| 2005-06-24 00:00:00 | DENIED |
| | |
| | 1.PERMIT APPLICATION HAS EXPIRED. |
| | OVER 180 DAYS WITH NO ACTIVITY.FBC |
| | 104.5.1.3.CONTACT NEIL MELICK BUILDING |
| | OFFICIAL TO HAVE PERMIT APPLICATION |
| | REINSTATED. 561-805-6654 |
| | |
| | 2. 713.13(2) F.S.THE NOTICE OF |
| | COMMENCEMENT MUST BE RE-RECORDED BECAUSE |
| | THE DESCRIBED IMPROVEMENT OR |
| | CONSTRUCTION DID NOT COMMENCE WITHIN 90 |
| | DAYS OF RECORDING. |
| | |
| | 3.THE BOTTOM FOOTING SHALL EXTEND NO |
| | LESS THAN 12" BELOW GRADE.FBC1804.1.3 |
| | |
| | 4.SUBMIT TWO COPIES OF TABLE 600 |
| | ENERGY CALCS. |
| | |
| | 5.SHOW LEDGER FASTENING SPACING FOR |
| | ROOF AND FLOORS. |
| | |
| | 6.MINIMUM ROOF SHEATHING THICKNESS IS |
| | 5/8" FBC 2309.3.1 |
| | |
| | 7.SHOW A ROOF SHEATHING NAILING |
| | SCHEDULE COMPLYING WITH FBC2306.1 WPB |
| | AMMENDMENTS. |
| | |
| | 8.SUBMIT 2 COPIES OF PRODUCT APPROVALS |
| | WITH QUALITY ASSURANCE FOR ROOFING, |
| | WINDOWS, IMPACT PROTECTION AND STRAPS |
| | AND TIE DOWNS. |
| | **ALL PRODUCT APPROVALS SUBMITTED SHALL |
| | HAVE THE FOLLOWING STATE APPROVALS |
| | ATTACHED** |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 9.SHOW A WALL FRAMING DETAIL AND |
| | INCLUDE STRAPING AND TIE-DOWNS, HEADERS |
| | AND SIZE.ALSO SHOW TIE-IN TO |
| | FOUNDATION. |
| | |
| | 10.SUBMIT FLOORING PLANS AND ROOF |
| | PLANS SEPERATLY.INCLUDE ALL TIE-INS |
| | USED FROM FOOTINGS UP INCLUDING ROOF |
| | FRAMING. THIS IS NEEDED FOR STEAMROOM |
| | AND FRONT PORCH. |
| | |
| | 11.NEW ROOF OVER STEAM ROOM APPEARS TO |
| | BE FLOATING WITH OUT MUCH SUPPORT. |
| | REDESIGN THIS ROOF AND INCLUDE DETAILS |
| | FOR ALL CONNECTIONS AND METHOD OF TIE-IN |
| | AND TIE-DOWN. |
| | |
| | 12.SHOW WHAT METHOD WILL BE USED FOR |
| | ROOF VENTILATION. |
| | |
| | 13. ON FRONT PORCH THE BEAM SUPPORTING |
| | JOISTS HAS NO MID SPAN SUPPORT. |
| | INCREASE BEAM SIZE OR ADD AN ADDITIONAL |
| | FOOTING. |
| | |
| | 14.SUBMIT A NEW BATHROOM PLAN. |
| | EXISTING BATHROOM IS 96" ON NEW PLAN |
| | BATHROOM IS OVER 20FT LONG. |
| | NEW PLAN ONLY SHOWS ON WALL. SHOW FLOOR |
| | PLAN. |
| | |
| | 15.SHOW HOW BEAM WILL BE TIED INTO |
| | EXISTING DECK. |
| | |
| | 16.SHOW STAIR DETAIL. FBC 1007.3 |
| | |
| | 17.VERIFY FOOTING SIZE ON ROOM |
| | ADDITION.IT APPEARS TO BE UNDERSIZED. |
| | FBC1804 |
| | |
| | 18.NOTE PLANS HAVE INSUFFICIENT |
| | INFORMATION FOR A COMPLETE REVIEW. |
| | AFTER REVIEWING RESUBMITTED PLANS |
| | ADDITIONAL CORRECTIONS MAY ARISE. |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | ART LANGE |
| | BUILDING PLANS EXAMINER |
| | 805-6672 |
| | |