| Plan Review Stops For Permit 04100002 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2005-01-14 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-01-14 |
Time |
09:14 |
Rev Time |
1.11 |
| Received By |
jwitmer |
Date |
2005-01-14 |
Time |
09:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2004-12-03 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-12-03 |
Time |
10:54 |
Rev Time |
1.11 |
| Received By |
jwitmer |
Date |
2004-12-03 |
Time |
10:54 |
Sent To |
|
|
| Notes |
| 2004-12-03 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT:04100002 | | | ADD: 1801 S FLAGLER #703/704 | | | CONT:ROGER E. FRISHKORN | | | TEL: 818-6472 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | | | 2) THE PROPOSED BUILDING STRUCTURE | | | TRANSGRESSES LEGAL BOUNDARY LINES | | | BETWEEN THE LOTS WHICH COMBINE TO FORM | | | 'THE SITE'.A 'UNITY OF TITLE' SHALL BE | | | RECORDED AT THE COUNTY COURTHOUSE. | | | SUBMIT A COPY OF THE RECORDED 'UNITY OF | | | OF TITLE' DOCUMENT SO THAT FBC TABLE 600 | | | BOUNDARY LINE REQUIREMENTS MAY BE DEEMED | | | NOT APPLICABLE. | | | | | | 3) NOTE # 6 INDICATES THE OWNER TO PULL | | | | | | A SEPERATE PERMIT FOR REPLACEMENT OF | | | WINDOWS AND DOORS. CORRECT TO ONLY A | | | GENERAL CONTRACTOR TO BE ABLE TO PULL | | | THIS PERMIT!!FL S S 489.105 | | | DEFINITIONS. | | | | | | 4) INSPECTOR KEN CONRAD INSPECTS SITE | | | TO | | | VERIFY THE OPENING CUT THROUGH THE SHEER | | | WALL IS EXISTING. AS PER CONVERSATION | | | WITH INSPECTOR, A ENGINEERS LETTER WILL | | | BE REQUIRED VERIFYING THERE WILL BE NO | | | ADVERSE AFFECTS OF THIS OPENING IN THE | | | SHEERWALL. | | | 5) BATH# 2 INDICATES A REMOVAL OF TUB | | | AND A NEW SHOWER, IF THE DRAIN IS MOVED | | | AND FLOOR IS CUT OR DRILLED, THIS WILL | | | REQUIRE A "GENERAL CONTRACTOR", PART OF | | | THE STRUCTURE. | | | | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-10-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-10-22 |
Time |
15:50 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2004-10-22 |
Time |
15:50 |
Sent To |
|
|
| Notes |
| 2004-10-22 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04100002 | | | ADD: 1801 S FLAGLER DR# 703-704 | | | CONT: JOSEPH A. JORY CRC057758 | | | TEL: (561)818-6472 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1STREVIEW | | | ACTION: DENIED | | | | | | 1) CRC CONTRACTOR WORKING OUT OF SCOPE | | | LICENSE. 489.105(C) A CONTRACTOR WHOSE | | | SERVICES ARE LIMITED TO CONSTRUCTION , | | | REMODELING, REPAIR OR IMPROVEMENT OF ONE | | | FAMILY, TWO FAMILY, OR THREE FAMILY | | | RESIDENCES NOT EXCEEDING TWO HABITABLE | | | STORIES ABOVE NO MORE THAN ONE UNINHAB- | | | ITABLE STORY AND ACCESSORY USE STRUCTURE | | | IN CONNECTION THEREWITH. | | | | | | 2) PROVIDE A UNITY OF TITLE BETWEEN THE | | | CONDO UNITS. | | | | | | 3) FL BLD CODE 1606.1.5: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A) EXTERIOR SWING DOORS | | | B) SLIDING GLASS DOORS | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 4)704.2.1.4 CORRIDOR PARTITIONS, SMOKE | | | STOP PARTITIONS, HORIZONTAL EXIT PART- | | | ITIONS, EXIT ENCLOSURES, AND FIRE | | | RATED WALLS REQUIRED TO HAVE PROTECTED | | | OPENINGS SHALL BE EFFECTIVELY AND | | | PERMANETLY IDENTIFIED WITH SIGNS OR | | | STENCILING IN A MANNER ACCEPTABLE TO THE | | | AUTHORITY HAVING JURISDICTION. SUCH IDEN | | | TIFICATION SHALL BE ABOVE ANY DECORATIVE | | | CEILING CEILING AND IN CONCEALED SPACES. | | | SUGGESTED WORDING" FIRE & SMOKE BARRIER | | | PROTECT ALL OPENINGS". | | | | | | 5) TABLE 803.3 MINIMUM INTERIOR FINISH | | | CLASSIFICATION; PROVIDE INFORMATION | | | BASED ON INTERIOR FINISH REQUIREMENTS | | | BASED ON OCCUPANCY. | | | | | | LOOK FOR COMMENTS BY THE OTHER PLAN | | | REVIEW DISCIPLINES THAT MAY BE WRITTEN | | | ON THE APPLICATION, PLANS, OR ATTACHED | | | SEPARATELY. WHEN RESUBMITTING PLANS | | | PLEASE CLEARLY INDICATE THE REVISION AND | | | REMOVE AND REPLACE ANY PAGES AS NECESS- | | | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH | | | THE PLANS WHEN RESUBMITTING PLANS. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN | | | BE FOUND, WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | JIM WITMER | | | BUILDING PLAN REVIEW | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
N |
Date |
2005-01-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-01-11 |
Time |
11:55 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2005-01-11 |
Time |
11:55 |
Sent To |
|
|
| Notes |
| 2005-01-11 00:00:00 | REDLINED 210.11C3, | | | BATH GFI'S TO BE 20A #12. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2004-11-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-11-18 |
Time |
07:16 |
Rev Time |
0.75 |
| Received By |
dpalmer |
Date |
2004-11-18 |
Time |
06:59 |
Sent To |
|
|
| Notes |
| 2004-11-18 00:00:00 | ************ UNSAT 2ND REVIEW ********* | | | | | | PLEASE SEE SOME COMMENTS FROM PREVIOUS | | | REVIEW STILL NEED TO BE ADDRESSED. | | | | | | | | | 1)NOTE: PLEASE SEE 210.52D FOR RECEPT | | | SPACING IN BATHRMS. ALL GFI'S ARE TO BE | | | WITHIN 3' OF SINK EDGE. | | | PLEASE SEE PREVIOUS NOTE# 5 | | | | | | 2)NOTE: PLEASE SHOW ALL CIRCUITING ON | | | PLANS. PLEASE SEE KITCHEN GFI AND SD'S | | | AND ANY OTHER POSSIBLE DEVICES. | | | | | | *** NEW COMMENTS DUE TO CHANGES IN PLANS | | | AND COMPLETE SUBMITTAL. *** | | | | | | | | | | | | | | | 1) NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | | | | 2)NOTE: PLEASE SEE LOAD CALCULATIONS | | | WHICH SHOWS 20KW OF HEAT FOR A/C ON EACH | | | PANEL, YET PANEL SCHEDULE SHOWS 2-2POLE | | | 30'S ? PLEASE ALSO SEE MECH PLANS WHICH | | | SHOWS A DIFFERENT LOAD FOR A/C UNIT | | | HEAT. | | | PLEASE ALSO SEE CIRCUITING ON PLANS FOR | | | A/C AHU'S ALSO. | | | ALL OF THESE NEED TO CORRELATE. | | | | | | 3)NOTE: PLEASE SEE 220.31B FOR LOAD | | | CALCULATIONS. PLEASE ADJUST. | | | | | | 4)NOTE: PLEASE SEE MAINS ARE SHOWN AS | | | 3-POLE BRKR DISC'S, HOWEVER SERVICE IS | | | SHOWN AS SINGLE PHASE?? | | | PLEASE CORRELATE. | | | | | | 5)NOTE: PLEASE SEE 210.52B1, | | | 220.16,210.11C1 FOR CIRCUITING OF DINING | | | RM RECEPTS. | | | | | | 6)NOTE: PLEASE SHOW A DEVICE/FIXTURE | | | LEGEND. ANY RECESSED FIXTURES SHOULD BE | | | SHOWN WITH MAX WATTAGE. 220.3B4 | | | | | | 7)NOTE: PLEASE SEE ATTACHED COPY OF FS | | | 553.80(2)(B) WITH RESPECT TO DESIGN | | | PROFESSIONAL FOR REPEATED COMMENTS. | | | THIS IS ONLY A NOTICE GIVEN AT THIS | | | TIME. | | | | | | PLEASE SEE ANY COMMENTS FROM ANY OTHER | | | REVIEWERS WHICH MAY AFFECT ELECTRICAL | | | PLANS. | | | PLEASE REMOVE ALL OLD SHEETS AND INSERT | | | NEW SHEETS INTO COMPLETE SETS FOR REVIEW | | | AND STAMPING. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-10-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-10-06 |
Time |
17:56 |
Rev Time |
0.75 |
| Received By |
dpalmer |
Date |
2004-10-06 |
Time |
17:56 |
Sent To |
|
|
| Notes |
| 2004-10-06 00:00:00 | ************* UNSAT ***************** | | | | | | 1)NOTE: PLEASE SEE THERE ARE TWO SHEET | | | E-1 AND E-2 IN EACH SET WITH ALL FOUR | | | SHEETS SHOWING THE SAME THING? | | | PLEASE SUBMIT TWO COMPLETE SETS FOR | | | REVIEW AND STAMPING. | | | | | | 2)NOTE: PLEASE SHOW ALL CIRCUITING ON | | | PLANS AND CORRELATE WITH PANEL SCHEDULE | | | (S) TO BE SUBMITTED SHOWING ALL MIN | | | CIRCUITS ETC TO MEET 2002 NEC. | | | PLEASE SHOW SIZE OF EXISTING PANELS/ | | | SERVICE. | | | SUBMIT LOAD CALCULATTIONS. | | | 215.5,220.31B | | | | | | 3)NOTE: PLEASE SEE 210.70 AND LS101 5-8 | | | FOR REQUIRED EGRESS LIGHTING FIXTURES. | | | PLEASE CORRELATE ELECTRICAL PLANS WITH | | | MECHANICAL PLANS. M-SHEETS SHOWS A FAN/ | | | LT UNIT, YET THIS IS NOT SHOWN ON E-PLAN | | | 'S. ELECTRICAL PLANS ONLY SHOW A J-BOX. | | | PLEASE SHOW ON ELECTRICAL PLANS IF IN | | | DESIGN. | | | | | | 4) NOTE: PLEASE SHOW ALL RECEPTS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED PER 210.8A-6 | | | | | | 5) NOTE: PLEASE LIST ALL THE REQ'D | | | DEDICATED BATH(S) CIRCUIT(S) ON PANEL | | | SCHEDULE. PER 210.52D, 210.11C3 | | | PLEASE ALSO SEE RECEPTS REQUIRED TO BE | | | W/IN 3'OF LAV/SINK. | | | PLEASE ALSO SEE IT IS NOT PERMITTED TO | | | CROSS OVER A SINK TO PLUG INTO A RECEPT. | | | GFI TO BE MOVED TO CENTER OF TWO SINKS | | | OR ADD AN ADDITIONAL RECEPT. | | | | | | 6)NOTE: PLEASE SEE FBC CHAPTER 34 | | | 3404.7.2.6 | | | | | | 7)NOTE: PLEASE SEE 408.7,240.24D, PANEL | | | NOT PERMITTED IN CLOTHES CLOSET. | | | | | | 8)NOTE: PLEASE SEE 210.52 FOR MISSING | | | RECEPT ON 2' OF WALL SPACE. BEDRM #1 | | | | | | PLEASE SEE POSSIBLE COMMENTS FROM OTHER | | | REVIEWERS WHICH MAY AFFECT ELECTRICAL | | | PLANS. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW SHEETS INTO TWO COMPLETE | | | SETS FOR REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2005-01-18 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2005-01-18 |
Time |
10:41 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2005-01-18 |
Time |
10:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2004-11-01 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2004-11-01 |
Time |
14:50 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2004-11-01 |
Time |
14:45 |
Sent To |
|
|
| Notes |
| 2004-11-01 00:00:00 | 1) DEMOLITION, RENOVATION AND | | | CONSTRUCTION TO COMPLY WITH NFPA 241. | | | | | | 2) ALL CONSTRUCTION DEBRIS MUST BE | | | REMOVED DAILY. | | | | | | 3) PLEASE INDICATE THE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | | | | | | NATE MCCRAY, CAPTAIN | | | 561-835-2910 OR 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2005-01-31 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-01-31 |
Time |
13:33 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2005-01-31 |
Time |
13:33 |
Sent To |
M |
|
| Notes |
| 2005-01-31 00:00:00 | TO "M/AC" BOX/AS BUILTS. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-01-10 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-01-10 |
Time |
08:17 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2005-01-10 |
Time |
08:16 |
Sent To |
|
|
| Notes |
| 2005-01-10 00:00:00 | TO "COMM BD#52" /RESUB. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-01-10 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2004-11-17 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2004-11-16 |
Time |
16:09 |
Sent To |
|
|
| Notes |
| 2004-11-16 00:00:00 | SENT TO COMM BD#30 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-11-12 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-11-12 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-11-12 |
Time |
14:31 |
Sent To |
|
|
| Notes |
| 2004-11-12 00:00:00 | TO COMM BD# |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-11-12 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-11-01 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-10-05 |
Time |
15:24 |
Sent To |
|
|
| Notes |
| 2004-10-05 00:00:00 | TO COMM BD#64 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2005-01-18 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-01-18 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
prafter |
Date |
2005-02-03 |
Time |
12:10 |
Sent To |
|
|
| Notes |
| 2005-02-03 00:00:00 | AS BUILT H.V.A.C. DRAWING OK, A/C | | | PLANS PUT WITH BUILDING PLANS IN FILE, | | | 04100002. | | | 2/3/05 PR. | | 2005-01-18 00:00:00 | PROVISO: | | | BY HAROLD MOSER/1ST REVIEW DATED | | | 12-04-04: | | | PER 2001 FBC(M)602.2.1, PVC IS NOT | | | ACCEPTABLE IN THE RETURN AIR PLENUM AS | | | INDICATED ON PLAN SHEET P-2 NOTE#4. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT HAROLD MOSER (561)805-6732. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2004-12-04 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2004-12-04 |
Time |
|
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2004-12-04 |
Time |
|
Sent To |
|
|
| Notes |
| 2004-12-04 00:00:00 | PASS WITH PRIVISO SEE NOTES ON PAGE | | | M-1. | | | REFER TO SECTION 602.2.1 FLORIDA | | | BUILDING CODE (MECHANICAL).P.V.C IS NOT | | | EXCEPTABLE IN RETURN AIR PLENUMS.AS PER | | | NOTE #4 ON PAGE P-2 | | | PLAN REVIEW BY HAROLD MOSER | | | (561)805-6732 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2004-10-26 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-10-26 |
Time |
11:14 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2004-10-26 |
Time |
10:35 |
Sent To |
|
|
| Notes |
| 2004-10-26 00:00:00 | DENIED: | | | 1.PLAN SHEET M-2 HVAC GENERAL NOTES | | | #2, "INSTALLATION OF SUPPLY/RETURN AIR | | | PLENUM SLOTS LOCATED IN THE CROWN | | | MOLDINGS".PLAN SHEET M-1 DOES NOT | | | INDICATE ANY RETURN AIR GRILLES.PER | | | 2001 FBC(M) 601.4, RETURN AIR REQUIRED | | | FROM ALL HABITABLE AREAS ISOLATED FROM | | | THE RETURN AIR. | | | | | | 2.AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIRED PER 2001 FBC(M) | | | 307.2.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2004-12-09 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-12-09 |
Time |
07:29 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2004-12-09 |
Time |
07:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2004-10-25 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-10-25 |
Time |
10:57 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2004-10-25 |
Time |
10:57 |
Sent To |
|
|
| Notes |
| 2004-10-25 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1) SHOW THE LOCATION OF THE WASH MACHINE | | | CONNECTION REQUIRED BY TABLE 403.1 | | | 2) SHT P-3 SANITARY RISER #4, ONLY THE | | | FIXTURES WITHIN THE BATHROOM GROUP SHALL | | | CONNECT TO THE WET-VENTED HORIZONTAL | | | BRANCH DRAIN. THE BAR SINK IN THE ENTRY | | | SHALL DISCHARGE DOWNSTREAM OF THE WET | | | VENT. SECTION 909.1 | | | 3) ALL SHEETS, THE DATE THE ARCHITECT | | | SIGNS AND SEALS THE PLANS SHALL BE ON | | | THE SEAL. FAC 6161-16.003 & FAC 61G1-16. | | | 004(5). FS 481.2055 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|