Plan Review Details - Permit 04100118
| Plan Review Stops For Permit 04100118 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2004-11-03 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2004-10-29 |
Time |
15:46 |
Rev Time |
0.75 |
| Received By |
jwitmer |
Date |
2004-11-03 |
Time |
10:25 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2004-10-29 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-10-27 |
Time |
11:12 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2004-10-27 |
Time |
12:19 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-10-05 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-10-05 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-10-05 |
Time |
14:16 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2004-10-27 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-10-27 |
Time |
11:06 |
Rev Time |
1.00 |
| Received By |
pkrauss |
Date |
2004-10-27 |
Time |
11:06 |
Sent To |
E |
|
| Notes |
| 2004-10-27 00:00:00 | PROVISO: | | | FAN SHUTDOWN BY DUCT SMOKE DETECTOR WITH | | | NOTIFICATION TO ALARM/STROBE REQUIRED | | | PER 2001 FBC(M) 606.2.1 & 606.4.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2004-10-19 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-10-05 |
Time |
14:16 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2004-10-19 |
Time |
07:38 |
Sent To |
|
|
| Notes |
| 2004-10-19 00:00:00 | DENIED: | | | 1.PLEASE NOTE ALL ENGINEERED PLANS ARE | | | TO BE SIGNED, SEALED AND DATED PER FS | | | 471.025 FAC 61G15-23. | | | | | | 2.LETTER INDICATES ROOF TOP CHANGE | | | OUT WHICH CONFLICTS WITH WORK DESCRIBED | | | ON THE PERMIT APPLICATION. | | | | | | 3.IS THE NEW DUCT WORK INDICATED ON | | | THE PERMIT APPLICATION IS FOR THE | | | RECEIVING OFFICE AREA SHOWN ON THE | | | PLANS SUBMITTED.WILL THIS BE A CHANGE | | | OUT OF DUCT OR IS THE ENTIRE SYSTEM | | | INCLUDING THE UNIT NEW?PLEASE CLARIFY. | | | | | | 4.PLANS INDICATE ROOF CURBS TO BE A | | | MINIMUM OF 14".PLEASE NOTE, PER 2001 | | | FBC 1511.7, CURBS SHALL BE A MINIMUM OF | | | 8" FROM THE ROOF SURFACE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
|