Plan Review Details - Permit 04100002
Plan Review Stops For Permit 04100002
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-01-14 Cont ID  
Sent By jwitmer Date 2005-01-14 Time 09:14 Rev Time 1.11
Received By jwitmer Date 2005-01-14 Time 09:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-12-03 Cont ID  
Sent By jwitmer Date 2004-12-03 Time 10:54 Rev Time 1.11
Received By jwitmer Date 2004-12-03 Time 10:54 Sent To  
Notes
2004-12-03 00:00:00BUILDING PLAN REVIEW
 PERMIT:04100002
 ADD: 1801 S FLAGLER #703/704
 CONT:ROGER E. FRISHKORN
 TEL: 818-6472
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'.A 'UNITY OF TITLE' SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE.
 SUBMIT A COPY OF THE RECORDED 'UNITY OF
 OF TITLE' DOCUMENT SO THAT FBC TABLE 600
 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
  
 3) NOTE # 6 INDICATES THE OWNER TO PULL
  
 A SEPERATE PERMIT FOR REPLACEMENT OF
 WINDOWS AND DOORS. CORRECT TO ONLY A
 GENERAL CONTRACTOR TO BE ABLE TO PULL
 THIS PERMIT!!FL S S 489.105
 DEFINITIONS.
  
 4) INSPECTOR KEN CONRAD INSPECTS SITE
 TO
 VERIFY THE OPENING CUT THROUGH THE SHEER
 WALL IS EXISTING. AS PER CONVERSATION
 WITH INSPECTOR, A ENGINEERS LETTER WILL
 BE REQUIRED VERIFYING THERE WILL BE NO
 ADVERSE AFFECTS OF THIS OPENING IN THE
 SHEERWALL.
 5) BATH# 2 INDICATES A REMOVAL OF TUB
 AND A NEW SHOWER, IF THE DRAIN IS MOVED
 AND FLOOR IS CUT OR DRILLED, THIS WILL
 REQUIRE A "GENERAL CONTRACTOR", PART OF
 THE STRUCTURE.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-10-22 Cont ID  
Sent By jwitmer Date 2004-10-22 Time 15:50 Rev Time 2.22
Received By jwitmer Date 2004-10-22 Time 15:50 Sent To  
Notes
2004-10-22 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04100002
 ADD: 1801 S FLAGLER DR# 703-704
 CONT: JOSEPH A. JORY CRC057758
 TEL: (561)818-6472
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1) CRC CONTRACTOR WORKING OUT OF SCOPE
 LICENSE. 489.105(C) A CONTRACTOR WHOSE
 SERVICES ARE LIMITED TO CONSTRUCTION ,
 REMODELING, REPAIR OR IMPROVEMENT OF ONE
 FAMILY, TWO FAMILY, OR THREE FAMILY
 RESIDENCES NOT EXCEEDING TWO HABITABLE
 STORIES ABOVE NO MORE THAN ONE UNINHAB-
 ITABLE STORY AND ACCESSORY USE STRUCTURE
 IN CONNECTION THEREWITH.
  
 2) PROVIDE A UNITY OF TITLE BETWEEN THE
 CONDO UNITS.
  
 3) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EXTERIOR SWING DOORS
 B) SLIDING GLASS DOORS
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 5) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2005-01-11 Cont ID  
Sent By dpalmer Date 2005-01-11 Time 11:55 Rev Time 0.33
Received By dpalmer Date 2005-01-11 Time 11:55 Sent To  
Notes
2005-01-11 00:00:00REDLINED 210.11C3,
 BATH GFI'S TO BE 20A #12.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-11-18 Cont ID  
Sent By dpalmer Date 2004-11-18 Time 07:16 Rev Time 0.75
Received By dpalmer Date 2004-11-18 Time 06:59 Sent To  
Notes
2004-11-18 00:00:00************ UNSAT 2ND REVIEW *********
  
 PLEASE SEE SOME COMMENTS FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
  
  
 1)NOTE: PLEASE SEE 210.52D FOR RECEPT
 SPACING IN BATHRMS. ALL GFI'S ARE TO BE
 WITHIN 3' OF SINK EDGE.
 PLEASE SEE PREVIOUS NOTE# 5
  
 2)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS. PLEASE SEE KITCHEN GFI AND SD'S
 AND ANY OTHER POSSIBLE DEVICES.
  
