Plan Review Details - Permit 04100136
Plan Review Stops For Permit 04100136
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-01-28 Cont ID  
Sent By jgomez Date 2005-01-28 Time 16:51 Rev Time 3.00
Received By jgomez Date 2005-01-28 Time 16:51 Sent To PC
Notes
2005-01-28 00:00:00BUILDING APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
  
 2-PROVIDE COMPLETE FLORIDA OR LOCAL
 PRODUCT APPROVAL FOR:(NOTE: MAKE SURE
 TO GET HISTORIC APPROVAL PRIOR TO
 SUBMITTAL TO THIS OFFICE:
 A) ENTRY DOOR.
 B) MECHANICAL ROOM DOOR.
 C) GARAGE DOOR.
 D) GET HISTORICAL APPROVAL FOR
 HORIZONTAL SLIDING WINDOW.
 E) GET HISTORAL APPROVAL FOR GLASS
 BLOCK
 F) GET HISTORICAL APPROVAL FOR ROOF
 TILE
 G) WINDOW MULLIONS.
  
 3- PROVIDE 2X STRUCTURAL BUCK DETAIL FOR
 SWING DOORS AS REQUIRED BY DOOR PRODUCT
 APPROVAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-01-18 Cont ID  
Sent By jgomez Date 2005-01-18 Time 14:28 Rev Time 2.50
Received By jgomez Date 2005-01-18 Time 13:47 Sent To PC
Notes
2005-01-18 00:00:003RDCHECKLIST:
 1- ENERGY CALCULATIONS: A) OWNER/AGENT
 TO SIGN & DATE BOTTOM OF FORM. ALSO,
 PERSON WHO PREPARED THE ENERGY CALCS
 NEED TO DATE THEM AS WELL.
  
 B) REVISE UNDER ATTIC AREA. SEE SECTION
 604.1.A.1 CHAPTER 13 FBC 2001.
  
 C) COMPLETE INFORMATION ON TOP OF FORM:
 ADDRESS, OWNER, BUILDER, PERMIT OFFICE,
 ETC.
  
 2- SOIL TEST REPORT: A) RECOMMENDS 24"
 MIN. WIDTH OF FOOTING AND BOTTOM OF
 FOOTING TO BE AT LEAST 18" BELOW GRADE
 (SEE PAGE 4). PLANS SUBMITTED SPECIFIES
 18" WIDE FOOTINGS AND THEY ARE ONLY 12"
 BELOW GRADE. CLARIFY WHICH ONE HAS THE
 CORRECT SPECIFICATIONS AND REVISE AS
 REQUIRED TO MATCH. SEC. 104.2.1.2 CITY
 AMENDEMNTS TO FBC 2001.
  
 B)SOIL TEST REPORT NEED TO HAVE
 ORIGINAL
 SEAL, SIGNATURE AND DATE AS REQUIRED BY
 CHAPTER 471 FL. STATUTES WHEN
 SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS.
  
 3- PROVIDE COMPLETE FLORIDA PRODUCT
 APPROVAL (NOTE: DADE COUNTY NOA'S ARE
 NOT STATEWIDE PRODUCT APPROVALS.
 FLORIDA
 PRODUCT APPROVALS ARE) OR APPLY FOR
 LOCAL PRODUCT FOR:
 A) GLASS BLOCK.
 B) "INSWING" ENTRY DOOR.
 C) FRENCH DOORS WITH LEGIBLE DRAWINGS.
 D) SINGLE HUNG WINDOWS W/ LEGIBLE DWGS.
 E) GARAGE DOOR(NOTE: SUBMIT ONLY ONE
 DOOR TYPE. THERE WERE 2 DIFFERENT DOORS
 SUBMITTED).
 F) "OUTSWING" STEEL DOOR. (MECH. RM).
 G) ROOF TILE.
 H) SIMPSON OR USP STRUCTURAL
 CONNECTORS.
 I) HORIZONTAL SLIDING WINDOWS.
 K) WINDOW MULLIONS.
  
 4- SURVEY IS NOT VALID WITHOUT ORIGINAL
 SIGNATURE, SEAL AND DATE, WHEN
 SUBMITTING FOR PUBLIC RECORDS.
  
 5- PROVIDE COMPLETE INFORMATION FOR
 STORM SHUTTERS, INCLUDING FLORIDA OR
 LOCAL PRODUCT APPROVAL, KEY PLAN AND
 COMPLETE INSTALLATION SCHEDULE. SEE
 ATTACHED SAMPLE. OR APPLY FOR A
 SEPARATE
 PERMIT.
  
 6-PROVIDE 2X STRUCTURAL BUCK DETAIL FOR
 ENTRY AND MECHANICAL ROOM DOORS AS
 REQUIRED ON INFORMATION SUBMITTED FOR
 DOOR TO BE USED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-11-30 Cont ID  
Sent By jgomez Date 2004-11-30 Time 17:32 Rev Time 0.00
Received By jgomez Date 2004-11-30 Time 17:30 Sent To  
Notes
2004-11-30 00:00:00CHECKLIST:
 1-PROVIDE ENERGY CALCULATIONS AS REQ'D
 BY SEC. 103 CHAPTER 13 FBC 2001.
  
 2-PROVIDE SOIL TEST REPORT.
  
 3-SPECIFY SIZE OF ATTIC ACCESS ABOVE
 MASTER BEDROOM WARDROBE. SEC. 2309.6
 FBC
  
 4-FLOOR PLANS ARE MISSING A LOT OF
 DIMENSIONS. ALSO, SOME DIMENSIONS ARE
 OVERLAPPING WITH OTHER INFORMATION AND
 ARE NOT LEGIBLE.
 **THERE ARE NOT DIMENSIONS FOR MASONRY
 OPENINGS AND FOR LOCATION OF CONCRETE
 BLOCK REINFORCING COLUMNS. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 5-SPECIFY SAFETY GLASS WHERE REQUIRED
 BY
 SEC. 2405.2.1 FBC 2001. SEE PLANS.
  
 6-REVISE STAIR WINDERS TO COMPLY WITH
 SECTION 1007.8.1 FBC 2001.
  
 7-SPECIFY FIREBLOCKING AT STAIRS AS
 REQUIRED BY SEC. 2305.1.4 FBC 2001.
  
 8-ONLY 2 SETS OF DRAWINGS ARE REQUIRED.
  
 9-PROVIDE COMPLETE DETAILS/SPECS FOR
 CEILING INSTALLATION AT FRONT AND BACK
 PORCHES. SEC. 2504.2 FBC 2001 AND ASTM
 C926 AND ASTM C1063.
  
 10-UPDATE TRUSS ANCHOR SCHEDULE. USE
 LATEST USP OR SIMPSON CATALOGUE.
 PROVIDE
 COMPLETE ENGINEERING CALCULATIONS FOR
 TYPE AND NUMBER OF FASTENERS THAT ARE
 DIFFERENT FROM THOSE PUBLISHED BY THE
 MANUFACTURER. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 CLARIFY WHY ARE THERE ADDITIONAL
 FASTENERS SPECIFIED ON RIGHT HAND SIDE
 COLUMN OF TRUSS SCHEDULE.
  
 11-PROVIDE COMPLETE FLORIDA OR LOCAL
 PRODUCT APPROVAL (2 COPIES) FOR:
 A) SINGLE HUNG WINDOWS.
 B) FIXED WINDOWS WITH SIZES AND SHAPES
 AS SHOWN ON PLANS.
 C) ROOF TILE.
 D) GLASS BLOCK.
 E) STRUCTURAL CONNECTORS (USP/SIMPSON).
 F) HORIZONTAL SLIDING WINDOWS.
 G) MECHANICAL ROOM EXTERIOR DOOR.
 H) FRENCH DOORS.
 I) ENTRY DOOR.
  
 12-ENGINEER TO PROVIDE COMPLETE SPECS
 FOR ROOF ASSEMBLY, INCLUDING TILE
 FASTENING AS REQUIRED BY SEC. 104.2.1.1
 CITY AMENDMENTS TO FBC 2001.
  
 13-PROVIDE COMPLETE INFORMATION FOR
 STORM SHUTTERS INCLUDING: KEY PLAN AND
 COMPLETE INSTALLATION SCHEDULE (SEE
 SAMPLE).
 ALSO, CLEARLY MARK ON DRAWINGS SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR TYPE AND
 SPACING TO BE USED ACCORDING TO THE
 DESIGN PRESSURES, EDGE DISTANCE, PANEL
 SPAN, CONNECTION TYPE AND STRUCTURE TO
 BE ATTACHED TO (MASONRY OR CONCRETE).
  
 14-AFTER CORRECTIONS ARE DONE, PLEASE
 TAKE DRAWINGS TO THE HISTORIC DISTRICT
 FOR APPROVAL STAMPS PRIOR TO SUBMITTAL
 TO THE BUILDING DEPARTMENT TO EXPEDITE
 THE REVIEW PROCESS.
  
 15-RE-SUBMITTAL FEES WILL BE CHARGED AT
 TIME OF RE-SUBMITTAL. SEE ENCLOSED FEE
 SCHEDULE.
  
 16-DETAIL K ON SHEET A-11 IS MISSING
 INFORMATION. SEE PLANS.
  
 17-PROVIDE ONLY DETAILS/SECTIONS THAT
 APPLY TO THIS PROJECT TO EXPEDITE REVIEW
 PROCESS AND AVOID CONFUSSIONS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-11-01 Cont ID  
Sent By kstevens Date 2004-10-22 Time 09:31 Rev Time 4.00
Received By jgomez Date 2004-11-01 Time 11:23 Sent To PC
Notes
2004-11-01 00:00:00CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-PROVIDE ENERGY CALCULATIONS AS REQ'D
 BY CHAPTER 13 FBC 2001.
 3-PROVIDE SOIL TEST REPORT.
 4-SPECIFY CONCRETE SLAB JOINTS AS REQ'D
 BY SEC. 1909.3 FBC 2001.
 5-SPECIFY SIZE OF ATTIC ACCESS @ 1ST &
 2ND FLOOR. SEC. 2309.6 FBC 2001.
 6-FLOOR PLANS NEED TO SHOW ALL INTERIOR
  
 DIMENSIONS. PLANS SUBMITTED HAVE NO
 INTERIOR DIMENSIONS. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 7-1ST FLOOR PLAN SHOWS STAIRS WITH
 WINDERS, AND 2ND FLOOR PLAN DOESN'T.
 CLARIFY AND SEC. SEC. 1007.8 FBC FOR
 WINDERS REQUIREMENTS.
 8-STAIR DETAIL ON SHEET A-3 DOESN'T
 MATCH FLOOR PLANS. A)REVISE NUMBER OF
 TREADS & RISERS.
 B)SHOW RAILING LOCATION.
 C)SHOW FIREBLOCKING AS REQUIRED BY SEC.
 2305.1.4 FBC 2001.
 D)REVISE NOTE REGARDING PICKETS
 SPACING.
 9-EGRESS WINDOWS ON BEDROOMS #2,3, AND
 4
 DON'T COMPLY WITH SEC. 1005.4.3 AND
 SEC. 1005.4.4 FBC 2001.
 **ALSO, WINDOWS SHOWN ON EXTERIOR
 ELEVA-
 TIONS ARE NOT DRAWN TO SCALE. REVISE.
 10-PASSING THRU LAUNDRY ROOM TO GO TO
 BEDROOM #2 IS NOT ALLOWED. SECTION
 1001.1.3 FBC 2001. REVISE AS REQ'D.
 11-SHEET A4: GARAGE DOOR SIZE SPECIFIED
 ON DESIGN PRESSURES CHART DOESN'T
 MATCH DOOR SHOWN ON ELEVATIONS.
 REVISE
 B)ADDITION NOTES DON'T APPLY.
 12-SHEET A6: A)FOOTING SIZE SHOWN ON
 FOUNDATION PLAN AND DETAIL F2 DON'T
 MATCH. REVISE AS REQUIRED.
 B)PROVIDE COMPLETE SECTION DETAIL THRU
 ENTRY COLUMNS SHOWING TRANSITION FROM
 SQUARE TO ROUND COLUMN. SEC.
 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 C)REVISE COLUMN BETWEEN FRENCH DOORS AT
 MASTER BEDROOM. SPECS CALL FOR POURED
 CONCRETE COLUMN, BUT DRAWING SHOWS
 CONCRETE BLOCK. REVISE AS REQUIRED.
 D)REVISE SIZE OF FOOTING F1 AT GARAGE
 AREA TO MATCH SIZE SHOWN ON DETAIL
 F1.
 13-PROVIDE COMPLETE SHEARWALL DETAILS &
 CLARIFY WHY IS ONLY A SHEARWALL ON ONE
 SIDE OF THE HOUSE ONLY @ 1ST FLOOR?
 PLANS DON'T IDENTIFY ALL SHEARWALL
 SEGMENTS ON 2ND FLOOR AS SPECIFIED ON
 DETAIL J OF SHEET A-10.
  
 14-SPECIFY BEAMS AT FRONT PORCH. INFO.
 MISSING ON SHEET A-6.
 15-PROVIDE COMPLETE DETAILS/SPECS FOR
 CEILING INSTALLATION AT FRONT & BACK
 PORCHES. SEC. 2504.2 FBC 2001 AND
 ASTM C926 AND ASTM C1063.
 16-SHEET A7: A)SPECIFY SIZE OF ROOF VENT
  
 AT 2ND FLOOR.
 B)SPECIFY MIN. THICKNESS OF STUCCO AS
 REQUIRED BY ASTM C-926. (PROVIDE
 SPECS
 ON ALL APPLICABLE FRAMING DETAILS)
 C)SEE COMMENTS ON PLANS.
 17-PROVIDE SMOKE DETECTORS AT 1ST & 2ND
 LEVEL. SEC. 905.2.2 FBC 2001.
 18-SHEET A-10: A)DETAIL J DOESN'T MATCH
  
 PLANS. REVISE AS REQUIRED.
 19-UPDATE TRUSS ANCHOR SCHEDULE. USE
 LATEST SIMPSON OR USP CATALOGUE THAT
 WAS REVISED TO COMPLY WITH SECTION
 1609.4.3 FBC 2001. PROVIDE
 ENGINEERING
 CALCS FOR VALUES THAT ARE DIFFERENT
  
 THAN THOSE PUBLISHED WHEN NUMBER OF
 FASTENERS ARE CHANGED.
 20-PROVIDE COMPLETE SPECS FOR SIZE AND
 REINFORCING FOR RAKED BEAM AT LIVING
 AREA. SE. 104.2.1.2 CITY AMENDMENTS.
 21-PROVIDE ONLY DETAILS THAT APPLY TO
 THIS PROJECT. OMIT THE REST.
 22-PROVIDE COMPLETE FLORIDA OR LOCAL
 PRDUCT APPROVAL (2 COPIES ONLY & WITH
  
 LEGIBLE DRAWINGS) FOR:
 A)SINGLE HUNG WINDOWS WITH LEGIBLE
 DWGS.
 B)FIXED WINDOWS WITH LEGIBLE DRAWINGS.
 C)ROOF TILE.
 D)GLASS BLOCK
 E)STRUCTURAL CONNECTORS (SIMPSON/USP)
 F)GARAGE DOOR.
 G)FRENCH DOORS.
 H)ENTRY DOOR.
  
 23-ENGINEER TO PROVIDE COMPLETE SPECS
 FOR ROOF ASSEMBLY AS REQUIRED BY SEC.
 104.2.1.1 CITY AMENDMENTS TO FBC
 2001.
 24-PROVIDE COMPLETE INFORMATION FOR
 STORM SHUTTERS. INCLUDING, KEY PLAN
 ANC COMPLETE INSTALLATION SCHEDULE.
 25-AFTER CORRECTIONS ARE DONE, PLEASE
 BRING PLANS TO THE HISTORIC DISTRICT
 FOR APPROVAL PRIOR TO SUBMITTING TO
 THE BUILDING DEPARTMENT.
 26-SHEET A-11. SEE COMMENTS ON PLANS
 FOR
 CLARIFICATION OF COLUMNS. STEEL OR
 WOOD.
 27-SHEET A-12: CLARIFY NUMBER OF BOLTS
 ON DETAIL C.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-01-06 Cont ID  
Sent By btrobaug Date 2005-01-06 Time 13:25 Rev Time 0.50
Received By btrobaug Date 2005-01-06 Time 12:54 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2004-11-29 Cont ID  
Sent By btrobaug Date 2004-11-29 Time 15:30 Rev Time 0.00
Received By btrobaug Date 2004-11-29 Time 15:30 Sent To B
Notes
2004-11-29 00:00:00OPENED REVIEW BY MISTAKE, ALREADY DID
 2ND REVIEW./WRT

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-11-18 Cont ID  
Sent By btrobaug Date 2004-11-18 Time 17:47 Rev Time 0.75
Received By btrobaug Date 2004-11-18 Time 16:25 Sent To P
Notes
2004-11-18 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE RISER DIAGRAM SHOWS THE 100AMP
 PANEL FEEDING THE PANEL MARKED 250, THE
 PANEL SCHEDULE INDICATES THIS AS 200
 AMPS, AND NO FEED FROM EITHER PANEL TO
 THE OTHER IS SHOWN.
  
 2} BOTH PANELS ARE BOTTOM FED, PLEASE
 CLARIFY, SEE RISER.
  
 3} SHOW CONDUCTOR SIZE, CONDUIT SIZE AND
 OCP FOR THE FEED BETWEEN PANELS.
  
 4} PLEASE DRAW THE LOCATION OF THE MAIN
 DISCONNECT ON THE PLAN.
  
 5} THERE IS ONLY ONE SMALL APPLIANCE
 CIRCUIT ON THE SCHEDULE, THE CALC LISTS
 3, PLEASE CORRELATE.
  
 6} THE BATH CIRCUITS LISTED ON THE
 SCHEDULE@15 AMPS DO NOT COMPLY WITH
 210.11(C)(3),20AMP.
  
 7} A SMOKE DETECTOR IS REQUIRED AT THE
 STAIR ON THE FIRST FLOOR, SEE 905.2.2
 F.B.C..
  
 8} THE MASTER BEDROOM AND BEDROOMS #3&4
 NEED RECEPTACLES FOR SPACING
 REQUIREMENTS OF 210.52(A)(1&2).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-10-14 Cont ID  
Sent By btrobaug Date 2004-10-14 Time 10:53 Rev Time 0.75
Received By btrobaug Date 2004-10-13 Time 13:21 Sent To M
Notes
2004-10-14 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALLED. MAINS/BRKRS AND PANELS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT PER 110.9.
  
 2} THE GEC SYSTEM MUST COMPLY WITH ALL
 AVAILABLE. SEE 250.52(A)(3), FOOTER
 STEEL.
  
 3} THE RISER SHOWS 2 ELECTRIC PANELS
 BUT THERE ARE THREE ON THE DRAWING.
 PLEASE
 INCLUDE ALL PANELS ON THE RISER.
  
 4} PLEASE PROVIDE A PANEL SCHEDULE SO
 THAT BRANCH CIRCUIT COMPLIANCE MAY BE
 DETERMINED.
  
 5} PLEASE NOTE THE CALCULATION FOR SMALL
 APPLIANCE CIRCUITS MUST COMPLY WITH
 210-16(A). 1500VA EACH.
  
 6} RECEPTACLES IN THE GARAGE MUST COMPLY
 WITH 210.8(A)(2), GFI.
  
 7} SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.SEE REVIEWED SET OF PLANS FOR
 LOCATIONS IN QUESTION.NFPA-72
 8-1.4.1.6.2 AND 905.2.2 FBC.
  
 8} THE RECEPTACLE IN BATH #4 MUST BE GFI
 PER 201.8(A)(1).
  
 9} PLEASE SEE MISSING RECEPT REQUIRED
 FOR A/C EQUIPMENT 210.63.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-01-03 Cont ID  
Sent By mjacobs Date 2005-01-03 Time 14:28 Rev Time 0.00
Received By mjacobs Date 2005-01-03 Time 14:28 Sent To E
Notes
2005-01-03 00:00:00TO "BT" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-11-12 Cont ID  
Sent By csiegber Date 2004-11-12 Time 11:14 Rev Time 0.00
Received By csiegber Date 2004-11-12 Time 11:13 Sent To E
Notes
2004-11-12 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-11-01 Cont ID  
Sent By jgomez Date 2004-11-01 Time 16:29 Rev Time 0.00
Received By jgomez Date 2004-10-06 Time 10:19 Sent To PC
Notes
2004-10-13 00:00:00TO SFD RACK/E
2004-10-06 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-01-11 Cont ID  
Sent By pkrauss Date 2005-01-11 Time 16:26 Rev Time 0.30
Received By pkrauss Date 2005-01-10 Time 16:26 Sent To P
Notes
2005-01-10 00:00:00PROVISO:
 1.RETURN AIR JUMPER FROM THE MASTER
 SUITE SHALL BE A MINIMUM OF 12" PER 2001
 FBC(M)601.4 EXCEPTION #1 & 3.
  
 2.A MINIMUM OF 4" AROUND THE AHU IS
 REQUIRED PER 2001 FBC(M)603.1.3.
  
 3.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-11-23 Cont ID  
Sent By prafter Date 2004-11-23 Time 09:59 Rev Time 0.45
Received By prafter Date 2004-11-23 Time 09:58 Sent To P
Notes
2004-11-23 00:00:00PREVIOUS MECH. NOTES 10/15/04 MUST BE
 ADDRESED.PAT RAFTER11/23/04
 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-10-15 Cont ID  
Sent By btrobaug Date 2004-10-14 Time 10:53 Rev Time 0.35
Received By PKRAUSS Date 2004-10-15 Time 09:57 Sent To P
Notes
2004-10-15 00:00:00DENIED:
 ENERGY AND MANUAL J CALCULATIONS ARE
 TO BE SUBMITTED WITH THE BUILDING PERMIT
 APPLICATION.PLEASE PROVIDE PLANS WITH
 MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-01-11 Cont ID  
Sent By pschmitz Date 2005-01-11 Time 10:25 Rev Time 0.00
Received By pschmitz Date 2005-01-11 Time 10:25 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-11-24 Cont ID  
Sent By kstevens Date 2004-11-24 Time 18:43 Rev Time 0.75
Received By kstevens Date 2004-11-24 Time 18:43 Sent To E
Notes
2004-11-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUBING
 FBC-2001 CHAPTER 1
  
 1) SHT A-9 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE, NOR DOES IS REFLECT THE
 FLOOR PLAN.
 A) THE WASH MACHINE AND LAUNDRY SINK
 SHALL NOT DRAIN THROUGH THE HORIZONTAL
 WET VENT OF THE BATHROOM FIXTURES.
 SECTION 909.1
  
 SEE ATTACHED SHEET TO SEE AN EXAMPLE OF
 A RISER DIAGRAM THAT REFLECTS THE FLOOR
 PLAN AND MEETS THE CODE REQUIREMENTS.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-10-22 Cont ID  
Sent By pkrauss Date 2004-10-15 Time 07:17 Rev Time 1.00
Received By kstevens Date 2004-10-22 Time 09:31 Sent To B
Notes
2004-10-22 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
 FBC-2001 BUILDING
  
 1) SHT A-9 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, NOR DOES IT
 MEET CODE REQUIREMENTS.
 A) FIXTURES FROM DIFFERENT BATHROOMS
 AND DIFFERENT LAYOUTS, (DIFFERENT WALL),
 ARE SHOWN ON THE SAME COMMON WALL.
 B) WASH MACHINE CONNECTION NOT SHOWN.
 C) ONLY TWO W/C'S SHOWN ON RISER DIAGR-
 AM FIRST FLOOR, WHEN THREE ARE SHOWN ON
 THE FLOOR PLAN.
 D) FIRST FIXTURES ON RISER DIAGRAM ARE
 NOT LABELED. IF THOSE FIXTURES ARE THE
 KITCHEN SINK, THEY SHOULD BE CONNECTED
 TO THE BLDG. DRAIN UPSTREAM OF THE POW-
 DER ROOM.
 E) GARAGE SINK NOT SHOWN ON RISER DIAG-
 RAM.
 F) BOTH BATHROOMS ON THE FIRST FLOOR
 SHOW TWO LAVS ON THE RISER DIAGRAM, WHEN
 BATH #2 ONLY HAS ONE ON THE FLOOR PLAN.
 G) MASTER BATH SHOWER NOT SHOWN ON THE
 RISER DIAGRAM.
 H) LAV IN UPSTAIRS BATHROOM #3 IS SHOWN
 GOING OUTSIDE OF THE BLDG. AND NOT IN
 THE ROOM.
 I) SIZE ALL PIPES IN SANT. RISER DIAGR-
 AM.
 SECTION 104.2.1
 2) MAY I SUGGEST THAT YOU HAVE YOUR
 PLUMBING CONTRACTOR INDICATE HOW THE
 PLUMBING WILL BE INSTALLED AND DRAW THE
 SANITARY RISER DIAGRAM, AND THEN REDRAW
 THE RISER ON THE PLANS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2005-01-18 Cont ID  
Sent By mmclean Date 2005-01-18 Time 14:22 Rev Time 0.00
Received By mmclean Date 2005-01-18 Time 14:22 Sent To B
Notes
2005-01-18 00:00:00RESTAMP PLANS.PLANS RETURNED TO JGOMEZ

Review Stop Z ZONING
Rev No 1 Status P Date 2004-10-13 Cont ID  
Sent By nleiva Date 2004-10-13 Time 09:05 Rev Time 0.50
Received By nleiva Date   Time   Sent To  
Notes
2004-10-13 00:00:00OK SHIRLEY GRAHAM