Plan Review Details - Permit 04100017
Plan Review Stops For Permit 04100017
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-06-24 Cont ID  
Sent By alange Date 2005-06-24 Time 11:07 Rev Time 3.00
Received By alange Date 2005-06-24 Time 07:09 Sent To E
Notes
2005-06-24 00:00:00DENIED
  
 1.PERMIT APPLICATION HAS EXPIRED.
 OVER 180 DAYS WITH NO ACTIVITY.FBC
 104.5.1.3.CONTACT NEIL MELICK BUILDING
 OFFICIAL TO HAVE PERMIT APPLICATION
 REINSTATED. 561-805-6654
  
 2. 713.13(2) F.S.THE NOTICE OF
 COMMENCEMENT MUST BE RE-RECORDED BECAUSE
 THE DESCRIBED IMPROVEMENT OR
 CONSTRUCTION DID NOT COMMENCE WITHIN 90
 DAYS OF RECORDING.
  
 3.THE BOTTOM FOOTING SHALL EXTEND NO
 LESS THAN 12" BELOW GRADE.FBC1804.1.3
  
 4.SUBMIT TWO COPIES OF TABLE 600
 ENERGY CALCS.
  
 5.SHOW LEDGER FASTENING SPACING FOR
 ROOF AND FLOORS.
  
 6.MINIMUM ROOF SHEATHING THICKNESS IS
 5/8" FBC 2309.3.1
  
 7.SHOW A ROOF SHEATHING NAILING
 SCHEDULE COMPLYING WITH FBC2306.1 WPB
 AMMENDMENTS.
  
 8.SUBMIT 2 COPIES OF PRODUCT APPROVALS
 WITH QUALITY ASSURANCE FOR ROOFING,
 WINDOWS, IMPACT PROTECTION AND STRAPS
 AND TIE DOWNS.
 **ALL PRODUCT APPROVALS SUBMITTED SHALL
 HAVE THE FOLLOWING STATE APPROVALS
 ATTACHED**
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 9.SHOW A WALL FRAMING DETAIL AND
 INCLUDE STRAPING AND TIE-DOWNS, HEADERS
 AND SIZE.ALSO SHOW TIE-IN TO
 FOUNDATION.
  
 10.SUBMIT FLOORING PLANS AND ROOF
 PLANS SEPERATLY.INCLUDE ALL TIE-INS
 USED FROM FOOTINGS UP INCLUDING ROOF
 FRAMING. THIS IS NEEDED FOR STEAMROOM
 AND FRONT PORCH.
  
 11.NEW ROOF OVER STEAM ROOM APPEARS TO
 BE FLOATING WITH OUT MUCH SUPPORT.
 REDESIGN THIS ROOF AND INCLUDE DETAILS
 FOR ALL CONNECTIONS AND METHOD OF TIE-IN
 AND TIE-DOWN.
  
 12.SHOW WHAT METHOD WILL BE USED FOR
 ROOF VENTILATION.
  
 13. ON FRONT PORCH THE BEAM SUPPORTING
 JOISTS HAS NO MID SPAN SUPPORT.
 INCREASE BEAM SIZE OR ADD AN ADDITIONAL
 FOOTING.
  
 14.SUBMIT A NEW BATHROOM PLAN.
 EXISTING BATHROOM IS 96" ON NEW PLAN
 BATHROOM IS OVER 20FT LONG.
 NEW PLAN ONLY SHOWS ON WALL. SHOW FLOOR
 PLAN.
  
 15.SHOW HOW BEAM WILL BE TIED INTO
 EXISTING DECK.
  
 16.SHOW STAIR DETAIL. FBC 1007.3
  
 17.VERIFY FOOTING SIZE ON ROOM
 ADDITION.IT APPEARS TO BE UNDERSIZED.
 FBC1804
  
 18.NOTE PLANS HAVE INSUFFICIENT
 INFORMATION FOR A COMPLETE REVIEW.
 AFTER REVIEWING RESUBMITTED PLANS
 ADDITIONAL CORRECTIONS MAY ARISE.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-11-01 Cont ID  
Sent By btrobaug Date 2004-10-27 Time 11:05 Rev Time 0.75
Received By alange Date 2004-11-01 Time 09:42 Sent To  
Notes
2004-11-01 00:00:00 
 DENIED
  
 INCOMPLETE INFORMATION SUBMITTED FOR A
 REVIEW.
 SUBMIT TWO COPIES OF THE FOLLOWING:
 PLANS SHOWING WORK TO BE COMPLETED.
 FOR EXAMPLE INCLUDE FOOTINGS AND DEPTH.
 REINFORCEMENT USED. SLAB INFORMATION.
 WALL DETAILS. ROOF DETAILS.
 SUBMIT PRODUCT APPROVALS FOR EXTERIOR
 COMPONENTS, WINDOWS, DOORS , ROOFING
 STRAPS AND TIE-DOWNS.
  
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-06-27 Cont ID  
Sent By btrobaug Date 2005-06-27 Time 12:41 Rev Time 0.50
Received By btrobaug Date 2005-06-27 Time 12:33 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2004-10-27 Cont ID  
Sent By pkrauss Date 2004-10-27 Time 07:15 Rev Time 0.50
Received By btrobaug Date 2004-10-27 Time 11:02 Sent To  
Notes
2004-10-27 00:00:00 
 PLEASE PROVIDE ELECTRICAL FLOOR PLANS OF
 AREAS AFFECTED BY THIS
 SCOPE,INDICATING COMPLIANCE WITH
 SPACING, CIRCUITING AND GROUND FAULT
 ARTICLES OF THE 2002 NEC.
 ALSO NOTE THAT AN ELECTRICAL PERMIT IS
 REQUIRED FOR THE THIS PROJECT IF ANY
 WIRING HAS TO BE EXTENDED, MOVED OR IS
 OTHERWISE INTERFERED WITH.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-10 Cont ID  
Sent By shill Date 2005-06-10 Time 16:55 Rev Time 0.00
Received By shill Date 2005-06-10 Time 16:55 Sent To B
Notes
2005-06-10 00:00:00TO AL DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-10-20 Cont ID  
Sent By csiegber Date 2004-10-20 Time 16:28 Rev Time 0.00
Received By csiegber Date 2004-10-20 Time 16:28 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-10-04 Cont ID  
Sent By mmclean Date 2004-10-19 Time 16:08 Rev Time 0.00
Received By csiegber Date 2004-10-04 Time 10:56 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-10-27 Cont ID  
Sent By kstevens Date 2004-10-22 Time 18:27 Rev Time 0.10
Received By pkrauss Date 2004-10-27 Time 07:10 Sent To E
Notes
2004-10-27 00:00:00NO MECHANICAL WORK OR CONTRACTOR
 INDICATED WITH PERMIT APPLICATION.
 PLEASE PROVIDE PLANS WITH MECHANICAL
 PERMIT APPLICATION.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-06-28 Cont ID  
Sent By jleech Date 2005-06-28 Time 07:46 Rev Time 0.25
Received By jleech Date 2005-06-28 Time 07:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2004-10-22 Cont ID  
Sent By csiegber Date 2004-10-20 Time 16:28 Rev Time 0.25
Received By kstevens Date 2004-10-22 Time 18:26 Sent To M
Notes
2004-10-22 00:00:00NO PLUMBING PLANS SUBMITTED - WORK PER
 CITY CODES SUBJECT TO FIELD INSPECTORS
 APPROVAL

Review Stop Z ZONING
Rev No 1 Status P Date 2004-10-19 Cont ID  
Sent By csiegber Date 2004-10-04 Time 10:56 Rev Time 0.00
Received By mmclean Date 2004-10-19 Time 16:08 Sent To I
Notes
***NONE***