 *** NEW COMMENTS DUE TO CHANGES IN PLANS
 AND COMPLETE SUBMITTAL. ***
  
  
  
  
 1) NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2)NOTE: PLEASE SEE LOAD CALCULATIONS
 WHICH SHOWS 20KW OF HEAT FOR A/C ON EACH
 PANEL, YET PANEL SCHEDULE SHOWS 2-2POLE
 30'S ? PLEASE ALSO SEE MECH PLANS WHICH
 SHOWS A DIFFERENT LOAD FOR A/C UNIT
 HEAT.
 PLEASE ALSO SEE CIRCUITING ON PLANS FOR
 A/C AHU'S ALSO.
 ALL OF THESE NEED TO CORRELATE.
  
 3)NOTE: PLEASE SEE 220.31B FOR LOAD
 CALCULATIONS. PLEASE ADJUST.
  
 4)NOTE: PLEASE SEE MAINS ARE SHOWN AS
 3-POLE BRKR DISC'S, HOWEVER SERVICE IS
 SHOWN AS SINGLE PHASE??
 PLEASE CORRELATE.
  
 5)NOTE: PLEASE SEE 210.52B1,
 220.16,210.11C1 FOR CIRCUITING OF DINING
 RM RECEPTS.
  
 6)NOTE: PLEASE SHOW A DEVICE/FIXTURE
 LEGEND. ANY RECESSED FIXTURES SHOULD BE
 SHOWN WITH MAX WATTAGE. 220.3B4
  
 7)NOTE: PLEASE SEE ATTACHED COPY OF FS
 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONAL FOR REPEATED COMMENTS.
 THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
 PLEASE SEE ANY COMMENTS FROM ANY OTHER
 REVIEWERS WHICH MAY AFFECT ELECTRICAL
 PLANS.
 PLEASE REMOVE ALL OLD SHEETS AND INSERT
 NEW SHEETS INTO COMPLETE SETS FOR REVIEW
 AND STAMPING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-10-06 Cont ID  
Sent By dpalmer Date 2004-10-06 Time 17:56 Rev Time 0.75
Received By dpalmer Date 2004-10-06 Time 17:56 Sent To  
Notes
2004-10-06 00:00:00************* UNSAT *****************
  
 1)NOTE: PLEASE SEE THERE ARE TWO SHEET
 E-1 AND E-2 IN EACH SET WITH ALL FOUR
 SHEETS SHOWING THE SAME THING?
 PLEASE SUBMIT TWO COMPLETE SETS FOR
 REVIEW AND STAMPING.
  
 2)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL SCHEDULE
 (S) TO BE SUBMITTED SHOWING ALL MIN
 CIRCUITS ETC TO MEET 2002 NEC.
 PLEASE SHOW SIZE OF EXISTING PANELS/
 SERVICE.
 SUBMIT LOAD CALCULATTIONS.
 215.5,220.31B
  
 3)NOTE: PLEASE SEE 210.70 AND LS101 5-8
 FOR REQUIRED EGRESS LIGHTING FIXTURES.
 PLEASE CORRELATE ELECTRICAL PLANS WITH
 MECHANICAL PLANS. M-SHEETS SHOWS A FAN/
 LT UNIT, YET THIS IS NOT SHOWN ON E-PLAN
 'S. ELECTRICAL PLANS ONLY SHOW A J-BOX.
 PLEASE SHOW ON ELECTRICAL PLANS IF IN
 DESIGN.
  
 4) NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
  
 5) NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
 PLEASE ALSO SEE RECEPTS REQUIRED TO BE
 W/IN 3'OF LAV/SINK.
 PLEASE ALSO SEE IT IS NOT PERMITTED TO
 CROSS OVER A SINK TO PLUG INTO A RECEPT.
 GFI TO BE MOVED TO CENTER OF TWO SINKS
 OR ADD AN ADDITIONAL RECEPT.
  
 6)NOTE: PLEASE SEE FBC CHAPTER 34
 3404.7.2.6
  
 7)NOTE: PLEASE SEE 408.7,240.24D, PANEL
 NOT PERMITTED IN CLOTHES CLOSET.
  
 8)NOTE: PLEASE SEE 210.52 FOR MISSING
 RECEPT ON 2' OF WALL SPACE. BEDRM #1
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWERS WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO TWO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-01-18 Cont ID  
Sent By nmccray Date 2005-01-18 Time 10:41 Rev Time 0.00
Received By nmccray Date 2005-01-18 Time 10:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-11-01 Cont ID  
Sent By nmccray Date 2004-11-01 Time 14:50 Rev Time 0.00
Received By nmccray Date 2004-11-01 Time 14:45 Sent To  
Notes
2004-11-01 00:00:001) DEMOLITION, RENOVATION AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2) ALL CONSTRUCTION DEBRIS MUST BE
 REMOVED DAILY.
  
 3) PLEASE INDICATE THE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-01-31 Cont ID  
Sent By mjacobs Date 2005-01-31 Time 13:33 Rev Time 0.00
Received By mjacobs Date 2005-01-31 Time 13:33 Sent To M
Notes
2005-01-31 00:00:00TO "M/AC" BOX/AS BUILTS.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-01-10 Cont ID  
Sent By mjacobs Date 2005-01-10 Time 08:17 Rev Time 0.00
Received By mjacobs Date 2005-01-10 Time 08:16 Sent To  
Notes
2005-01-10 00:00:00TO "COMM BD#52" /RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-01-10 Cont ID  
Sent By mjacobs Date 2004-11-17 Time 11:04 Rev Time 0.00
Received By mjacobs Date 2004-11-16 Time 16:09 Sent To  
Notes
2004-11-16 00:00:00SENT TO COMM BD#30

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-11-12 Cont ID  
Sent By csiegber Date 2004-11-12 Time 14:31 Rev Time 0.00
Received By csiegber Date 2004-11-12 Time 14:31 Sent To  
Notes
2004-11-12 00:00:00TO COMM BD#

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-11-12 Cont ID  
Sent By csiegber Date 2004-11-01 Time 14:30 Rev Time 0.00
Received By csiegber Date 2004-10-05 Time 15:24 Sent To  
Notes
2004-10-05 00:00:00TO COMM BD#64

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-01-18 Cont ID  
Sent By pkrauss Date 2005-01-18 Time 15:42 Rev Time 0.00
Received By prafter Date 2005-02-03 Time 12:10 Sent To  
Notes
2005-02-03 00:00:00AS BUILT H.V.A.C. DRAWING OK, A/C
 PLANS PUT WITH BUILDING PLANS IN FILE,
 04100002.
 2/3/05 PR.
2005-01-18 00:00:00PROVISO:
 BY HAROLD MOSER/1ST REVIEW DATED
 12-04-04:
 PER 2001 FBC(M)602.2.1, PVC IS NOT
 ACCEPTABLE IN THE RETURN AIR PLENUM AS
 INDICATED ON PLAN SHEET P-2 NOTE#4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT HAROLD MOSER (561)805-6732.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-12-04 Cont ID  
Sent By hmoser Date 2004-12-04 Time   Rev Time 0.00
Received By hmoser Date 2004-12-04 Time   Sent To  
Notes
2004-12-04 00:00:00PASS WITH PRIVISO SEE NOTES ON PAGE
 M-1.
 REFER TO SECTION 602.2.1 FLORIDA
 BUILDING CODE (MECHANICAL).P.V.C IS NOT
 EXCEPTABLE IN RETURN AIR PLENUMS.AS PER
 NOTE #4 ON PAGE P-2
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-10-26 Cont ID  
Sent By pkrauss Date 2004-10-26 Time 11:14 Rev Time 0.30
Received By pkrauss Date 2004-10-26 Time 10:35 Sent To  
Notes
2004-10-26 00:00:00DENIED:
 1.PLAN SHEET M-2 HVAC GENERAL NOTES
 #2, "INSTALLATION OF SUPPLY/RETURN AIR
 PLENUM SLOTS LOCATED IN THE CROWN
 MOLDINGS".PLAN SHEET M-1 DOES NOT
 INDICATE ANY RETURN AIR GRILLES.PER
 2001 FBC(M) 601.4, RETURN AIR REQUIRED
 FROM ALL HABITABLE AREAS ISOLATED FROM
 THE RETURN AIR.
  
 2.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-12-09 Cont ID  
Sent By kstevens Date 2004-12-09 Time 07:29 Rev Time 0.50
Received By kstevens Date 2004-12-09 Time 07:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-10-25 Cont ID  
Sent By kstevens Date 2004-10-25 Time 10:57 Rev Time 1.00
Received By kstevens Date 2004-10-25 Time 10:57 Sent To  
Notes
2004-10-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHOW THE LOCATION OF THE WASH MACHINE
 CONNECTION REQUIRED BY TABLE 403.1
 2) SHT P-3 SANITARY RISER #4, ONLY THE
 FIXTURES WITHIN THE BATHROOM GROUP SHALL
 CONNECT TO THE WET-VENTED HORIZONTAL
 BRANCH DRAIN. THE BAR SINK IN THE ENTRY
 SHALL DISCHARGE DOWNSTREAM OF THE WET
 VENT. SECTION 909.1
 3) ALL SHEETS, THE DATE THE ARCHITECT
 SIGNS AND SEALS THE PLANS SHALL BE ON
 THE SEAL. FAC 6161-16.003 & FAC 61G1-16.
 004(5). FS 481.2055
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]