Plan Review Details - Permit 04100178
Plan Review Stops For Permit 04100178
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-10-26 Cont ID  
Sent By rbrown Date 2004-10-26 Time 14:28 Rev Time 0.00
Received By rbrown Date 2004-10-26 Time 14:28 Sent To  
Notes
2004-10-26 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) WORKING DRAWING REVIEW ONLY.NO
 PERMIT CAN BE ISSUED UNTIL THE PERMIT
 APPLICATION AND FEES ARE SUBMITTED.
  
 2) 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 3) 481.213 F.S.ARCHITECT'S LICENSE.A
 SEARCH ON THE DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION WEBSITE SHOWED
 THAT DAVID SER'S ARCHITECT'S LICENSE
 (AR0014739) IS DELINQUENT.NO PERMIT
 CAN BE ISSUED FOR THESE PLANS UNTIL THIS
 IS RECTIFIED.
  
 4) FBC 603STRUCTURAL MEMBERS IN TYPE I
 CONSTRUCTION.SHEETS A-3 AND A-4 SHOW
 WOOD 'LOFT' FLOOR AND STAIR TREAD
 CONSTRUCTION.ALL STRUCTURAL MEMBERS
 SHALL BE OF NON-COMBUSTIBLE MATERIALS.
 AMEND THE PLANS.
  
 5) FBC 104.2.1THE PLANS SHALL DETAIL
 (OR STATE "SUBMIT SHOP DRAWINGS" FOR)
 THE MEANS OF ATTACHMENT FOR THE TEMPERED
 GLASS BALUSTRADE, THE CONNECTION BETWEEN
 EACH STAIR TREAD AND IT'S WIRE HANGERS,
 MEANS OF ATTACHMENT FOR THE HANDRAIL.
 SEE ALSO, COMMENT 4 ABOVE.
  
 6) FBC 1608.2.2THE GUARDRAIL SHALL BE
 DESIGNED AND CONSTRUCTED FOR A
 CONCENTRATED LOAD OF 200 LB APPLIED IN
 ANY DIRECTION AT THE TOP OF THE
 GUARDRAIL, A CONCENTRATED HORIZONTAL
 LOAD OF 200 LB APPLIED ON A 1 SQ FT AREA
 AT ANY POINT, AND A LINE LOAD OF 50 PLF
 APPLIED HORIZONTALLY AT THE REQUIRED
 GUARDRAIL HEIGHT WITH A SIMULTANEOUS
 LINE LOAD OF 100 PLF APPLIED VERTICALLY
 DOWNWARD ON THE TOP OF THE GUARDRAIL.
 THESE LOADS SHALL NOT BE APPLIED
 SIMULTANEOUSLY (UNLESS NOTED ABOVE) BUT
 SHALL BE APPLIED INDIVIDUALLY TO PRODUCE
 MAXIMUM STRESS IN EACH OF THE COMPONENTS
 OR SUPPORTS.AMEND/ANNOTATE THE PLANS.
  
 7) FBC 1608.2.1THE HANDRAIL SHALL BE
 DESIGNED AND CONSTRUCTED FOR A
 CONCENTRATED LOAD OF 200 LB AND A LINE
 LOAD OF 50 PLF.THESE LOADS SHALL NOT
 BE APPLIED SIMULTANEOUSLY BUT SHALL BE
 APPLIED INDIVIDUALLY AT ANY POINT, AND
 IN ANY DIRECTION, TO PRODUCE MAXIMUM
 STRESS IN EACH OF THE COMPONENTS OR
 SUPPORTS.AMEND/ANNOTATE THE PLANS.
  
 8) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS, TO FORM A SET OF
 'OLD/VOID SHEETS', FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-10-08 Cont ID  
Sent By dpalmer Date 2004-10-08 Time 07:19 Rev Time 0.33
Received By dpalmer Date 2004-10-08 Time 07:19 Sent To  
Notes
2004-10-08 00:00:00******* UNSAT ********
  
 **PLANS ONLY IN FOR "PLAN REVIEW"****
  
 1)NOTE: PLEASE SEE A NEW WATERFALL
 DETAIL IS SHOWN ON A-SHEETSYET THIS
 DOES NOT APPEAR ON ELECTRICAL PLANS??
 PLEASE SUBMIT INFORMATION FOR NEW PUMP,
 CONNECTION ETC.
  
 2)NOTE: PLEASE SEE 210.52C3-5 FOR RECEPT
 'S ALONG PENINSULAR COUNTERSPACE.
  
 3)NOTE: PLEASE SEE 210.52 FOR NEW LOFT
 AREA AND WALL ADJACENT TO NEW LOFT.
 PLEASE INDICATE CIRCUITS/ PANEL.
  
 4)NOTE: PLEASE SEE NOTE # 27 MENTIONS
 ROMEX PERMITTED BY OWNER OR ARCH.
 PLEASE SEE 2002 NEC 334.12. ROMEX NMC
 IS NOT PERMITTED IN THIS BLDG DUE TO
 TYPE 1 AND TYPE 2 CONSTRUCTION.
  
 5)NOTE: PLEASE SEE NOTE #28 MENTIONS
 SD'S TO WIRED TO KITCHEN/BATH CIRCUITS.
 PLEASE SEE 2002 210.12, THIS WOULD
 REQUIRE ARC FAULT ON THOSE CIRCUITS ALSO
 PLEASE SEE NFPA-72 8-1.4.6.1.2 FOR
 POSSIBLE SD REQUIRED IN LOFT AREA.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-11-05 Cont ID  
Sent By mcarsill Date 2004-11-05 Time 10:27 Rev Time 0.00
Received By mcarsill Date 2004-11-05 Time 10:27 Sent To  
Notes
2004-11-05 00:00:001) PROVIDE SEPARATE PLANS AND PERMITS
 FOR FIRE SPRINKLER REMODEL.
  
 2) SMOKE DETECTORS ARE MISSING ON MEP 1
  
 PAGE. SMOKE DETECTORS ARE REQUIRED ON
 EVERY LEVEL AND INSIDE AND OUTSIDE
 OF EACH SLEEPING ROOM.
  
 3) NO HANDRAILS DISPLAYED FOR THE
 THREE STAIR TREADS.
  
 4) PLEASE PROVIDE PRESCRIPTIVE
 STRENGTH REQUIREMENTS FOR HANDRAIL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By csiegber Date 2004-10-06 Time 10:00 Sent To  
Notes
2004-10-06 00:00:00TO COMM BD#34

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-11-15 Cont ID  
Sent By pkrauss Date 2004-11-15 Time 10:53 Rev Time 0.20
Received By pkrauss Date 2004-11-15 Time 10:53 Sent To  
Notes
2004-11-15 00:00:00NO MECHANICAL WORK INDICATED ON PLANS.
 PLEASE PROVIDE PLANS INDICATING ANY NEW
 DUCTWORK OR NEW A/C EQUIPMENT WITH THE
 MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS @ (561)805-6719.

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-10-25 Cont ID  
Sent By kstevens Date 2004-10-25 Time 16:17 Rev Time 1.00
Received By kstevens Date 2004-10-25 Time 16:16 Sent To  
Notes
2004-10-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SUBMIT A SANITARY RISER DIAGRAM SHOW-
 ING EXISTING RISER FOR LAV. SHOW HOW THE
 RISER FOR THE LAV IS BEING REROUTED. -
 SHOW HOW LAV WILL BE CONNECTED INTO THE
 EXISTING SANITARY. SECTIONS 104.2.1 AND
 104.3.1.1
 2) INDICATE DIMENSIONS OF POWDER ROOM.
 3) SHT MEP-2 PLUMBING NOTES:
 #5 AIR CHAMBERS ARE NOT APPROVED. DELE-
 TE FROM REFERENCE. SECTION 604.9
 #6 2-1/2" PIPE AND SMALLER SHAL SLOPE
 1/4" PER FOOT. TABLE 704.1 - CORRECT
 THE NOTE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***