Plan Review Details - Permit 04100155
Plan Review Stops For Permit 04100155
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-02-02 Cont ID  
Sent By mjacobs Date 2005-02-02 Time 14:36 Rev Time 0.00
Received By mjacobs Date 2005-02-02 Time 14:36 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-01-12 Cont ID  
Sent By mjacobs Date 2005-01-12 Time 07:39 Rev Time 0.00
Received By mjacobs Date 2005-01-12 Time 07:39 Sent To PC
Notes
2005-01-12 00:00:00BUILDING PLAN REVIEW
 PERMIT:04100155
 ADD:1319 DOUGLAS AVE
 CONT:BETTER BUILDERS&RENOVATIONS
 TEL: (561)795-0660
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW #3
 ACTION:DENIED
  
 1)ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SINGNAATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
 PLEASE SEE F.B.C. SEC.104.2.1
  
  
  
 BUILDING PLAN REVIEW
 MYRON JACOBS
 TEL: (561)805-6726
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-12-10 Cont ID  
Sent By mjacobs Date 2004-12-10 Time 16:15 Rev Time 0.50
Received By mjacobs Date 2004-12-10 Time 16:15 Sent To E
Notes
2004-12-10 00:00:00SENT TO "BT" DESK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-11-09 Cont ID  
Sent By mjacobs Date 2004-11-09 Time 07:55 Rev Time 1.00
Received By mjacobs Date 2004-11-09 Time 07:55 Sent To  
Notes
2004-11-09 00:00:00BUILDING PLAN REVIEW
 PERMIT:04100155
 ADD:1319 DOUGLASS AVE
 CONT:BETTER BUILDERS & RENEVATORS, INC
 TEL: (561)795-0660
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
 1STREVIEW
 ACTION:DENIED
  
 1 ) 713.13 F.S.A NOTICE OF
 COMMENCEMENT SHALL BE RECORDED AT PALM
 BEACH COUNTY COURTHOUSE AND A COPY
 SUBMITTED TO THIS OFFICE BEFORE A
 PERMIT
 CAN BE ISSUED. BLANK FORMS ARE
 AVAILABLE
 FROM THIS OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST
 BE
 RE-RECORDED IF THE DESCRIBED
 IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2)PLEASE SUBMIT MORE INFORMATION ON
 RAILINGS TO BE REPLACE. A DRAWING
 SHOWING WHERE THE RAILINGS ARE WILL BE
 VERY HELPFUL.ARE THEY INSIDE OR
 OUTSIDE?
 PLEASE SEE F.B.C.SEC.1007.5
  
  
 BUILDING PLAN REVIEW
 MYRON JACOBS
 TEL: (561)805-6726
 FAX: (561)659-8026
  
  
  
 1 ) 713.13 F.S.A NOTICE OF
 COMMENCEMENT SHALL BE RECORDED AT PALM
 BEACH COUNTY COURTHOUSE AND A COPY
 SUBMITTED TO THIS OFFICE BEFORE A PERMIT
 CAN BE ISSUED. BLANK FORMS ARE AVAILABLE
 FROM THIS OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-02-02 Cont ID  
Sent By btrobaug Date 2005-02-02 Time 15:11 Rev Time 0.50
Received By btrobaug Date 2005-01-28 Time 13:22 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-01-11 Cont ID  
Sent By btrobaug Date 2005-01-11 Time 14:34 Rev Time 0.50
Received By btrobaug Date 2005-01-11 Time 13:19 Sent To B
Notes
2005-01-11 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} INDICATE THE SIZE AND TYPE OF THE
 CONDUIT AND CONDUCTORS IN THE
 "EXISTING"
 RISER.
  
 2} FURNISH A LOAD CALCULATION FOR THE
 HOUSE PANEL, ADD SAME TO UNIT CALCS.
  
 3} THE DESIGNER OF RECORD MUST PRINT AND
 SIGN THE PLANS PER 104.2.1 FBC. THIS
 COMMENT WAS ON THE PEVIOUS REVIEW. IF
 THERE ARE QUESTIONS PLEASE CALL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-12-21 Cont ID  
Sent By btrobaug Date 2004-12-21 Time 09:23 Rev Time 0.75
Received By btrobaug Date 2004-12-21 Time 08:28 Sent To  
Notes
2004-12-21 00:00:00 
 HAND DRAWN CHANGES TO THE PLAN ARE
 UNACCEPTABLE. THE PLANS CAN ONLY BE
 REVISED BY THE DESIGNER OF RECORD AND
 SHALL CONTAIN THE PRINTED NAME AND
 SIGNATURE OF SAME PER FBC 104.2.1.
  
 REMOVE ALL DIAGRAMS FROM THE PLAN THAT
 ARE NOT TO BE USED. ALSO THE TERM
 "OPTIONAL "REFERENCING THE GUTTER IS
 NOTACCEPTABLE. IF IT IS NOT TO BE
 INSTALLEDREMOVE IT FROM THE PLAN. SEE
 AN
 ELECTRICAL CONTRACTOR OR ENGINEER IF
 UNCLEAR ON SETTING UP THE SERVICE.
  
 INDICATE WHICH ARTICLES ARE BEING USED
 FOR CALCULATIONS. SEE 220.32.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-11-05 Cont ID  
Sent By csiegber Date 2004-11-05 Time 14:24 Rev Time 0.00
Received By btrobaug Date 2004-11-05 Time 18:25 Sent To B
Notes
2004-11-05 00:00:00PROVIDE PLANS INDICATING SCOPE OF WORK
 BEING DONE PER 104.2.1 FBC.AND 215.5
 NEC
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-01-28 Cont ID  
Sent By mjacobs Date 2005-01-28 Time 12:02 Rev Time 0.00
Received By mjacobs Date 2005-01-28 Time 12:02 Sent To E
Notes
2005-01-28 00:00:00TO "BT" DESK/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-01-03 Cont ID  
Sent By mjacobs Date 2005-01-03 Time 14:25 Rev Time 0.00
Received By mjacobs Date 2005-01-03 Time 14:25 Sent To E
Notes
2005-01-03 00:00:00TO "BT" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-12-10 Cont ID  
Sent By mjacobs Date 2004-12-10 Time 16:16 Rev Time 0.00
Received By mjacobs Date 2004-12-10 Time 16:16 Sent To E
Notes
2004-12-10 00:00:00SENT TO "BT" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-10-28 Cont ID  
Sent By csiegber Date 2004-10-28 Time 14:24 Rev Time 0.00
Received By csiegber Date 2004-10-28 Time 14:24 Sent To E
Notes
***NONE***