received By dpalmer Date 2004-10-15 Time 16:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-11-03 Cont ID  
Sent By nmccray Date 2004-11-03 Time 11:57 Rev Time 0.00
Received By nmccray Date 2004-11-03 Time 11:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-12-09 Cont ID  
Sent By mjacobs Date 2004-12-09 Time 09:36 Rev Time 0.00
Received By mjacobs Date 2004-12-09 Time 09:36 Sent To P
Notes
2004-12-09 00:00:00SENT TO "P" BOX.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-11-09 Cont ID  
Sent By csiegber Date 2004-11-09 Time 11:35 Rev Time 0.00
Received By csiegber Date 2004-11-09 Time 11:35 Sent To P
Notes
2004-11-09 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-23 Cont ID  
Sent By kstevens Date 2004-11-03 Time 15:35 Rev Time 0.00
Received By kstevens Date 2004-10-08 Time 15:36 Sent To  
Notes
2004-10-08 00:00:00TO COMM BD#10

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-12-23 Cont ID  
Sent By kstevens Date 2004-12-23 Time 15:37 Rev Time 1.00
Received By kstevens Date 2004-12-23 Time 15:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-11-24 Cont ID  
Sent By mjacobs Date 2004-12-09 Time 09:37 Rev Time 0.33
Received By kstevens Date 2004-11-24 Time 07:12 Sent To  
Notes
2004-11-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) AIR CHAMBERS ARE NOT APPROVED.
 DELETE
 FROM WATER RISER DIAGRAM. WATER HAMMER
 ARRESTORS REQUIRED BY SECTION 604.9
 SHALL BE LOCATED NEAR THE FIXTURE NOT
 IN
 THE CEILING. PDI-WH 201 AND MANUF.
 INSTALLATION INSTRUCTIONS.
 2) REMOVE ALL VOIDED SHEETS AND SUBMIT 2
 SETS OF PLANS FOR REVIEW. SUBMIT 1
 VOIDED SET OF SHEETS SEPARATELY FOR
 COMPAIRISON. SECTION 104.2.1
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-11-01 Cont ID  
Sent By kstevens Date 2004-11-01 Time 14:12 Rev Time 0.75
Received By kstevens Date 2004-11-01 Time 14:02 Sent To  
Notes
2004-11-01 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT P-1 WATER RISER DIAGRAM. THE
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE
 RANGE" NOT IN THE CEILING AS SHOWN.
 PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved