| 2004-11-01 00:00:00 | CHECKLIST: |
| | 1-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 2-PROVIDE ENERGY CALCULATIONS AS REQ'D |
| | BY CHAPTER 13 FBC 2001. |
| | 3-PROVIDE SOIL TEST REPORT. |
| | 4-SPECIFY CONCRETE SLAB JOINTS AS REQ'D |
| | BY SEC. 1909.3 FBC 2001. |
| | 5-SPECIFY SIZE OF ATTIC ACCESS @ 1ST & |
| | 2ND FLOOR. SEC. 2309.6 FBC 2001. |
| | 6-FLOOR PLANS NEED TO SHOW ALL INTERIOR |
| | |
| | DIMENSIONS. PLANS SUBMITTED HAVE NO |
| | INTERIOR DIMENSIONS. SEC. 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |
| | 7-1ST FLOOR PLAN SHOWS STAIRS WITH |
| | WINDERS, AND 2ND FLOOR PLAN DOESN'T. |
| | CLARIFY AND SEC. SEC. 1007.8 FBC FOR |
| | WINDERS REQUIREMENTS. |
| | 8-STAIR DETAIL ON SHEET A-3 DOESN'T |
| | MATCH FLOOR PLANS. A)REVISE NUMBER OF |
| | TREADS & RISERS. |
| | B)SHOW RAILING LOCATION. |
| | C)SHOW FIREBLOCKING AS REQUIRED BY SEC. |
| | 2305.1.4 FBC 2001. |
| | D)REVISE NOTE REGARDING PICKETS |
| | SPACING. |
| | 9-EGRESS WINDOWS ON BEDROOMS #2,3, AND |
| | 4 |
| | DON'T COMPLY WITH SEC. 1005.4.3 AND |
| | SEC. 1005.4.4 FBC 2001. |
| | **ALSO, WINDOWS SHOWN ON EXTERIOR |
| | ELEVA- |
| | TIONS ARE NOT DRAWN TO SCALE. REVISE. |
| | 10-PASSING THRU LAUNDRY ROOM TO GO TO |
| | BEDROOM #2 IS NOT ALLOWED. SECTION |
| | 1001.1.3 FBC 2001. REVISE AS REQ'D. |
| | 11-SHEET A4: GARAGE DOOR SIZE SPECIFIED |
| | ON DESIGN PRESSURES CHART DOESN'T |
| | MATCH DOOR SHOWN ON ELEVATIONS. |
| | REVISE |
| | B)ADDITION NOTES DON'T APPLY. |
| | 12-SHEET A6: A)FOOTING SIZE SHOWN ON |
| | FOUNDATION PLAN AND DETAIL F2 DON'T |
| | MATCH. REVISE AS REQUIRED. |
| | B)PROVIDE COMPLETE SECTION DETAIL THRU |
| | ENTRY COLUMNS SHOWING TRANSITION FROM |
| | SQUARE TO ROUND COLUMN. SEC. |
| | 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |
| | C)REVISE COLUMN BETWEEN FRENCH DOORS AT |
| | MASTER BEDROOM. SPECS CALL FOR POURED |
| | CONCRETE COLUMN, BUT DRAWING SHOWS |
| | CONCRETE BLOCK. REVISE AS REQUIRED. |
| | D)REVISE SIZE OF FOOTING F1 AT GARAGE |
| | AREA TO MATCH SIZE SHOWN ON DETAIL |
| | F1. |
| | 13-PROVIDE COMPLETE SHEARWALL DETAILS & |
| | CLARIFY WHY IS ONLY A SHEARWALL ON ONE |
| | SIDE OF THE HOUSE ONLY @ 1ST FLOOR? |
| | PLANS DON'T IDENTIFY ALL SHEARWALL |
| | SEGMENTS ON 2ND FLOOR AS SPECIFIED ON |
| | DETAIL J OF SHEET A-10. |
| | |
| | 14-SPECIFY BEAMS AT FRONT PORCH. INFO. |
| | MISSING ON SHEET A-6. |
| | 15-PROVIDE COMPLETE DETAILS/SPECS FOR |
| | CEILING INSTALLATION AT FRONT & BACK |
| | PORCHES. SEC. 2504.2 FBC 2001 AND |
| | ASTM C926 AND ASTM C1063. |
| | 16-SHEET A7: A)SPECIFY SIZE OF ROOF VENT |
| | |
| | AT 2ND FLOOR. |
| | B)SPECIFY MIN. THICKNESS OF STUCCO AS |
| | REQUIRED BY ASTM C-926. (PROVIDE |
| | SPECS |
| | ON ALL APPLICABLE FRAMING DETAILS) |
| | C)SEE COMMENTS ON PLANS. |
| | 17-PROVIDE SMOKE DETECTORS AT 1ST & 2ND |
| | LEVEL. SEC. 905.2.2 FBC 2001. |
| | 18-SHEET A-10: A)DETAIL J DOESN'T MATCH |
| | |
| | PLANS. REVISE AS REQUIRED. |
| | 19-UPDATE TRUSS ANCHOR SCHEDULE. USE |
| | LATEST SIMPSON OR USP CATALOGUE THAT |
| | WAS REVISED TO COMPLY WITH SECTION |
| | 1609.4.3 FBC 2001. PROVIDE |
| | ENGINEERING |
| | CALCS FOR VALUES THAT ARE DIFFERENT |
| | |
| | THAN THOSE PUBLISHED WHEN NUMBER OF |
| | FASTENERS ARE CHANGED. |
| | 20-PROVIDE COMPLETE SPECS FOR SIZE AND |
| | REINFORCING FOR RAKED BEAM AT LIVING |
| | AREA. SE. 104.2.1.2 CITY AMENDMENTS. |
| | 21-PROVIDE ONLY DETAILS THAT APPLY TO |
| | THIS PROJECT. OMIT THE REST. |
| | 22-PROVIDE COMPLETE FLORIDA OR LOCAL |
| | PRDUCT APPROVAL (2 COPIES ONLY & WITH |
| | |
| | LEGIBLE DRAWINGS) FOR: |
| | A)SINGLE HUNG WINDOWS WITH LEGIBLE |
| | DWGS. |
| | B)FIXED WINDOWS WITH LEGIBLE DRAWINGS. |
| | C)ROOF TILE. |
| | D)GLASS BLOCK |
| | E)STRUCTURAL CONNECTORS (SIMPSON/USP) |
| | F)GARAGE DOOR. |
| | G)FRENCH DOORS. |
| | H)ENTRY DOOR. |
| | |
| | 23-ENGINEER TO PROVIDE COMPLETE SPECS |
| | FOR ROOF ASSEMBLY AS REQUIRED BY SEC. |
| | 104.2.1.1 CITY AMENDMENTS TO FBC |
| | 2001. |
| | 24-PROVIDE COMPLETE INFORMATION FOR |
| | STORM SHUTTERS. INCLUDING, KEY PLAN |
| | ANC COMPLETE INSTALLATION SCHEDULE. |
| | 25-AFTER CORRECTIONS ARE DONE, PLEASE |
| | BRING PLANS TO THE HISTORIC DISTRICT |
| | FOR APPROVAL PRIOR TO SUBMITTING TO |
| | THE BUILDING DEPARTMENT. |
| | 26-SHEET A-11. SEE COMMENTS ON PLANS |
| | FOR |
| | CLARIFICATION OF COLUMNS. STEEL OR |
| | WOOD. |
| | 27-SHEET A-12: CLARIFY NUMBER OF BOLTS |
| | ON DETAIL C. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |