Plan Review Details - Permit 04090891
Plan Review Stops For Permit 04090891
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-04-29 Cont ID  
Sent By adarroug Date 2005-04-29 Time 18:07 Rev Time 0.00
Received By adarroug Date 2005-04-29 Time 18:07 Sent To M
Notes
2005-04-29 00:00:00TO "PKRAUSS" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-02-23 Cont ID  
Sent By adarroug Date 2005-02-23 Time 15:52 Rev Time 0.00
Received By adarroug Date 2005-02-23 Time 15:52 Sent To M
Notes
2005-02-23 00:00:00TO "M" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-10-04 Cont ID  
Sent By csiegber Date 2004-10-04 Time 09:15 Rev Time 0.00
Received By adarroug Date 2005-02-23 Time 15:49 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-05-05 Cont ID  
Sent By prafter Date 2005-05-05 Time 09:10 Rev Time 0.50
Received By prafter Date 2005-05-05 Time 09:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-03-30 Cont ID  
Sent By pkrauss Date 2005-03-30 Time 07:44 Rev Time 0.35
Received By pkrauss Date 2005-03-30 Time 07:43 Sent To  
Notes
2005-03-30 00:00:00PROVISO:
 RETURN AIR SHALL BE DUCTED INTO THE
 LIVING AREA.AIR FROM THE BATHROOM AREA
 SHALL NOT BE RECIRCULATED, RETURN AIR
 SHALL NOT BE LOCATED IN THE BATHROOM
 AREA.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-10-05 Cont ID  
Sent By csiegber Date 2004-10-04 Time 09:15 Rev Time 0.35
Received By pkrauss Date 2004-10-05 Time 08:56 Sent To  
Notes
2004-10-05 00:00:00PROVISO:
 PER CONVERSATION WITH SCOTT O'DONNELL,
 TRANSFER GRILLES ARE TO BE INSTALLED IN
 THE BEDROOM AREAS.TRANSFER GRILLE
 SHALL A MINIMUM OF 50 SQ INCHES TO 100
 100 CFM OF SUPPLY AIR TO THAT SPACE.