Plan Review Details - Permit 04100184
Plan Review Stops For Permit 04100184
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2005-10-11 Cont ID  
Sent By jgomez Date 2005-10-11 Time 18:31 Rev Time 0.33
Received By jgomez Date 2005-10-11 Time 18:31 Sent To PC
Notes
2005-10-11 00:00:00SHUTTERS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2005-10-06 Cont ID  
Sent By jgomez Date 2005-10-06 Time 13:52 Rev Time 0.33
Received By jgomez Date 2005-10-06 Time 13:52 Sent To PC
Notes
2005-10-06 00:00:00BUILDING SUBMITTAL CHECKLIST:
 1- STORM SHUTTERS KEY PLAN SHOWS THAT
 EMERGENCY EGRESS DOOR IS LOCATED IN THE
 GARAGE. THIS IS NOT ALLOWED BY SECTION
 1005.4.5 FBC 2001. NEED TO PROVIDE
 EMERGENCY EGRESS THAT SATISFY CODE
 SECTION CITED ABOVE. REVISE INSTALLATION
 SCHEDULE AND KEY PLAN AS REQUIRED.
  
 2- HAND WRITTEN NOTES ON SHEET 5 OF 7 OF
 SHUTTERS DRAWINGS DON'T MATCH DIMENSIONS
 SHOWN ON THE INSTALLATION SCHEDULE.
 REVISE AS REQUIRED.
  
 3- CONTRACTOR NEEDS TO UPDATE THE
 LICENSE AND WORKERS COMPENSATION WITH
 THE CLERKS AT THE FRONT COUNTER.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-09-27 Cont ID  
Sent By jgomez Date 2005-09-27 Time 10:34 Rev Time 0.33
Received By jgomez Date 2005-09-27 Time 10:34 Sent To PC
Notes
2005-09-27 00:00:00BUILDING REVIEW SUBMITTAL CHECKLIST:
 1- ENERGY CALCULATIONS AND ELECTRICAL
 DRAWING WERE REVISED. OWES $70.00 FOR
 REVISION FEES.
  
 2- PROVIDE FLORIDA PRODUCT APPROVAL FOR
 GARAGE DOORS WITH SAME REPORT AND DWGS
 SUBMITTED TO FLORIDA BUILDING COMMISSION
 FOR APPROVAL.
  
 3- A) PROVIDE FLORIDA PRODUCT APPROVAL
 FOR STORM SHUTTERS WITH SAME DRAWINGS
 SUBMITTED TO FLORIDA BUILDING COMMISSION
 FOR APPROVAL.
  
 B) PROVIDE KEY PLAND AND COMPLETE
 INSTALLATION SCHEDULE (SEE ATTACHED
 SAMPLE).
  
 C) CLEARLY MARK ON SHUTTERS DRAWINGS
 SPECIFIC MOUNTING CONDITIONS AND ANCHOR
 TYPE AND SPACING TO BE USED ACCORDING TO
 THE DESIGN PRESSURES, EDGE DISTANCE,
 PANEL SPAN, CONNECTION TYPE AND
 STRUCTURE TO BE ATTACHED TO (CONCRETE OR
 CONCRETE BLOCK).
  
 4- CONTRACTOR NEEDS TO UPDATE WORKERS
 COMPENSATION INSURANCE. EXPIRED 9-24-05.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-08-29 Cont ID  
Sent By jgomez Date 2005-08-29 Time 14:19 Rev Time 0.33
Received By jgomez Date 2005-08-29 Time 14:19 Sent To  
Notes
2005-08-29 00:00:00RE-STAMP PLANS. SET STOLEN FROM JOBSITE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-12-13 Cont ID  
Sent By jgomez Date 2004-12-13 Time 15:48 Rev Time 2.50
Received By jgomez Date 2004-12-13 Time 15:48 Sent To PC
Notes
2004-12-13 00:00:00BUILDING REVIEW PROVISO:
 1-SPECIFY ON PLANS SIZE OF CEILING
 FANS SINCE CREDIT WAS TAKEN ON THE
 ENERGY CALCULATIONS FOR CEILING FANS.
 SEE TABLE 6-6 CHAPTER 13 FBC 2001.
  
 2-PROVIDE FLORIDA PRODUCT APPROVAL FOR
 GARAGE DOORS WITH SAME REPORT & DWGS
 SUBMITTED TO FLORIDA BUILDING
 COMMISSION FOR REVIEW AND APPROVAL.
  
 3-PROVIDE FLORIDA PRODUCT APPROVAL FOR
 STORM SHUTTERS WITH SAME DRAWINGS THAT
 WERE SUBMITTED TO FLORIDA BUILDING
 COMMISSION FOR REVIEW AND APPROVAL.
 **ALSO, CLEARLY INDICATE ON SHUTTER
 DWGS SPECIFIC MOUNTING CONDITIONS AND
 ANCHOR TYPE AND SPACING TO BE USED
 ACCORDING TO THE DESIGN PRESSURES, EDGE
 DISTANCE, PANEL SPAN, CONNECTION TYPE
 AND STRUCTURE TO BE ATTACHED TO (MASONRY
 OR CONCRETE).
  
 4-FLOOD ZONE A7: NEED TO PROVIDE THE
 ELEVATION CERTIFICATE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-11-10 Cont ID  
Sent By jgomez Date 2004-11-10 Time 16:29 Rev Time 0.00
Received By btrobaug Date 2004-11-30 Time 11:39 Sent To PC
Notes
2004-11-10 00:00:00CHECKLIST:
 1-HOUSE IS LOCATED ON FLOOD ZONE A7.
 REVISE SURVEY AS REQUIRED.
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-BRING DWGS TO PALM BEACH COUNTY TO
 VERIFY IF IMPACT FEES ARE DUE OR IF
 CREDIT IS DUE. BRING BACK STAMPED DWGS
 AND COPY OF PAID RECEIPT.
 4-SPECIFY JOINTS IN CONCRETE SLAB OR
 SPECIFY WWM SUPPORTS AND SPACING AS
 REQUIRED BY SEC. 1909.3 FBC 2001.
 5-UPDATE ALL REFERENCE STANDARDS ON
 GENERAL NOTES. SEE CHAPTER 35 FBC 2001
 FOR PROPER EDITION (YEAR) OF STANDARDS
 TO BE REFERENCED.
 6-SPECIFY MASONRY OPENING FOR SINGLE
 HUNG WINDOWS 34E TO VERIFY COMPLIANCE
 WITH SEC. 1005.4.4 FBC 2001 FOR WINDOW
 CLEAR HEIGHT OPENING.
 7-WHEN CREDIT FOR CEILING FANS IS TAKEN
 ON THE ENERGY CALCS, THEN, NEED TO
 SPECIFY SIZE OF FAN. SEE TABLE 6-6 ON
 CHAPTER 13 FBC 2001.
 8-REVISE ENERGY CALCULATIONS. THERE IS
 NOT EXTERIOR FRAMED WALL BUT ADJACENT
 FRAMED WALL.
 9-PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR: A)SINGLE HUNG WINDOWS:
 FLORIDA PRODUCT APPROVAL NUMBER DOESN'T
 MATCH.
 B)GARAGE DOOR WITH SIZE OF DOOR AS SHOWN
 ON PLANS. ALSO, FLORIDA NUMBER DOESN'T
 MATCH.
 C)ENTRY DOOR AS SHOWN ON PLANS.
 D)EXTERIOR FRENCH DOORS WITH APPROVED
 FLORIDA BUILDING COMMISSION STATUTES.
 PENDING STATUS IS NOT ACEPTABLE.
  
 10-PROVIDE COMPLETE INFORMATION FOR
 STORM SHUTTERS. NEED FLORIDA OR LOCAL
 PRODUCT APPROVAL ALONG WITH KEY PLAN AND
 COMPLETE INSTALLATION SCHEDULE. SEE
 ATTACHED SAMPLE. ALSO. INDICATE ON
 DRAWINGS SPECIFIC ANCHOR TYPE AND
 SPACING TO BE USED ACCORDING TO DESIGN
 PRESSURES, PANEL SPAN, EDGE DISTANCE,
 CONNECTOR TYPE AND STRUCTURE TO BE
 ATTACHED TO (MASONRY OR WOOD)
 11-PROVIDE COMPLETE SPECIFICATIONS FOR
 ROOF ASSEMBLIES INCLUDING FASTENERS AS
 REQUIRED BY SEC. 104.2.1.1 OF CITY
 AMENDMENTS TO FBC 2001.
 12-DECLARED VALUE WAS TOO LOW. IT WAS
 UPDATED TO $146,892. THEREFORE,
 ADDITIONAL FEES WILL BE ASSESSED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-10-13 Cont ID  
Sent By btrobaug Date 2005-10-13 Time 13:38 Rev Time 0.50
Received By btrobaug Date 2005-10-13 Time 13:29 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-10-07 Cont ID  
Sent By btrobaug Date 2005-10-07 Time 16:51 Rev Time 0.50
Received By btrobaug Date 2005-10-06 Time 17:09 Sent To PC
Notes
2005-10-07 00:00:00 
 THE REVISED PLANS SUBMITTED DO NOT
 CONTAIN ALL THE PREVIOUS REVISIONS THAT
 WERE APPROVED.
 THE PLANS MUST CORRELATE WITH THE ACTUAL
 WORK INSTALLED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-09-23 Cont ID  
Sent By btrobaug Date 2005-09-23 Time 16:26 Rev Time 0.50
Received By btrobaug Date 2005-09-22 Time 16:41 Sent To B
Notes
2005-09-23 00:00:00 
 60.00 REVISION FEE OWED

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-11-30 Cont ID  
Sent By btrobaug Date 2004-11-30 Time 12:24 Rev Time 0.50
Received By btrobaug Date 2004-11-30 Time 11:39 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-10-21 Cont ID  
Sent By btrobaug Date 2004-10-21 Time 15:55 Rev Time 0.50
Received By btrobaug Date 2004-10-21 Time 15:25 Sent To M
Notes
2004-10-21 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE NOTE THE BATH CIRCUITS ON THE
 PANEL SCHEDULE MUST COMPLY WITH
 210.11(C)(3), 20AMP #12 WIRE.
  
 2} SPACING OF THE BATH RECEPTACLES MUST
 COMPLY WITH 210.52(D). SEE MASTER BATH.
  
 3} PLEASE CHECK KITCHEN RECEPTACLE
 SPACING. MUST COMPLY WITH 210.52(C).
  
 4} PLEASE CHECK ALL RECEPTACLE SPACING
 FOR COMPLIANCE WITH 210.52 (A). SEE
 MASTER BEDROOM WALL ADJACENT TO DOOR.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-10-13 Cont ID  
Sent By adarroug Date 2005-10-13 Time 11:10 Rev Time 0.00
Received By adarroug Date 2005-10-13 Time 11:10 Sent To E
Notes
2005-10-13 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-10-11 Cont ID  
Sent By adarroug Date 2005-10-11 Time 13:32 Rev Time 0.00
Received By adarroug Date 2005-10-11 Time 13:32 Sent To B
Notes
2005-10-11 00:00:00TO "JGOMEZ" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-10-04 Cont ID  
Sent By adarroug Date 2005-10-04 Time 16:40 Rev Time 0.00
Received By adarroug Date 2005-10-04 Time 16:40 Sent To B
Notes
2005-10-04 00:00:00TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-10-04 Cont ID  
Sent By adarroug Date 2005-10-04 Time 16:36 Rev Time 0.00
Received By adarroug Date 2005-10-04 Time 16:36 Sent To E
Notes
2005-10-04 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-09-20 Cont ID  
Sent By adarroug Date 2005-09-20 Time 11:29 Rev Time 0.00
Received By adarroug Date 2005-09-20 Time 11:29 Sent To E
Notes
2005-09-20 00:00:00TO "BTROBAUG" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-08-29 Cont ID  
Sent By adarroug Date 2005-08-29 Time 13:14 Rev Time 0.00
Received By adarroug Date 2005-08-29 Time 13:14 Sent To B
Notes
2005-08-29 00:00:00TO "JGOMEZ" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-11-24 Cont ID  
Sent By mjacobs Date 2004-11-24 Time 13:35 Rev Time 0.00
Received By mjacobs Date 2004-11-24 Time 13:35 Sent To E
Notes
2004-11-24 00:00:00SENT TO "BT" DESK/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-11-10 Cont ID  
Sent By mmclean Date 2004-10-19 Time 18:48 Rev Time 0.00
Received By jgomez Date 2004-10-06 Time 14:24 Sent To PC
Notes
2004-10-20 00:00:00TO SFD RACK/E
2004-10-06 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-09-15 Cont ID  
Sent By fgodard Date 2005-09-15 Time 14:50 Rev Time 0.30
Received By fgodard Date 2005-09-15 Time 14:50 Sent To  
Notes
2005-09-15 00:00:00CHANGE IN EQUIPMENT MANUFACTURER
 ONLY/SAME TONNAGE AND SEER.OKAY PER
 PATTY KRAUSS

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2004-12-04 Time   Rev Time 0.00
Received By   Date 2004-12-04 Time   Sent To B
Notes
2004-12-04 00:00:00PRIVISO
 MARK DUCT SIZE ON PLAN BEFOR ROUGH
 INSPECTION (MARKED ON PLAN)
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status   Date   Cont ID  
Sent By btrobaug Date 2004-11-30 Time 12:24 Rev Time 0.00
Received By hmoser Date 2004-11-02 Time 13:38 Sent To  
Notes
2004-11-02 00:00:00PLAN DENIED
  
 1) NO SIZE ON RETURN AIR CAN,NO DUCT
 SIZE ON RETURN AIR DUCT,IT IS VERRY HARD
 TO READ PLANS WITH DOTED LINES.PLAN
 REVIEW BY HAROLD MOSER (561)805-6732

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-11-04 Cont ID  
Sent By kstevens Date 2004-11-04 Time 17:52 Rev Time 0.33
Received By kstevens Date 2004-11-04 Time 17:52 Sent To B1
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2004-12-13 Cont ID  
Sent By mmclean Date 2004-12-13 Time 16:37 Rev Time 0.00
Received By mmclean Date 2004-12-13 Time 16:35 Sent To B
Notes
2004-12-13 00:00:00RESTAMP NEW SURVEY.

Review Stop Z ZONING
Rev No 1 Status P Date 2004-10-19 Cont ID  
Sent By mmclean Date 2004-10-19 Time 18:48 Rev Time 0.00
Received By mmclean Date 2004-10-19 Time 18:48 Sent To I
Notes
***NONE***