Plan Review Details - Permit 04100134
Plan Review Stops For Permit 04100134
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-10-05 Cont ID  
Sent By csiegber Date 2004-10-05 Time 15:37 Rev Time 0.00
Received By csiegber Date 2004-10-05 Time 15:37 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-10-15 Cont ID  
Sent By csiegber Date 2004-10-05 Time 15:38 Rev Time 0.35
Received By pkrauss Date 2004-10-15 Time 13:07 Sent To  
Notes
2004-10-15 00:00:00PROVISO:
 TRANSFER GRILLES INDICATED ABOVE THE
 DOORS ARE NOT SIZED.MINIMUM OF 50 SQ
 INCHES OF FREE AREA REQUIRED PER 100 CFM
 OF SUPPLY AIR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.